12.3 In the case motor does not run in spite of no trip message appearing ...

When the motor does not run in spite of no trip message appearing on the display, proceed to troubleshooting according to the following flowchart.

Motor does not run.

YES : NO :

Is 7-segment LED display turned on?

Check input power and MCCB.

Is input power

 

Input power

correct?

 

supply correctly.

 

 

 

Make a service call.

Is  blinking?

Main circuit power is undervoltage. If input voltage or DC reactor (DCL) voltage is low, check the connection.

For monitoring input voltage, refer to the section 8.1.

Is  blinking?

Control power is undervoltage. Check input voltage and connection of control power supply. (This is an option for the 22 kW or lower type.)

Is blinking?

 

 

Circuit between ST and CC is open. Close the circuit between the

 

 

 

 

 

terminal assigned as ST (standby) and CC of the control terminal

 

 

 

board, (Refer to 7.2.1)

 

 

 

Change setting value of ST (standby) signal selection parameter

 

 

 

. (Refer to 6.2.1)

Is trip indication appearing?

 

 

 

 

 

 

(Refer to 12.1.)

 

 

Investigate the cause of failure and remove the cause before

 

 

 

 

 

resetting the inverter. For resetting, refer to the section 12.2.

 

 

 

 

 

 

 

and trip indication are appearing alternately?

The inverter is in retry operation. Retry operation discontinues if stop or emergency stop operation is done or power supply is cut off.

 

 

 

In case of control panel operation: Turn on the RUN key to continue operation.

 

Is LED on

 

 

Check to see if control panel operation frequency is set or not. (Refer to 3.2.2)

 

RUN/STOP key

 

 

In other operation mode: Change setting of control device selection parameter

 

 

 

.(Refer to 3.2.1)

 

turned on?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In case of control panel operation: Change setting of control device

 

 

 

 

selection parameter to "1". (Refer to 5.3.)

 

 

 

 

Setup status of input terminals can be checked by the monitor. (Refer to

 

 

 

 

8.1.)

 

 

 

 

 

 

 

In other operation mode: Check to see if external operation command is

 

 

 

 

input.

 

 

 

 

Check setup contents of parameter (selection of operation to

 

 

 

 

which priority is given when forward and reverse run commands are input

 

 

 

 

simultaneously). (Refer to 6.2.2.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is appearing on

 

 

 

Check to see if frequency setting signal is set at "0".

display?

 

 

 

Check setup contents of frequency setting signal parameters

 

 

 

 

 

 

, , and . (Refer to 5.3.)

 

 

 

 

 

 

Check setting of points 1 and 2 of frequency setting signal.

 

 

 

 

 

 

(Refer to 7.3.)

 

 

 

 

 

 

Check to see if operation start frequency is set higher than operation

 

 

 

 

 

 

frequency. (Refer to 6.7.)

 

 

 

 

 

 

Check to see if frequency (preset-speed operation frequency, etc.) is

 

 

 

 

 

 

set at "0".

 

 

 

 

 

 

Check to see if the motor is loaded too heavily or locked. - Reduce

 

 

 

 

 

 

load to the motor.

 

 

 

 

 

 

 

 

 

Check contents of parameters and indications appearing on the monitor.

For table of parameters and monitor indications, refer to the articles 10 and 8 respectively.

L-6

Page 243
Image 243
Toshiba VF-A7 Is input power Input power Correct?, Make a service call, Is LED on, RUN/STOP key, Turned on?