7.2 Applied operation with input and output signals (operation by the terminal board)

7. 2. 1 Functions of input terminals (in case of sink logic)

Signals that are supplied to control input terminals from the programmable controller, etc. are used to operate or set up the inverter.

Since function of each contact input terminal is selectable from 136 functions, this inverter makes it possible to design a system flexibly.

[Control terminal board]

 

RES

S1

 

S2

 

S3

 

S4

 

RX

II

AM

 

FP

OUT2

 

F

R

ST

CC

CC

RR VPP

FM OUT1 P2

FL FLB FL

■Setting of contact input terminal function

Terminal

Title

Function

Adjustment

Default setting

range

 

 

 

 



Always active function selection

 

 (No assignment

 

function)

 

 

 

 

F



Input terminal selection #1 (F)



 (Forward rotation)

R



Input terminal selection #2 (R)

 (Reverse rotation)

 

ST



Input terminal selection #3 (ST)

(Refer to

 (Standby)

RES



Input terminal selection #4 (RES)

 (Reset)

page G-4.)

S1



Input terminal selection #5 (S1)

 (Preset speed #1)

S2



Input terminal selection #6 (S2)

 

 (Preset speed #2)

S3



Input terminal selection #7 (S3)

 

 (Preset speed #3)

S4



Input terminal selection #8 (S4)

 

 (Preset speed #4)

Option



Input terminal selection #9#16

 

Note:When (Always active function selection) is selected, selected function is generally activated regardless of positive or negative logic.

Note:is for use of expansion TB option unit.

■Connection method

1) In case of positive logic (a-contact) input

Inverter

a-contact switch

Input

 

terminal

 

CC

2)In case of negative logic (b-contact) input

Inverter

b-contact switch

Input

 

terminal

 

CC

This function is activated when the input terminal and CC (common) are short-circuit, and it is used for forward rotation, reverse rotation, preset speed operation, etc.

This function is activated when the input terminal and CC (common) are open-circuit, and it is used for standby signal, reset signal, etc.

G-2

Page 169
Image 169
Toshiba VF-A7 Functions of input terminals in case of sink logic, Control terminal board, Connection method