5.5 Factory default setting



Standard setting mode selection

Function

This parameter is to set two or more parameters at a time for different commands. Using this parameter, all parameters can be also return to their respective default settings by one operation, and save or set specific parameters individually.

Title

Function

Adjustment range

Default setting

 

 

: -

 

 

 

: 50Hz standard setting

 

 

 

: 60Hz standard setting

 



Standard setting

: Factory default setting

mode selection

: Trip clear

 

: Clearing accumulating operation time

 

 

 

 

 

 

: Initialization of type form information

 

 

 

: Memorization of user-defined parameters

 

 

 

: Reset of user-defined parameters

 

This parameter is used to change the settings of other parameters. Therefore, 0 is always displayed. This parameter cannot be used when the inverter is in operation. So, put the inverter out of operation

before using this parameter.

You can check the previous settings by selecting  last set data in status monitor mode. (Refer to 8.1 for details.)

[Set value]

[ 50 Hz standard setting (  = ) ]

Setting at  causes all the following parameters to be set for operation using a base frequency of 50Hz.(This does not change the settings of any other parameters.)

Maximum frequency : 50Hz

VI/II reference point #2 frequency : 50Hz

Base frequency #1 : 50Hz

RR reference point #2 frequency : 50Hz

Base frequency #2 : 50Hz

RX reference point #2 frequency : 50Hz

Base frequency #3 : 50Hz

RX2 reference point #2 frequency : 50Hz

Base frequency #4 : 50Hz

BIN reference point #2 frequency : 50Hz

Upper limit frequency : 50Hz

Pulse reference point #2 frequency : 50Hz

Forward speed limit input level : 50Hz Point #2 frequency : 50Hz

Reverse speed limit input level : 50Hz

Automatic light-load high-speed operation frequency : 50Hz

Commercial power/inverter switching frequency : 50Hz

[ 60 Hz standard setting (  = ) ]

Setting  at  causes all the following parameters to be set for operation using a base frequency of 60Hz.(This does not change the settings of any other parameters.)

Maximum frequency : 60Hz

VI/II reference point #2 frequency : 60Hz

Base frequency #1 : 60Hz

RR reference point #2 frequency : 60Hz

Base frequency #2 : 60Hz

RX reference point #2 frequency : 60Hz

Base frequency #3 : 60Hz

RX2 reference point #2 frequency : 60Hz

Base frequency #4 : 60Hz

BIN reference point #2 frequency : 60Hz

Upper limit frequency : 60Hz

Pulse reference point #2 frequency : 60Hz

Forward speed limit input level : 60Hz Point #2 frequency : 60Hz

Reverse speed limit input level : 60Hz

Automatic light-load high-speed operation frequency : 60Hz

Commercial power/inverter switching frequency : 60Hz

E-13

Page 74