York YPAL 061, YPAL 050, YPAL 051, YPAL 060 manual Faults And Lockouts, Service

Models: YPAL 060 YPAL 051 YPAL 050 YPAL 061

1 168
Download 168 pages 27.04 Kb
Page 160
Image 160

Service

FORM 100.50-NOM6 (1207)

FAULTS AND LOCKOUTS

LIGHT EMITTING DIODE

ALARM CODES

The light emitting diode (LED) installed on the Unit Controller is used to indicate the functionality of the Unit Controller and the unit. Normal operation is indicated by the LED flashing ON and OFF at a rate of one-second. A one-second ON followed by a one- second OFF flash. This means there are no active flash codes, faults or clock-outs. However there may be faults recorded in the history buffer.

A flash rate of 250 ms ON and OFF indicates a current alarm is present. The alarm code number will also be flashing on the four-digit character display. See Table 8-9 for a description of each of the alarm codes.

If the LED is constantly on (does not flash), the board has failed and must be replaced. If the LED is OFF this indicates no power to the board or a board failure. Two flashes ON, then two-seconds OFF indicates the control is timing out on an Anti-Cycle-Delay (ASCD). To bypass theASCD timer depress the TEST/UP button 3 times within 5 seconds.

An active alarm is represented by a flashing alarm code numeral. There are 43 alarms in all. Not all the alarms are critical enough to shut down the system. Some alarms flag the problem to bring it to the attention of the operator or technician while allowing the system to continue to operate.

The display flashes the current or most recent code and contains the last five failures as well. To recall the last five failures from the most recent to the oldest of the five, press the “Alarm/Change” button once and each code is displayed for two seconds. Each failure code is numbered 1 to 5 and the number is shown in the two-digit character display located above the four- digit display.

The current and last five alarms can also be views under the “ALARM” tab using the Simplicity PC software.

A unit lockout can be reset in three ways:

Removing the 24 VAC supply to the Unit Con- troller.

Press the TEST/UP button twice in 5 seconds.

By a communicated command.

160

JOHNSON CONTROLS

Page 160
Image 160
York YPAL 061, YPAL 050, YPAL 051, YPAL 060 manual Faults And Lockouts, Service