TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
|
|
| INITIAL/ |
|
|
| |
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX | DESCRIPTION | |
(HEX) | (DEC) | VALUE | VALUE | VALUE | |||
|
| ||||||
|
|
| (HEX) |
|
|
| |
B4 H | 180 H |
| 70 | 50 | 85 | MORNING | |
| TEMPERATURE SETPOINT (DEGREES F) | ||||||
|
|
|
|
|
| ||
B5 H | 181 H |
| 60 | 0 | 200 | DUCT PRESSURE SETPOINT (0.025” WC INCREMENTS, DEFAULT | |
| = 1.500” WC « 60) | ||||||
|
|
|
|
|
| ||
B5 L | 181 L |
| 180 | 0 | 200 | DUCT PRESSURE SHUTDOWN SETPOINT (0.025” WC | |
| INCREMENTS, DEFAULT = 4.500” WC « 180) | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
B6 H | 182 H |
| 70 | 0 | 100 | BUILDING PRESSURE SETPOINT (0.005” WC INCREMENTS, 0 = | |
| |||||||
|
|
|
|
|
| ||
B7 H | 183 H |
| 55 | 40 | 65 | ECONOMIZER FIRST STAGE (UPPER) SETPOINT (DEGREES F) | |
B7 L | 183 L |
| 50 | 40 | 65 | ECONOMIZER SECOND STAGE (LOWER) SETPOINT (DEGREES F) | |
B8 H | 184 H |
| 20 | 0 | 100 | ECONOMIZER MINIMUM POSITION (PERCENT) | |
B9 H | 185 H |
| 27 | 10 | 50 | ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT (BTU PER | |
| POUND) | ||||||
|
|
|
|
|
| ||
B9 L | 185 L |
| 27 | 10 | 50 | ECONOMIZER RETURN AIR ENTHALPY SETPOINT (BTU PER | |
| POUND) | ||||||
|
|
|
|
|
| ||
BA H | 186 H |
| 55 | 40 | 80 | ECONOMIZER OUTSIDE AIR TEMPERATURE ENABLE SETPOINT | |
| (DEGREES F) | ||||||
|
|
|
|
|
| ||
BB H | 187 H |
| 4 | 0 | 23 | ||
|
|
|
|
|
|
| |
BB L | 187 L |
| 0 | 0 | 59 | ||
BC H | 188 H |
| 80 | 10 | 100 | EXHAUST DAMPER POSITION FOR EXHAUST FAN TO TURN ON | |
| – MODULATING ONLY (PERCENT) | ||||||
|
|
|
|
|
| ||
BC L | 188 L |
| 20 | 0 | 90 | EXHAUST DAMPER POSITION FOR EXHAUST FAN TO TURN OFF | |
| – MODULATING ONLY (PERCENT) | ||||||
|
|
|
|
|
| ||
BD H | 189 H |
| 60 | 10 | 100 | ECONOMIZER DAMPER POSITION FOR EXHAUST FAN TO TURN | |
| ON – | ||||||
|
|
|
|
|
| ||
BD L | 189 L |
| 20 | 0 | 90 | ECONOMIZER DAMPER POSITION FOR EXHAUST FAN TO TURN | |
| OFF – | ||||||
|
|
|
|
|
| ||
BE H | 190 H |
| 0 | 0 | 80 | SUPPLY AIR TEMPERATURE ALARM SETPOINT FOR COOLING | |
| (DEGREES F, 0 = DISABLED) | ||||||
|
|
|
|
|
| ||
BE L | 190 L |
| 0 | 0 | 120 | SUPPLY AIR TEMPERATURE ALARM SETPOINT FOR HEATING | |
| (DEGREES F, 0 = DISABLED) | ||||||
|
|
|
|
|
| ||
BF H | 191 H |
| 5 | 0 | 25 | SPACE SENSOR ALARM TEMPERATURE (DEGREES F, 0 = | |
| DISABLED) | ||||||
|
|
|
|
|
| ||
BF L | 191 L |
| 60 | 0 | 120 | SPACE SENSOR ALARM TIME (MINUTES, 0 = DISABLED) | |
C2 H | 194 H |
| 0 | 0 | 255 | ||
C3 H | 195 H |
| - | - | - | ASCD TIMER FOR COMPRESSOR #1 HIGH BYTE | |
C3 L | 195 L |
| - | - | - | ASCD TIMER FOR COMPRESSOR #1 LOW BYTE. (SECONDS, | |
| COUNTS DOWN) | ||||||
|
|
|
|
|
| ||
C4 H | 196 H |
| - | - | - | ASCD TIMER FOR COMPRESSOR #2 HIGH BYTE | |
|
|
|
|
|
|
| |
C4 L | 196 L |
| - | - | - | ASCD TIMER FOR COMPRESSOR #2 LOW BYTE (SECONDS, | |
| COUNTS DOWN) | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
C5 H | 197 H |
| - | - | - | ASCD TIMER FOR COMPRESSOR #3 HIGH BYTE | |
C5 L | 197 L |
| - | - | - | ASCD TIMER FOR COMPRESSOR #3 LOW BYTE. (SECONDS, | |
| COUNTS DOWN) | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
| Continued on next page | |