User Interface Control Center

FORM 100.50-NOM6 (1207)

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

 

 

 

INITIAL/

 

 

 

ADDRESS

ADDRESS

BIT

DEFAULT

MIN

MAX

DESCRIPTION

(HEX)

(DEC)

VALUE

VALUE

VALUE

 

 

 

 

 

(HEX)

 

 

 

B4 H

180 H

 

70

50

85

MORNING WARM-UP AND VAV HEATING: RETURN AIR

 

TEMPERATURE SETPOINT (DEGREES F)

 

 

 

 

 

 

B5 H

181 H

 

60

0

200

DUCT PRESSURE SETPOINT (0.025” WC INCREMENTS, DEFAULT

 

= 1.500” WC « 60)

 

 

 

 

 

 

B5 L

181 L

 

180

0

200

DUCT PRESSURE SHUTDOWN SETPOINT (0.025” WC

 

INCREMENTS, DEFAULT = 4.500” WC « 180)

 

 

 

 

 

 

 

 

 

 

 

 

 

B6 H

182 H

 

70

0

100

BUILDING PRESSURE SETPOINT (0.005” WC INCREMENTS, 0 =

 

-0.250” WC, DEFAULT = 0.100” WC « 70)

 

 

 

 

 

 

B7 H

183 H

 

55

40

65

ECONOMIZER FIRST STAGE (UPPER) SETPOINT (DEGREES F)

B7 L

183 L

 

50

40

65

ECONOMIZER SECOND STAGE (LOWER) SETPOINT (DEGREES F)

B8 H

184 H

 

20

0

100

ECONOMIZER MINIMUM POSITION (PERCENT)

B9 H

185 H

 

27

10

50

ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT (BTU PER

 

POUND)

 

 

 

 

 

 

B9 L

185 L

 

27

10

50

ECONOMIZER RETURN AIR ENTHALPY SETPOINT (BTU PER

 

POUND)

 

 

 

 

 

 

BA H

186 H

 

55

40

80

ECONOMIZER OUTSIDE AIR TEMPERATURE ENABLE SETPOINT

 

(DEGREES F)

 

 

 

 

 

 

BB H

187 H

 

4

0

23

PRE-OCCUPANCY PURGE TIME (HOURS)

 

 

 

 

 

 

 

BB L

187 L

 

0

0

59

PRE-OCCUPANCY PURGE TIME (MINUTES)

BC H

188 H

 

80

10

100

EXHAUST DAMPER POSITION FOR EXHAUST FAN TO TURN ON

 

– MODULATING ONLY (PERCENT)

 

 

 

 

 

 

BC L

188 L

 

20

0

90

EXHAUST DAMPER POSITION FOR EXHAUST FAN TO TURN OFF

 

– MODULATING ONLY (PERCENT)

 

 

 

 

 

 

BD H

189 H

 

60

10

100

ECONOMIZER DAMPER POSITION FOR EXHAUST FAN TO TURN

 

ON – NON-MODULATING ONLY (PERCENT)

 

 

 

 

 

 

BD L

189 L

 

20

0

90

ECONOMIZER DAMPER POSITION FOR EXHAUST FAN TO TURN

 

OFF – NON-MODULATING ONLY (PERCENT)

 

 

 

 

 

 

BE H

190 H

 

0

0

80

SUPPLY AIR TEMPERATURE ALARM SETPOINT FOR COOLING

 

(DEGREES F, 0 = DISABLED)

 

 

 

 

 

 

BE L

190 L

 

0

0

120

SUPPLY AIR TEMPERATURE ALARM SETPOINT FOR HEATING

 

(DEGREES F, 0 = DISABLED)

 

 

 

 

 

 

BF H

191 H

 

5

0

25

SPACE SENSOR ALARM TEMPERATURE (DEGREES F, 0 =

 

DISABLED)

 

 

 

 

 

 

BF L

191 L

 

60

0

120

SPACE SENSOR ALARM TIME (MINUTES, 0 = DISABLED)

C2 H

194 H

 

0

0

255

INTELLI-START RECOVERY TIME (MINUTES, 0 = DISABLED)

C3 H

195 H

 

-

-

-

ASCD TIMER FOR COMPRESSOR #1 HIGH BYTE

C3 L

195 L

 

-

-

-

ASCD TIMER FOR COMPRESSOR #1 LOW BYTE. (SECONDS,

 

COUNTS DOWN)

 

 

 

 

 

 

C4 H

196 H

 

-

-

-

ASCD TIMER FOR COMPRESSOR #2 HIGH BYTE

 

 

 

 

 

 

 

C4 L

196 L

 

-

-

-

ASCD TIMER FOR COMPRESSOR #2 LOW BYTE (SECONDS,

 

COUNTS DOWN)

 

 

 

 

 

 

 

 

 

 

 

 

 

C5 H

197 H

 

-

-

-

ASCD TIMER FOR COMPRESSOR #3 HIGH BYTE

C5 L

197 L

 

-

-

-

ASCD TIMER FOR COMPRESSOR #3 LOW BYTE. (SECONDS,

 

COUNTS DOWN)

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page

138

 

 

 

 

 

JOHNSON CONTROLS

Page 138
Image 138
York YPAL 051, YPAL 061, YPAL 050, YPAL 060 manual 138