Startup

The supply, exhaust and return fans have tie down bolts are installed at the factory to prevent movement in the fan assemblies during shipment. THESE HOLD DOWN BOLTS MUST BE REMOVED PRIOR TO OPERATION OF THE ABOVE FANS. There are eight bolts per assembly two at each comer of the fan skids, front and rear. The bolt locations are shown in Figure 3-1. The bolt heads are red in color and a label identifies their location in the unit.

FORM 100.50-NOM6 (1207)

13.Verify proper belt tension of supply fan, exhaust fan or return fan (refer to Maintenance section of manual). Belts must be checked after 24 hours of initial operation.

14. Manually rotate condenser fan blades, supply exhaust and return blower wheels and motors, to assure freedom of movement.

15. Verify proper condensate drain trap installation (refer to Figure 2-6). Fill traps with water prior to unit start-up.

16. If applicable, verify installation of air filters (refer to Installation section for size and quantity).

 

EXHAUST FAN ASSEMBLY

Fan Hold

 

Brackets

 

 

Fan Hold Down Brackets (4)

 

LD13268

SUPPLY FAN ASSEMBLY

FIG. 3-1 – FAN HOLD DOWN BRACKETS

48

JOHNSON CONTROLS