1 -R410-A PRESSURE / TEMPERATURE CHART
Unit Placement
Maintenance
Shielded wire must be used that is grounded at the control panel only
Supply Air Temperature Reset
Cooling Setup
Remove the combustion vent assembly from the return compartment
Fault Output
The Simplicity Control then starts a 3 minute timer
Page 119
Image 119
FORM
100.50-NOM6
(1207)
SYSTEM OPTIONS
LD13024
6
JOHNSON CONTROLS
119
Page 118
Page 120
Page 119
Image 119
Page 118
Page 120
Contents
New Release
PACKAGED ROOFTOP AIR CONDITIONING UNITS
YPAL YPAL YPAL YPAL DESIGN LEVEL F SIMPLICITY ELITE CONTROL
INSTALLATION, OPERATION & MAINTENANCE
READ BEFORE PROCEEDING
GENERAL SAFETY GUIDELINES
SAFETY SYMBOLS
BASE MODEL NUMBER
CHANGEABILITY OF THIS DOCUMENT
NOMENCLATURE
TABLE OF CONTENTS
Thermostat
TABLE OF CONTENTS
INITIAL START-UP
TABLE OF CONTENTS
COOLING COMPRESSOR LOCKOUT
TABLE OF CONTENTS
VARIABLE AIR VOLUME VAV
CONDENSER FAN OPERATION
TABLE OF CONTENTS
“Supply Air Temp Alarm Setpoint for Cooling” Alarm
TABLE OF CONTENTS
“Supply Air Temp Alarm Setpoint for Heating” Alarm
“Economizer Minimum Position” Alarm
TABLE OF CONTENTS
LIST OF TABLES
LIST OF FIGURES
Condensing Section
SECTION 1 - INTRODUCTION
Steam and Hot water - This option will be available in the future
Introduction
Heating Section
INDOOR AIR QUALITY
AIR MANAGEMENT
CONTROLS
Gas Heat Sections - Are factory and leaked checked
Introduction
If the VAV boxes in the conditioned
SECTION 2 - INSTALLATION
installed, it is the responsibility of the
installing contractor to take appropri
Installation
Proper rigging and handling of the equipment is
Center of Gravity
UNIT WEIGHTS
Installation
TABLE 2-2 - UNIT WEIGHTS - 050-061 MODELS
TABLE 2-4 - UNIT CORNER WEIGHTS - 050-061 MODELS
UNIT WEIGHTS CONTINUED
Unit Placement
ROOF CURB INSTALLATION
Installation
TABLE 2-5 - PHYSICAL DATA - 050-061 MODELS
PHYSICAL DATA
TABLE 2-6 - PHYSICAL DATA - COMPRESSORS
PHYSICAL DATA CONTINUED
Installation
TABLE 2-5 - PHYSICAL DATA - 050-061 MODELS CONTINUED
GENERAL
GENERAL
ARRANGEMENT DRAWING
050-061 MODELS
2-4 - GENERAL ARRANGEMENT DRAWING CONT
ARRANGEMENT
GENERAL
Installation
ARRANGEMENT DRAWING CONT
CONTINUED
GENERAL ARRANGEMENTDRAWINGS
GENERAL
SUPPLY
Installation
CURB LAYOUT DRAWING / 050-061 MODELS
FIG. 2-5 - GENERAL ARRANGEMENT DRAWING
Load Definitions
ELECTRICAL DATA
TABLE 2-10 - SUPPLY AND EXHAUST FAN MOTOR DATA - TEFC
ELECTRIC DATA CONTINUED
Installation
TABLE 2-9 - SUPPLY AND EXHAUST FAN MOTOR DATA - ODP
TABLE 2-15 - AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
ELECTRIC DATA CONTINUED
TABLE 2-14 - ELECTRIC HEAT
H must be at least 1 inch plus fan total static pressure X = 1/2 H
Condensate Drain Piping
Condensate Drain Trap
Installation
Space Sensor
Shielded wire must be used that is grounded at the control panel only
Thermostat
Fan input
Shutdown Input
Fault Output
CO2 Sensor
Occupied / Unoccupied Input
VAV Heat Relay Output
Supply Air Temperature Reset
2. All wiring is Class 2, low voltage
FIELD CONTROL WIRING CONNECTIONS
Installation
Wiring Notes
Minimum CircuitAmpacity MCA is based on 125%
POWER WIRING
Overcurrent Protection Device Data is supplied on
FIG. 2-9 - SINGLE-POINT POWER SUPPLY WIRING
SINGLE-POINT POWER SUPPLY WIRING
Field Power Supply
Installation
Field Power Supply
SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT SWITCH
Field Power Supply #1
DUAL-POINT POWER SUPPLY WIRING
Installation
Field Power Supply #2
CONTROLS
Building Pressure Transducer
Static Pressure Probe Installation
Static Pressure Control Plastic Tubing Pneumatic Tubing
Duct Static Transducer
LD13127
Filter Compartment Economizer Compartment
FIG. 2-12 - ATMOSPHERIC SENSOR PROBE
Installation
Duct Connection Guidelines
Gas Piping Recommendations
GAS HEATING
1. Remove the combustion vent assembly from the return compartment
Installation
Unit Checks
SECTION 3 - START-UP
FIG. 3-1 - FAN HOLD DOWN BRACKETS
Startup
UNIT CHECKS - POWER APPLIED
Verifying Compressor Rotation
Compressor Oil Level Check
Superheat R-410A
Refrigerant Charge
Checking Superheat and Subcooling
Subcooling R-410A
Leak Checking
Startup
TABLE 3-1 -R410-A PRESSURE / TEMPERATURE CHART
Post Start Checks
Pre-Start Checks
Startup
Manifold Gas Pressure Adjustment
Compressors
SECTION 4 - MAINTENANCE
Filters
Linkages
Belt Tension
Maintenance
Condenser Coils
Motor Bearing Lubrication
Belt Tensioning
Belt Replacement
Maintenance
Filter Drier Replacement
Forward Curved Fans
Mounting Details
Fan Motor
Fan Shaft Bearings
FIG. 4-6 - BEARING WITH ECCENTRIC CAM
Eccentric Type
Bearing Lock Devices
Maintenance
3. Torque screw “A” to full recommended value
Torquing of Set-screws
1. Torque screw “A” to 1/2 recommended torque
2. Torque screw “B” to full min. recommended value
JOHNSON CONTROLS
THIS PAGE INTENTIONALLY LEFT BLANK
FORM 100.50-NOM6
SECTION 5 - SEQUENCE OF OPERATION
Unoccupied Cooling
Sequence of Operation
Thermostat Input
Occupied Cooling
Cooling Operation - Occupied or Unoccupied
Space Sensor - Hard Wired or Communicated
Occupied Heating
Unoccupied Heating
Sequence of Operation
Heating Operation - Occupied or Unoccupied
Stand Alone
Heating Operation - Occupied or Unoccupied
If after 5 minutes the return air temperature is between 1.5 F and 1.9 F above the “CV OCCUPIED COOLING SETPOINT” or “CV
Cooling Operation - Occupied or Unoccupied
Sequence of Operation
Cooling - Occupied with Thermostat
Occupied or Unoccupied Heating with a Thermo- stat
Occupied Cooling with Hard Wired or Communi- cated Space Sensor
Cooling - Unoccupied with Thermostat
Sequence of Operation
Cooling - Unoccupied with a Hard Wired or Com- municated Space Sensor
Heating - Occupied with a Hard Wired or Com- municated Space Sensor
Heating - Unoccupied with a Hard Wired or Com- municated Space Sensor
Occupied Cooling - Stand Alone
Sequence of Operation
Cooling - Unoccupied Stand Alone
Heating - Occupied Stand Alone
Heating - Unoccupied Stand Alone
Configuration Jumpers and Potentiometers
Operation and Pressure Control Range
Sequence of Operation
Constant Volume CV
Variable Air Volume VAV
“DUCT PRESSURE SHUTDOWN SETPOINT”
VAV Supply Fan Speed Control
Dry Bulb
Sequence of Operation
“RETURN AIR HUMIDITY SENSOR INSTALLED”
Single Enthalpy
Dual Enthalpy
“OUTSIDE AIR HUMIDITY SENSOR INSTALLED”
Sequence of Operation
Constant Volume Economizer Set Point
Variable Air Volume Economizer Set Point
Sequence of Operation
ECONOMIZER LOADING
Economizer / Compressor Operation
Economizer PI Loop Proportional and Integral
Sequence of Operation
Constant Volume
Variable Air Volume
The unit can not be in an active heating or cooling mode
The unit must have an economizer installed
The unit type must be Constant Volume
TABLE 5-5 COMPRESSOR ON WHEN SPACE INPUT SATISFIED
Sequence of Operation
Conditions of Operation
Cooling
Sequence of Operation
Heating
Sequence of Operation
The Simplicity Control then starts a 3 minute timer
Sequence of Operation
Sequence of Operation
The following parameter must be enabled in order to use to feature
Sequence of Operation
Sequence of Operation
Sequence of Operation
The following must be enabled for Metric Operation
Sequence of Operation
Sequence of Operation
Sequence of Operation
Subsequent Operation
When the “CV OCCUPIED HEATING” set point is reached the Simplicity Elite control will divide the elapsed time into 5-minute increments
MORNING WARM-UP
Sequence of Operation
Sequence of Operation
Sequence of Operation
The following parameters must be programmed to use Hydronic Heat
Sequence of Operation
Manual
Fixed Minimum
Demand Ventilation
Sequence of Operation
Definitions
VENTILATION LOW AMBIENT MINIMUM POSITION RESET
Sequence of Operation
Sequence of Operation
On/Off Control Based on Outdoor Damper Posi- tion
On/Off Control Based on Building Pressure
Sequence of Operation
Sequence of Operation
Modulating Damper with Fixed Speed Exhaust
Modulating Exhaust with a VFD
When the building static pressure is 0.025” WC or more above the “BUILDING PRESSURE SETPOINT” the Simplicity Elite control sends a 2 to 10 volt DC signal to open the exhaust damper. The output is at the “EXD+” and “EXD-“ terminals at the P14 connector
Sequence of Operation
Criteria for Operation
Sequence of Operation
Sequence of Operation
Sequence of Operation
The following parameters must be programmed to use this feature
Sequence of Operation
Sequence of Operation “Supply Air Temp Alarm Setpoint for Heating”
Alarm
SAT ALARM FOR HEATING
Sequence of Operation
“Economizer Minimum Position” Alarm
“Supply Air Temp Alarm Setpoint for Cooling” Alarm
“SUPPLY AIR TEMP ALARM SETPOINT FOR HEATING”
Sequence of Operation
“Economizer Minimum Position” Alarm
“ECONOMIZER MINIMUM POSITION” alarm and flash an Alarm Code
SECTION 6 - USER INTERFACE
User Interface Control Center
0.000
TABLE 6-1 - PARAMETER POINTS LIST
100º - 180º
TABLE - 6-1 - PARAMETER POINTS LIST CONT
User Interface Control Center
TABLE - 6-1 - PARAMETER POINTS LIST CONT
UNITS OF ADJUSTMENT
ADJUSTMENT
SETTING
2. Left click on Dealers / Distributors
Simplicity PC Download
User Interface Control Center
1. On the internet connect to YorkUPG.Com
LD13037
3. Left click on software
User Interface Control Center
USB Adapter Drive - Simplicity Pocket PC
FREEnet Serial
Establishing Communication
FREEnet USB
LD13041
User Interface Control Center
LD13040
7. Left-click on the particular Simplicity device de- sired
LD13043
User Interface Control Center
JOHNSON CONTROLS
LD13015
EQUIPMENT INSTALLATION
SIMPLICITY PC DATA SCREENS
DEVICE NAMES
LD13017
User Interface Control Center
SENSOR READINGS
LD13018
ECONOMIZER/EXHAUST
LD13019
User Interface Control Center
FANS
LD13020
COOLING SETUP
LD13021
User Interface Control Center
COOLING STATUS
LD13022
HEATING SETUP
LD13023
User Interface Control Center
HEATING STATUS
LD13024
SYSTEM OPTIONS
LD13025
User Interface Control Center
OUTPUTS/STATUS
LD13026
INPUTS
COMFORT/DEMAND VENTILATION
LD13014
JOHNSON CONTROLS
User Interface Control Center
GRAPHIC
CLOCK
LD13029
WEEKLY SCHEDULE SETTINGS
Weekly Schedule
HOLIDAY SCHEDULE
User Interface Control Center
Holiday Schedule
LD13031
ALARMS
LD13032
REVISING SETTINGS
User Interface Control Center
LD13033
To open the change screen double left click
LD13034
User Interface Control Center
LD13035
TABLE 6-2 - SIMPLICITY ELITE DATA MAP
Writing to any register not in this list may cause erratic operation
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
1A H
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
1A L
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
User Interface Control Center
60 L
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
4A H
50 L
115 L
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
A6 L
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
A4 L
A5 L
BA H
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
CA L
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
User Interface Control Center
TABLE 7-1 - DEFINITIONS
SECTION 7 - PARAMETER DESCRIPTIONS AND OPTIONS
TABLE 7-1 - DEFINITIONS CONTINUED
Parameter Description and Options
DEFINITION
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
TABLE 7-1 - DEFINITIONS CONTINUED
Parameter Description and Options
DEFINITION
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
TABLE 7-1 - DEFINITIONS CONTINUED
Parameter Description and Options
DEFINITION
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
TABLE 7-1 - DEFINITIONS CONTINUED
Parameter Description and Options
DEFINITION
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
TABLE 7-1 - DEFINITIONS CONTINUED
Parameter Description and Options
DEFINITION
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
TABLE 7-1 - DEFINITIONS CONTINUED
Parameter Description and Options
Duct Pressure Transducer
SECTION 8 - SERVICE
Temperature Sensors
Building Pressure Transducer
Service
Return Fan Pressure Transducer
Discharge Pressure Transducer
TABLE 8-6 - HUMIDITY SENSOR OUTPUTS
Suction Pressure Transducer
Humidity Sensors
TABLE 8-5 - PRESSURE TRANSDUCERS
TABLE 8-7 - CO2 SENSOR OUTPUT
Furnace Status Input
Service
CO2 Sensor
SAT+
FIG. 8-1 - CONNECTOR LOCATIONS
TABLE 8-8 - WIRING DATA
RAT+
TABLE 8-8 - WIRING DATA CONTINUED
Service
VAV OPEN +
TABLE 8-8 - WIRING DATA CONTINUED
VAV OPEN
Service
FAULTS AND LOCKOUTS
DESCRIPTION
TABLE 8-9 - ALARM CODE DESCRIPTIONS
ALARM CODE
TABLE 8-9 - ALARM CODE DESCRIPTIONS CONTINUED
Service
YPAL 060 Compressors 1B and 2B YPAL 061 Compressors 1B, 2A and 2B
Space Temperature Sensor Alarm
Low Pressure Cutout Alarm 09, 10
Limit Switch Alarms 13, 14
Gas Heating Alarms 16
Dirty Filter Switch Alarm
Supply Air Temperature Sensor Alarm
Return Air Temperature Sensor Alarm
Outdoor Air Temperature Sensor Alarm
Time Clock Error Alarm
Outdoor Humidity Sensor Alarm
Return Humidity Sensor Alarm
IAQ CO2 Sensor Alarm
Space Temperature Trending Alarm
Supply Air Temperature Cooling Alarm
Supply Air Temperature Heating Alarm
Economizer Minimum Position Alarm
ALL RIGHTS RESERVED