York YPAL 050, YPAL 061, YPAL 051, YPAL 060 manual 1 - DEFINITIONS CONTINUED, Menu Item, Definition

Models: YPAL 060 YPAL 051 YPAL 050 YPAL 061

1 168
Download 168 pages 27.04 Kb
Page 149
Image 149

 

FORM 100.50-NOM6 (1207)

 

TABLE 7-1 – DEFINITIONS (CONTINUED)

 

 

 

 

 

 

 

MENU ITEM

DEFINITION

 

 

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE LOW

 

 

LPS3

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 3 TO THE

 

 

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

 

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE LOW

 

 

LPS4

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 4 TO THE

 

 

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

 

 

THIS PARAMETER ESTABLISHED THE MAXIMUM POSITION

 

 

MAXIMUM IAQ ECONOMIZER POSITION

THE OUTDOOR DAMPER CAN OPEN TO IN THE DEMAND

 

 

 

VENTILATION MODE

 

 

 

THIS PARAMETER GIVES THE STATUS OF THE UNOCCUPIED

 

 

METER OF UNOCCUPIED OVERRIDE ENABLED

OVERRIDE INPUT. OFF MEANS IT IS NOT IN OVERRIDE MODE

 

 

 

AND ON MEANS IT IS IN OVERRIDE MODE.

 

 

 

WHEN THIS OPTION IS TURNED ON THE TEMPERATURE DATA

 

 

METRIC OPERATION

WILL BE CONVERTED TO METRIC UNITS. 0 = IMPERIAL, 1 =

 

 

 

METRIC

 

 

MINIMUM RUN TIME FOR COMPRESSORS

THIS PARAMETER ESTABLISHES THE MINIMUM RUN TIME FOR

 

 

THE COMPRESSORS, 1 TO 10 MINUTES

 

 

 

 

 

MINUTE

THIS PARAMETER IS USED TO ENTER THE MINUTES OF THE

 

 

CURRENT TIME.

 

 

 

 

 

MODULATING POWER EXHAUST INSTALLED

THIS PARAMETER MUST BE TURNED ON IN ORDER TO USE

 

 

MODULATING EXHAUST, EITHER DAMPER OR VFD

 

 

 

 

 

MONTH

THIS PARAMETER IS USED TO ENTER THE CURRENT MONTH 1

 

 

TO 12. FOR EXAMPLE 1 WOULD BE JANUARY

 

 

 

 

 

 

THIS PARAMETER IS USED TO DETERMINE THE ON AND OFF

 

 

MORNING WARM-UP / VAV RETURN AIR TEMP

POINTS FOR VAV OCCUPIED HEATING OPERATION IN THE

 

 

STAND ALONE OR SPACE SENSOR MODE OF OPERATION. IT

 

 

SETPOINT

 

 

IS ALSO USED TO CONTROL THE HEATING OPTION IN THE

 

 

 

 

 

 

MORNING WARM-UP MODE.

 

 

MORNING WARM-UP ENABLE

THIS PARAMETER MUST BE TURNED ON TO ENABLE MORNING

 

 

WARM-UP OPERATION

 

 

 

 

 

NETWORK OCCUPIED FLAG

THIS GIVES THE STATUS OF THE COMMUNICATED OCCUPIED

 

 

COMMAND, OFF UNOCCUPIED, ON OCCUPIED

 

 

 

 

 

OCC INPUT

THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL OCC

 

 

- OCCUPIED INPUT

 

 

 

 

 

 

THIS PARAMETER MUST BE TURNED ON IN ORDER TO USE THE

 

 

OCCUPIED INPUT ENABLED

HARD WIRED OR COMMUNICATED OCCUPIED INPUT. IT MUST

 

 

BE TURNED OFF IN ORDER TO USE THE DAILY OR HOLIDAY

 

 

 

 

 

 

SCHEDULING FEATURE

 

 

 

THIS PARAMETER ESTABLISHES AN OUTDOOR SET POINT TO

 

 

 

7

OUTDOOR AIR TEMP COOLING LOCKOUT

LOCKOUT COOLING OPERATION. WHEN THE TEMPERATURE IS

 

 

BELOW THIS SETTING COOLING IS LOCKED OUT

 

 

 

THIS PARAMETER ESTABLISHES AN OUTDOOR SET POINT TO

 

 

OUTDOOR AIR TEMP HEATING LOCKOUT

LOCKOUT HEATING OPERATION. WHEN THE TEMPERATURE IS

 

 

 

ABOVE THIS SETTING HEATING IS LOCKED OUT

 

 

OUTSIDE AIR ENTHALPY

THIS PARAMETER IS THE CALCULATED VALUE FOR THE

 

 

OUTDOOR AIR ENTHALPY

 

 

 

 

 

 

Continued on next page

 

JOHNSON CONTROLS

149

Page 149
Image 149