| FORM |
| |
TABLE |
|
|
|
|
|
|
|
MENU ITEM | DEFINITION |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE LOW |
|
|
LPS3 | PRESSURE SWITCH FOR COMPRESSOR SYSTEM 3 TO THE |
|
|
| UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE LOW |
|
|
LPS4 | PRESSURE SWITCH FOR COMPRESSOR SYSTEM 4 TO THE |
|
|
| UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. |
|
|
| THIS PARAMETER ESTABLISHED THE MAXIMUM POSITION |
|
|
MAXIMUM IAQ ECONOMIZER POSITION | THE OUTDOOR DAMPER CAN OPEN TO IN THE DEMAND |
|
|
| VENTILATION MODE |
|
|
| THIS PARAMETER GIVES THE STATUS OF THE UNOCCUPIED |
|
|
METER OF UNOCCUPIED OVERRIDE ENABLED | OVERRIDE INPUT. OFF MEANS IT IS NOT IN OVERRIDE MODE |
|
|
| AND ON MEANS IT IS IN OVERRIDE MODE. |
|
|
| WHEN THIS OPTION IS TURNED ON THE TEMPERATURE DATA |
|
|
METRIC OPERATION | WILL BE CONVERTED TO METRIC UNITS. 0 = IMPERIAL, 1 = |
|
|
| METRIC |
|
|
MINIMUM RUN TIME FOR COMPRESSORS | THIS PARAMETER ESTABLISHES THE MINIMUM RUN TIME FOR |
|
|
THE COMPRESSORS, 1 TO 10 MINUTES |
|
| |
|
|
| |
MINUTE | THIS PARAMETER IS USED TO ENTER THE MINUTES OF THE |
|
|
CURRENT TIME. |
|
| |
|
|
| |
MODULATING POWER EXHAUST INSTALLED | THIS PARAMETER MUST BE TURNED ON IN ORDER TO USE |
|
|
MODULATING EXHAUST, EITHER DAMPER OR VFD |
|
| |
|
|
| |
MONTH | THIS PARAMETER IS USED TO ENTER THE CURRENT MONTH 1 |
|
|
TO 12. FOR EXAMPLE 1 WOULD BE JANUARY |
|
| |
|
|
| |
| THIS PARAMETER IS USED TO DETERMINE THE ON AND OFF |
|
|
MORNING | POINTS FOR VAV OCCUPIED HEATING OPERATION IN THE |
|
|
STAND ALONE OR SPACE SENSOR MODE OF OPERATION. IT |
|
| |
SETPOINT |
|
| |
IS ALSO USED TO CONTROL THE HEATING OPTION IN THE |
|
| |
|
|
| |
| MORNING |
|
|
MORNING | THIS PARAMETER MUST BE TURNED ON TO ENABLE MORNING |
|
|
|
| ||
|
|
| |
NETWORK OCCUPIED FLAG | THIS GIVES THE STATUS OF THE COMMUNICATED OCCUPIED |
|
|
COMMAND, OFF UNOCCUPIED, ON OCCUPIED |
|
| |
|
|
| |
OCC INPUT | THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL OCC |
|
|
- OCCUPIED INPUT |
|
| |
|
|
| |
| THIS PARAMETER MUST BE TURNED ON IN ORDER TO USE THE |
|
|
OCCUPIED INPUT ENABLED | HARD WIRED OR COMMUNICATED OCCUPIED INPUT. IT MUST |
|
|
BE TURNED OFF IN ORDER TO USE THE DAILY OR HOLIDAY |
|
| |
|
|
| |
| SCHEDULING FEATURE |
|
|
| THIS PARAMETER ESTABLISHES AN OUTDOOR SET POINT TO |
|
|
| 7 | ||
OUTDOOR AIR TEMP COOLING LOCKOUT | LOCKOUT COOLING OPERATION. WHEN THE TEMPERATURE IS |
| |
| BELOW THIS SETTING COOLING IS LOCKED OUT |
|
|
| THIS PARAMETER ESTABLISHES AN OUTDOOR SET POINT TO |
|
|
OUTDOOR AIR TEMP HEATING LOCKOUT | LOCKOUT HEATING OPERATION. WHEN THE TEMPERATURE IS |
|
|
| ABOVE THIS SETTING HEATING IS LOCKED OUT |
|
|
OUTSIDE AIR ENTHALPY | THIS PARAMETER IS THE CALCULATED VALUE FOR THE |
|
|
OUTDOOR AIR ENTHALPY |
|
| |
|
|
| |
| Continued on next page |
|