| FORM |
| |
TABLE |
|
|
|
|
|
|
|
MENU ITEM | DEFINITION |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH |
|
|
HSP1 | PRESSURE SWITCH FOR COMPRESSOR SYSTEM 1 TO THE |
|
|
| UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH |
|
|
HSP2 | PRESSURE SWITCH FOR COMPRESSOR SYSTEM 2 TO THE |
|
|
| UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH |
|
|
HSP3 | PRESSURE SWITCH FOR COMPRESSOR SYSTEM 3 TO THE |
|
|
| UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH |
|
|
HSP4 | PRESSURE SWITCH FOR COMPRESSOR SYSTEM 4 TO THE |
|
|
| UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. |
|
|
| THIS PARAMETER REVERSES THE ACTION OF THE HYDRONIC |
|
|
HYDRONIC HEAT ACTUATOR VALVE REVERSE | VALVE. WHEN THE PARAMETER IS TURNED ON A 2 VOLT INPUT |
|
|
ACTING | TO THE VALVE IS FULL OPEN AND A 10 VOLT INPUT TO THE |
|
|
| VALVE IS FULL CLOSED |
|
|
HYDRONIC HEATING ENABLED | THIS PARAMETER MUST BE TURNED ON TO ENABLE HYDRONIC |
|
|
HEATING OPERATION |
|
| |
|
|
| |
HYDRONIC HEATING STAGE #1 SUPPLY AIR | THIS PARAMETER ESTABLISHES THE SETPOINT FOR |
|
|
CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING |
|
| |
SETPOINT |
|
| |
FIRST STAGE OPERATION |
|
| |
|
|
| |
| THIS PARAMETER ESTABLISHES THE SETPOINT FOR |
|
|
HYDRONIC HEATING STAGE #2 SUPPLY AIR | CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING |
|
|
SETPOINT | SECOND STAGE OPERATION AND ALSO THE CONTROL |
|
|
| SETPOINT FOR VAV HYDRONIC HEATING OPERATION |
|
|
IAQ SENSOR RANGE | THIS PARAMETER IDENTIFIES TO THE UNIT CONTROLLER THE |
|
|
RANGE OF THE CO2 SENSOR IN PPM |
|
| |
|
|
| |
IAQ SETPOINT | THE UNIT CONTROLLER WILL TRY AND MAINTAIN THE CO2 |
|
|
LEVEL IN THE SPACE TO WITHIN +/- 100 PPM OF THIS VALUE |
|
| |
|
|
| |
INDOOR FAN (G) | THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL G |
|
|
- SUPPLY FAN |
|
| |
|
|
| |
INDOOR FAN MIN RUN TIME | THIS GIVES THE STATUS OF THE MINIMUM SUPPLY FAN RUN |
|
|
TIME IN SECONDS |
|
| |
|
|
| |
INDOOR FAN OUTPUT | THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE |
|
|
UNIT CONTROLLER TO THE SUPPLY FAN |
|
| |
|
|
| |
INDOOR FAN VFD OUTPUT | THIS GIVES THE STATUS OF THE ANALOG OUTPUT FROM THE |
|
|
UNIT CONTROLLER TO THE SUPPLY FAN IN % |
|
| |
|
|
| |
INPUT AIR PROVING SWITCH | THIS IS THE STATUS OF THE AIR PROVING SWITCH INPUT TO |
|
|
THE UNIT CONTROLLER, OFF OR ON |
|
| |
| 7 | ||
|
| ||
| THIS IS THE STATUS OF THE DIRTY FILTER SWITCH INPUT TO |
| |
INPUT DIRTY FILTER SWITCH | THE UNIT CONTROLLER, OFF - CLEAN FILTER, ON - DIRTY |
|
|
| FILTER |
|
|
| THIS GIVES THE STATUS OF THE BINARY INPUT FROM THE |
|
|
INPUT INDOOR FAN OVERLOAD SWITCH | SUPPLY FAN OVERLOAD TO THE UNIT CONTROLLER, OFF - |
|
|
| FAULT, ON - NORMAL OPERATION |
|
|
| Continued on next page |
|