FORM 100.50-NOM6 (1207)

 

TABLE 7-1 – DEFINITIONS (CONTINUED)

 

 

 

 

 

 

 

MENU ITEM

DEFINITION

 

 

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

 

 

HSP1

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 1 TO THE

 

 

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

 

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

 

 

HSP2

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 2 TO THE

 

 

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

 

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

 

 

HSP3

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 3 TO THE

 

 

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

 

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

 

 

HSP4

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 4 TO THE

 

 

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

 

 

THIS PARAMETER REVERSES THE ACTION OF THE HYDRONIC

 

 

HYDRONIC HEAT ACTUATOR VALVE REVERSE

VALVE. WHEN THE PARAMETER IS TURNED ON A 2 VOLT INPUT

 

 

ACTING

TO THE VALVE IS FULL OPEN AND A 10 VOLT INPUT TO THE

 

 

 

VALVE IS FULL CLOSED

 

 

HYDRONIC HEATING ENABLED

THIS PARAMETER MUST BE TURNED ON TO ENABLE HYDRONIC

 

 

HEATING OPERATION

 

 

 

 

 

HYDRONIC HEATING STAGE #1 SUPPLY AIR

THIS PARAMETER ESTABLISHES THE SETPOINT FOR

 

 

CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING

 

 

SETPOINT

 

 

FIRST STAGE OPERATION

 

 

 

 

 

 

THIS PARAMETER ESTABLISHES THE SETPOINT FOR

 

 

HYDRONIC HEATING STAGE #2 SUPPLY AIR

CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING

 

 

SETPOINT

SECOND STAGE OPERATION AND ALSO THE CONTROL

 

 

 

SETPOINT FOR VAV HYDRONIC HEATING OPERATION

 

 

IAQ SENSOR RANGE

THIS PARAMETER IDENTIFIES TO THE UNIT CONTROLLER THE

 

 

RANGE OF THE CO2 SENSOR IN PPM

 

 

 

 

 

IAQ SETPOINT

THE UNIT CONTROLLER WILL TRY AND MAINTAIN THE CO2

 

 

LEVEL IN THE SPACE TO WITHIN +/- 100 PPM OF THIS VALUE

 

 

 

 

 

INDOOR FAN (G)

THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL G

 

 

- SUPPLY FAN

 

 

 

 

 

INDOOR FAN MIN RUN TIME

THIS GIVES THE STATUS OF THE MINIMUM SUPPLY FAN RUN

 

 

TIME IN SECONDS

 

 

 

 

 

INDOOR FAN OUTPUT

THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE

 

 

UNIT CONTROLLER TO THE SUPPLY FAN

 

 

 

 

 

INDOOR FAN VFD OUTPUT

THIS GIVES THE STATUS OF THE ANALOG OUTPUT FROM THE

 

 

UNIT CONTROLLER TO THE SUPPLY FAN IN %

 

 

 

 

 

INPUT AIR PROVING SWITCH

THIS IS THE STATUS OF THE AIR PROVING SWITCH INPUT TO

 

 

THE UNIT CONTROLLER, OFF OR ON

 

 

 

7

 

 

 

THIS IS THE STATUS OF THE DIRTY FILTER SWITCH INPUT TO

 

INPUT DIRTY FILTER SWITCH

THE UNIT CONTROLLER, OFF - CLEAN FILTER, ON - DIRTY

 

 

 

FILTER

 

 

 

THIS GIVES THE STATUS OF THE BINARY INPUT FROM THE

 

 

INPUT INDOOR FAN OVERLOAD SWITCH

SUPPLY FAN OVERLOAD TO THE UNIT CONTROLLER, OFF -

 

 

 

FAULT, ON - NORMAL OPERATION

 

 

 

Continued on next page

 