FORM 100.50-NOM6 (1207)

TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)

ADDRESS

DESCRIPTION

UNITS OF ADJUSTMENT

RANGE OF

CURRENT

NUMBER

ADJUSTMENT

SETTING

 

 

72/73/74/

ALARM ARRAY

DATA - 5 CHARACTERS

0 - 255

0

75/76

 

 

 

 

 

 

 

 

 

77

VAV / CV SELECTION

READ ONLY FLAG

CV = 0

0

VAV = 1

 

 

 

 

78

HOT GAS REHEAT

PARAMETER BIT

0 = OFF, 1 = ON

OFF

79

HOT GAS PRESENT ON COMPRESSOR # 1

PARAMETER BIT

0 = OFF, 1 = ON

OFF

80

COMPRESSORS AVAILABLE FOR COOLING

PARAMETER BIT

2 - 4

2

81

STAGES OF HEAT AVAILABLE

PARAMETER BIT

0 - 3

2

0 = DISABLED

 

 

 

 

82

DUCT STATIC READING

PRESSURE - INCHES OF

0.000 - 5.000

0000

H2O

 

 

 

 

83

BUILDING STATIC PRESSURE

PRESSURE - INCHES OF

0.000 - 5.000

0000

H2O

 

 

 

 

84

LOW AMBIENT KIT INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

85

BUILDING STATIC PRESSURE SENSOR INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

86

ERV INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

87

ERV UNOCCUPIED FAN ENABLE

PARAMETER BIT

0 = OFF, 1 = ON

OFF

 

 

 

 

 

88

DUCT STATIC SHUTDOWN SETPOINT

PRESSURE - INCHES OF

0.000 - 5.000

4.500

H2O

 

 

 

 