TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)
ADDRESS | DESCRIPTION | UNITS OF ADJUSTMENT | RANGE OF | CURRENT | |
NUMBER | ADJUSTMENT | SETTING | |||
|
| ||||
72/73/74/ | ALARM ARRAY | DATA - 5 CHARACTERS | 0 - 255 | 0 | |
75/76 | |||||
|
|
|
| ||
|
|
|
|
| |
77 | VAV / CV SELECTION | READ ONLY FLAG | CV = 0 | 0 | |
VAV = 1 | |||||
|
|
|
| ||
78 | HOT GAS REHEAT | PARAMETER BIT | 0 = OFF, 1 = ON | OFF | |
79 | HOT GAS PRESENT ON COMPRESSOR # 1 | PARAMETER BIT | 0 = OFF, 1 = ON | OFF | |
80 | COMPRESSORS AVAILABLE FOR COOLING | PARAMETER BIT | 2 - 4 | 2 | |
81 | STAGES OF HEAT AVAILABLE | PARAMETER BIT | 0 - 3 | 2 | |
0 = DISABLED | |||||
|
|
|
| ||
82 | DUCT STATIC READING | PRESSURE - INCHES OF | 0.000 - 5.000 | 0000 | |
H2O | |||||
|
|
|
| ||
83 | BUILDING STATIC PRESSURE | PRESSURE - INCHES OF | 0.000 - 5.000 | 0000 | |
H2O | |||||
|
|
|
| ||
84 | LOW AMBIENT KIT INSTALLED | PARAMETER BIT | 0 = OFF, 1 = ON | OFF | |
85 | BUILDING STATIC PRESSURE SENSOR INSTALLED | PARAMETER BIT | 0 = OFF, 1 = ON | OFF | |
86 | ERV INSTALLED | PARAMETER BIT | 0 = OFF, 1 = ON | OFF | |
87 | ERV UNOCCUPIED FAN ENABLE | PARAMETER BIT | 0 = OFF, 1 = ON | OFF | |
|
|
|
|
| |
88 | DUCT STATIC SHUTDOWN SETPOINT | PRESSURE - INCHES OF | 0.000 - 5.000 | 4.500 | |
H2O | |||||
|
|
|
|