ELECTRIC DATA (CONTINUED)
TABLE 2-14 – ELECTRIC HEAT
KW |
| NOMINAL VOLTAGE |
| ||
208/3/60 | 230/3/60 | 460/3/60 | 575/3/60 | ||
| |||||
| AMPS | AMPS | AMPS | AMPS | |
40 | 96 | 96 | 48 | 40 | |
80 | 193 | 193 | 96 | 80 | |
108 | 260 | 260 | 130 | 109 | |
150 | — | — | 181 | 151 |
TABLE 2-15 – AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
Limitations |
| Model Size |
| |
| 50 | 51 | 60 | 61 |
Minimum | 10000 - | 10000 - | 12500 - | 12500 - |
Airflow at | 22500 | 22500 | 24000 | 24000 |
Standard Design |
|
|
|
|
Conditions. |
|
|
|
|
CFM* |
|
|
|
|
(min to max) |
|
|
|
|
Entering Wet | 57/75 | 57/75 | 57/75 | 57/75 |
Bulb Temp F° |
|
|
|
|
(min/max) |
|
|
|
|
Entering Dry | 68/90 | 68/90 | 68/90 | 68/90 |
Bulb Temp F° |
|
|
|
|
(min/max) |
|
|
|
|
Ambient Temp F° | 50/120 | 50/120 | 50/120 | 50/120 |
without Low |
|
|
|
|
Amb option |
|
|
|
|
Ambient Temp F° | 0/120 | 0/120 | 0/120 | 0/120 |
with Low Amb |
|
|
|
|
option |
|
|
|
|
* Cooling Only Units |
|
|
|
|
FORM
2
JOHNSON CONTROLS | 31 |