| FORM |
| |
TABLE |
|
|
|
|
|
|
|
MENU ITEM | DEFINITION |
|
|
| IN THE INTERMITTENT FAN MODE THIS IS THE TIME DELAY |
|
|
COOL FAN OFF DELAY | BETWEEN THE TIME THE COOLING CALL IS TERMINATED AND |
|
|
| THE SHUT DOWN OF THE SUPPLY FAN |
|
|
| IN THE INTERMITTENT FAN MODE THIS IS THE TIME DELAY |
|
|
COOL FAN ON DELAY | BETWEEN THE TIME THE COOLING CALL IS INITIATED AND THE |
|
|
| START OF THE SUPPLY FAN |
|
|
COOLING MODE OPERATION ENABLE | THIS PARAMETER MUST BE TURNED ON TO ALLOW COOLING |
|
|
OPERATION |
|
| |
|
|
| |
COOL 1 (Y1) | THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL Y1 |
|
|
- FIRST STAGE COOLING |
|
| |
|
|
| |
COOL 2 (Y2) | THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL Y2 |
|
|
- SECOND STAGE COOLING |
|
| |
|
|
| |
COOL 3 (Y3) | THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL Y3 |
|
|
- THIRD STAGE COOLING |
|
| |
|
|
| |
COOL 4 (Y4) | THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL Y4 |
|
|
- FOURTH STAGE COOLING |
|
| |
|
|
| |
CURRENT BUS ADDRESS | THIS IDENTIFIES THE ADDRESS OF THE UNIT ON THE |
|
|
NETWORK |
|
| |
|
|
| |
CV CURRENT OPERATING COOLING SETPOINT | THIS PARAMETER IDENTIFIES THE COOLING SET POINT THE |
|
|
UNIT CONTROLLER IS CONTROLLING TO COOLING TOO |
|
| |
|
|
| |
CV CURRENT OPERATING HEATING SETPOINT | THIS PARAMETER IDENTIFIES THE HEATING SET POINT THE |
|
|
UNIT CONTROLLER IS CONTROLLING TO HEATING TOO |
|
| |
|
|
| |
CV OCCUPIED COOLING SET POINT | THIS IS THE SPACE OR RETURN AIR TEMPERATURE THE UNIT |
|
|
WILL CONTROL TO WHEN IN THE OCCUPIED COOLING MODE. |
|
| |
|
|
| |
CV OCCUPIED HEATING SET POINT | THIS IS THE SPACE OR RETURN AIR TEMPERATURE THE UNIT |
|
|
WILL CONTROL TO WHEN IN THE OCCUPIED HEATING MODE. |
|
| |
|
|
| |
| THIS IS THE SPACE OR RETURN AIR TEMPERATURE THE UNIT |
|
|
CV UNOCCUPIED COOLING SET POINT | WILL CONTROL TO WHEN IN THE UNOCCUPIED COOLING |
|
|
| MODE. |
|
|
CV UNOCCUPIED HEATING SET POINT | THIS IS THE SPACE OR RETURN AIR TEMPERATURE THE UNIT |
|
|
WILL CONTROL TO WHEN IN THE UNOCCUPIED HEATING MODE. |
|
| |
|
|
| |
DAY OF MONTH | THIS PARAMETER IS USED TO ENTER THE CURRENT DAY OF |
|
|
THE MONTH, 1 - 31 |
|
| |
|
|
| |
DAY OF WEEK | THIS PARAMETER IS USED TO ENTER THE DAY OF THE WEEK |
|
|
|
| ||
|
|
| |
| THIS PARAMETER MUST BE TURNED ON TO ENABLE DEMAND |
|
|
DEMAND VENTILATION (IAQ) ENABLED | VENTILATION. DEMAND VENTILATION INCREASE THE AMOUNT |
|
|
OF VENTILATION AIR IN RESPONSE TO A INCREASE IN THE CO2 |
|
| |
|
|
| |
| LEVEL IN THE CONDITIONED SPACE |
| 7 |
DEMAND VENTILATION (IAQ) VALUE (CO2) | THIS THE CO2 INPUT VALUE TO THE UNIT CONTROLLER IN PPM |
| |
|
| ||
DIFFERENTIAL ENTHALPY MODE ENABLED | THIS PARAMETER MUST BE TURNED ON IN ORDER TO USE |
|
|
DIFFERENTIAL ENTHALPY |
|
| |
|
|
| |
DIRTY FILTER SWITCH DATA | THIS PARAMETER GIVE THE STATUS OF THE DIRTY FILTER |
|
|
SWITCH, 0 = CLEAN, 1 = DIRTY |
|
| |
|
|
|
Continued on next page
JOHNSON CONTROLS | 143 |