User Interface Control Center
FORM
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
|
|
| INITIAL/ |
|
|
|
|
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX |
| DESCRIPTION |
(HEX) | (DEC) | VALUE | VALUE | VALUE |
| ||
|
|
| |||||
|
|
| (HEX) |
|
|
|
|
|
| 3 |
|
|
| 1 | = ADDRESS / DOWN BUTTON PRESSED |
|
| 4 |
|
|
| NA | |
|
| 5 |
|
|
| NA | |
|
|
|
|
|
|
| |
|
| 6 |
|
|
| NA | |
|
| 7 |
|
|
| NA | |
|
|
|
|
|
|
| |
18 H | 24 H | NA | - | - | - | OUTPUT STATUS BYTE #1 | |
|
| 0 |
|
|
| 1 | = COMPRESSOR #1 ON |
|
| 1 |
|
|
| 1 | = COMPRESSOR #2 ON |
|
| 2 |
|
|
| 1 | = COMPRESSOR #3 ON |
|
| 3 |
|
|
| 1 | = COMPRESSOR #4 ON |
|
|
|
|
|
|
|
|
|
| 4 |
|
|
| 1 | = CONDENSER FAN #1 ON |
|
| 5 |
|
|
| 1 | = CONDENSER FAN #2 ON |
|
| 6 |
|
|
| 1 | = INDOOR FAN ON |
|
| 7 |
|
|
| 1 | = EXHAUST FAN ON |
18 L | 24 L | NA | - | - | - | OUTPUT STATUS BYTE #2 | |
|
| 0 |
|
|
| 1 | = STAGE 1 HEAT ON |
|
| 1 |
|
|
| 1 | = STAGE 2 HEAT ON |
|
| 2 |
|
|
| 1 | = STAGE 3 HEAT ON |
|
| 3 |
|
|
| NA | |
|
| 4 |
|
|
| NA | |
|
| 5 |
|
|
| NA | |
|
| 6 |
|
|
| NA | |
|
| 7 |
|
|
| NA | |
19 H | 25 H | NA | - | - | - | OUTPUT STATUS BYTE #3 | |
|
| 0 |
|
|
| 1 | = COMPRESSORS OFF BECAUSE FREE COOLING IS AVAILABLE |
|
| 1 |
|
|
| 1 | = COMPRESSORS OFF BECAUSE OF LOW AMBIENT |
|
| 2 |
|
|
| 1 | = COMPRESSORS OFF BECAUSE SUPPLY VOLTAGE IS LOW |
|
| 3 |
|
|
| 1 | = CONTROL IS IN COMFORT VENTILATION MODE |
|
| 4 |
|
|
| 1 | = DISABLE CONTROL IS ACTIVE |
|
| 5 |
|
|
| 1 | = ECONOMIZER IS USING FREE COOLING |
|
| 6 |
|
|
| NA | |
|
| 7 |
|
|
| NA | |
19 L | 25 L | NA | - | - | - | OUTPUT STATUS BYTE #4 | |
|
|
|
|
|
|
|
|
|
| 0 |
|
|
| 1 | = COMPRESSOR #1 OFF BECAUSE OF ASCD |
|
| 1 |
|
|
| 1 | = COMPRESSOR #2 OFF BECAUSE OF ASCD |
|
| 2 |
|
|
| 1 | = COMPRESSOR #3 OFF BECAUSE OF ASCD |
|
| 3 |
|
|
| 1 | = COMPRESSOR #4 OFF BECAUSE OF ASCD |
|
| 4 |
|
|
| NA | |
|
| 5 |
|
|
| NA | |
|
| 6 |
|
|
| NA | |
|
|
|
|
|
|
| |
|
| 7 |
|
|
| NA | |
1A H | 26 H | NA | 12 | - | - | OPTION BYTE #2 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Continued on next page |
132 |
|
|
|
|
|
| JOHNSON CONTROLS |