TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
|
|
| INITIAL/ |
|
|
| |
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX | DESCRIPTION | |
(HEX) | (DEC) | VALUE | VALUE | VALUE | |||
|
| ||||||
|
|
| (HEX) |
|
|
| |
1F H | 31 H | NA | 0 | 0 | 255 | COMPRESSOR #1 ACCUMULATED RUN TIME (HOURS, HIGH | |
BYTE) | |||||||
|
|
|
|
|
| ||
1F L | 31 L | NA | 0 | 0 | 255 | COMPRESSOR #1 ACCUMULATED RUN TIME (HOURS, LOW BYTE) | |
20 H | 32 H | NA | 0 | 0 | 255 | COMPRESSOR #2 ACCUMULATED RUN TIME (HOURS, HIGH | |
BYTE) | |||||||
|
|
|
|
|
| ||
20 L | 32 L | NA | 0 | 0 | 255 | COMPRESSOR #2 ACCUMULATED RUN TIME (HOURS, LOW BYTE) | |
21 H | 33 H | NA | 0 | 0 | 255 | COMPRESSOR #3 ACCUMULATED RUN TIME (HOURS, HIGH | |
BYTE) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
21 L | 33 L | NA | 0 | 0 | 255 | COMPRESSOR #3 ACCUMULATED RUN TIME (HOURS, LOW BYTE) | |
22 H | 34 H | NA | 0 | 0 | 255 | COMPRESSOR #4 ACCUMULATED RUN TIME (HOURS, HIGH | |
BYTE) | |||||||
|
|
|
|
|
| ||
22 L | 34 L | NA | 0 | 0 | 255 | COMPRESSOR #4 ACCUMULATED RUN TIME (HOURS, LOW BYTE) | |
24 H | 36 H | NA | 1 | 1 | 250 | REQUESTED ADDRESS CHANGE (BUS ADDRESS) | |
26 L | 38 L | NA | NA | NA | NA | REQUESTED OPERATION | |
|
| 0 |
|
|
| 1 = REQUEST FOR 1ST STAGE COOLING | |
|
|
|
|
|
|
| |
|
| 1 |
|
|
| 1 = REQUEST FOR 2ND STAGE COOLING | |
|
| 2 |
|
|
| 1 = REQUEST FOR 3RD STAGE COOLING | |
|
| 3 |
|
|
| 1 = REQUEST FOR 4TH STAGE COOLING | |
|
| 4 |
|
|
| 1 = REQUEST FOR 1ST STAGE HEATING | |
|
| 5 |
|
|
| 1 = REQUEST FOR 2ND STAGE HEATING | |
|
| 6 |
|
|
| 1 = REQUEST FOR 3RD STAGE HEATING | |
|
| 7 |
|
|
| 1 = REQUEST FOR FAN | |
|
|
|
|
|
|
| |
|
|
|
|
|
| REGISTERS 39 - 51 STORE THE MODEL NUMBER. WHEN | |
| 39 H - 51 |
|
|
|
| WRITTEN, ALL 13 REGISTERS (AT 2 BYTES PER REGISTER) | |
27 H - 33 L | NA |
|
|
| SHOULD BE WRITTEN. THE FORMAT IS ASCII. CHARACTER #1 | ||
L |
|
|
| ||||
|
|
|
|
| IS IN 39 H. CHARACTER #2 IS IN 39 L. CHARACTER #3 IS IN 40 H, | ||
|
|
|
|
|
| ||
|
|
|
|
|
| AND SO ON. | |
|
|
|
|
|
| REGISTERS 52 - 64 STORE THE SERIAL NUMBER. WHEN | |
| 52 H - 64 |
|
|
|
| WRITTEN, ALL 13 REGISTERS (AT 2 BYTES PER REGISTER) | |
34 H - 40 L | NA |
|
|
| SHOULD BE WRITTEN. THE FORMAT IS ASCII. CHARACTER #1 | ||
L |
|
|
| ||||
|
|
|
|
| IS IN 52 H. CHARACTER #2 IS IN 52 L. CHARACTER #3 IS IN 53 H, | ||
|
|
|
|
|
| ||
|
|
|
|
|
| AND SO ON. | |
|
|
|
|
|
| REDLINE/LOADSHED STATUS (5 MINUTE TIMER IS STARTED | |
41 L | 65 L | NA | NA | NA | NA | EACH WRITE. VALUE IS CLEARED IF TIMER IS ALLOWED TO | |
|
|
|
|
|
| FINISH.) | |
|
| 0 |
|
|
| 1 = SET REDLINE OPERATION | |
|
| 1 |
|
|
| 1 = SET LOADSHED OPERATION | |
|
| 2 - 7 |
|
|
| BITS | |
42 L | 66 L |
| 255 |
|
| CLEAR LOCKOUT STATUS | |
|
|
|
|
|
| WRITE “00” TO CLEAR ALL LOCKOUTS. ANY OTHER VALUE IS | |
|
|
|
|
|
| IGNORED. ALWAYS READS 255. | |
|
|
|
|
|
|
| |
43 H | 67 H |
| - | 0 | 255 | READING THIS ADDRESS RETURNS EEPROM CHECKSUM HIGH | |
| BYTE | ||||||
|
|
|
|
|
| ||
|
|
|
|
|