User Interface Control Center

FORM 100.50-NOM6 (1207)

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

 

 

 

INITIAL/

 

 

 

ADDRESS

ADDRESS

BIT

DEFAULT

MIN

MAX

DESCRIPTION

(HEX)

(DEC)

VALUE

VALUE

VALUE

 

 

 

 

 

(HEX)

 

 

 

1F H

31 H

NA

0

0

255

COMPRESSOR #1 ACCUMULATED RUN TIME (HOURS, HIGH

BYTE)

 

 

 

 

 

 

1F L

31 L

NA

0

0

255

COMPRESSOR #1 ACCUMULATED RUN TIME (HOURS, LOW BYTE)

20 H

32 H

NA

0

0

255

COMPRESSOR #2 ACCUMULATED RUN TIME (HOURS, HIGH

BYTE)

 

 

 

 

 

 

20 L

32 L

NA

0

0

255

COMPRESSOR #2 ACCUMULATED RUN TIME (HOURS, LOW BYTE)

21 H

33 H

NA

0

0

255

COMPRESSOR #3 ACCUMULATED RUN TIME (HOURS, HIGH

BYTE)

 

 

 

 

 

 

 

 

 

 

 

 

 

21 L

33 L

NA

0

0

255

COMPRESSOR #3 ACCUMULATED RUN TIME (HOURS, LOW BYTE)

22 H

34 H

NA

0

0

255

COMPRESSOR #4 ACCUMULATED RUN TIME (HOURS, HIGH

BYTE)

 

 

 

 

 

 

22 L

34 L

NA

0

0

255

COMPRESSOR #4 ACCUMULATED RUN TIME (HOURS, LOW BYTE)

24 H

36 H

NA

1

1

250

REQUESTED ADDRESS CHANGE (BUS ADDRESS)

26 L

38 L

NA

NA

NA

NA

REQUESTED OPERATION

 

 

0

 

 

 

1 = REQUEST FOR 1ST STAGE COOLING

 

 

 

 

 

 

 

 

 

1

 

 

 

1 = REQUEST FOR 2ND STAGE COOLING

 

 

2

 

 

 

1 = REQUEST FOR 3RD STAGE COOLING

 

 

3

 

 

 

1 = REQUEST FOR 4TH STAGE COOLING

 

 

4

 

 

 

1 = REQUEST FOR 1ST STAGE HEATING

 

 

5

 

 

 

1 = REQUEST FOR 2ND STAGE HEATING

 

 

6

 

 

 

1 = REQUEST FOR 3RD STAGE HEATING

 

 

7

 

 

 

1 = REQUEST FOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

REGISTERS 39 - 51 STORE THE MODEL NUMBER. WHEN

 

39 H - 51

 

 

 

 

WRITTEN, ALL 13 REGISTERS (AT 2 BYTES PER REGISTER)

27 H - 33 L

NA

 

 

 

SHOULD BE WRITTEN. THE FORMAT IS ASCII. CHARACTER #1

L

 

 

 

 

 

 

 

 

IS IN 39 H. CHARACTER #2 IS IN 39 L. CHARACTER #3 IS IN 40 H,

 

 

 

 

 

 

 

 

 

 

 

 

AND SO ON.

 

 

 

 

 

 

REGISTERS 52 - 64 STORE THE SERIAL NUMBER. WHEN

 

52 H - 64

 

 

 

 

WRITTEN, ALL 13 REGISTERS (AT 2 BYTES PER REGISTER)

34 H - 40 L

NA

 

 

 

SHOULD BE WRITTEN. THE FORMAT IS ASCII. CHARACTER #1

L

 

 

 

 

 

 

 

 

IS IN 52 H. CHARACTER #2 IS IN 52 L. CHARACTER #3 IS IN 53 H,

 

 

 

 

 

 

 

 

 

 

 

 

AND SO ON.

 

 

 

 

 

 

REDLINE/LOADSHED STATUS (5 MINUTE TIMER IS STARTED

41 L

65 L

NA

NA

NA

NA

EACH WRITE. VALUE IS CLEARED IF TIMER IS ALLOWED TO

 

 

 

 

 

 

FINISH.)

 

 

0

 

 

 

1 = SET REDLINE OPERATION

 

 

1

 

 

 

1 = SET LOADSHED OPERATION

 

 

2 - 7

 

 

 

BITS 2-7 UNUSED

42 L

66 L

 

255

 

 

CLEAR LOCKOUT STATUS

 

 

 

 

 

 

WRITE “00” TO CLEAR ALL LOCKOUTS. ANY OTHER VALUE IS

 

 

 

 

 

 

IGNORED. ALWAYS READS 255.

 

 

 

 

 

 

 

43 H

67 H

 

-

0

255

READING THIS ADDRESS RETURNS EEPROM CHECKSUM HIGH

 

BYTE

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page

134

 

 

 

 

 

JOHNSON CONTROLS

Page 134
Image 134
York YPAL 051, YPAL 061, YPAL 050, YPAL 060 manual 134