FORM 100.50-NOM6 (1207)

ELECTRICAL DATA

ELECTRICAL SERVICE SIZING

In order to use the electrical service required for the cooling only eco2 rooftop, use the appropriate calculations listed below from U.L. 1995. Based on the configuration of the rooftop, the calculations will yield different MCA (minimum circuit ampacity), and MOP (maximum overcurrent protection).

Using the following load definitions and calculations, determine the correct electrical sizing for your unit. All concurrent load conditions must be considered in the calculations, and you must use the highest value for any combination of loads.

Load Definitions:

LOAD1 is the current of the largest motor – com- pressor or fan motor.

LOAD2 is the sum of the remaining motor cur- rents that may run concurrently with LOAD1.

LOAD3 is the current of the electric heaters

– zero for cooling only units.

LOAD4 is the sum of any remaining currents greater than or equal to 1.0 amp.

Use the following calculations to determine MCA

and MOP for units supplied with a single-point power 2 connection:

MCA = (1.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4 MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4

If the MOP does not equal a standard current rating of an overcurrent protective device, then the marked maximum rating is to be the next lower standard rating. However, if the device selected for MOP is less than the MCA, then select the lowest standard maximum fuse size greater than or equal to the MCA.

TABLE 2-7 – COMPRESSOR DATA - R410A

 

 

 

 

 

NOMINAL VOLTAGE

 

 

 

MODEL

 

MODEL

208-230/3/60

 

460/3/60

 

575/3/60

 

 

 

RLA*

LRA

RLA*

 

LRA

RLA*

 

LRA

 

1A

ZP120

33.3

239

17.9

 

125

12.8

 

80

 

 

 

 

 

 

 

 

 

 

 

050

1B

ZP137

48.0

245

18.6

 

125

14.7

 

100

2A

ZP121

33.3

239

17.9

 

125

12.8

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2B

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

1A

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

 

 

 

 

 

 

 

051

1B

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

 

 

 

 

 

 

2A

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

2B

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

1A

ZP137

48.0

245

18.6

 

125

14.7

 

100

060

1B

ZP182

55.7

340

26.9

 

172

23.7

 

132

 

 

 

 

 

 

 

 

 

 

2A

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

2B

ZP182

55.7

340

26.9

 

172

23.7

 

132

 

1A

ZP154

51.3

300

22.4

 

150

19.8

 

109

 

 

 

 

 

 

 

 

 

 

 

061

1B

ZP182

55.7

340

25.0

 

172

23.7

 

132

2A

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2B

ZP182

55.7

340

25.0

 

172

23.7

 

132

TABLE 2-8 – POWER SUPPLY VOLTAGE LIMITS

POWER SUPPLY

MINIMUM VOLTAGE

MAXIMUM VOLTAGE

208/230V/3PH/60HZ

187

253

 

 

 

460V/3PH/60HZ

414

506

575V/3PH/60HZ

518

632

 

 

 

JOHNSON CONTROLS

29

Page 29
Image 29
York YPAL 050, YPAL 061, YPAL 051 manual Electrical Data, Load Definitions, Electrical Service Sizing, Compressor Data R410A