VAV Heat Relay Output
This is a 24 VDC output that is turned on when the unit is in the heating mode. The field can use this as a signal to trigger the opening of the VAV boxes for heating operation. This feature uses two ¼ inch male tabs identified as (VAV OPEN +) and (VAV OPEN
Supply Air Temperature Reset
An external 0 to 10 VDC input can be applied to terminals (REM+) and
Below 1.0 VDC – the blower is
Below 1.5 VDC – the cooling and heating is disabled
At 2.0 VDC – the control uses the lower set point
Between 2.0 VDC and 10 VDC the change in set point is proportional to the change in voltage.
At 10.0 VDC – the control uses the upper set point
FORM
COMMUNICATION
The Simplicity Unit Controller is designed to communicate using Modbus Client protocol. Through the use of a ModLINC translator the unit can also communicate using BACnet MS/TP protocol.
Through the use of a FREEnet Serial or USB adapter 2 the Simplicity Unit Controller can be connected directly
to a computer. Multiple units can be daisy chained together and through the use of the adapter connected to a computer or a network. This allows remote monitoring of the unit as well as the ability to change settings and options from a remote location.
Connection to the unit is done through either of two
See Table 6-1 for parameter points list.
DIRTY FILTER SWITCH
On units with a dirty filter switch option, an adjustable differential pressure switch is installed to monitor the pressure drop across the filters. When the pressure drop across the filters exceeds the setting of the switch, the switch closes sending a