User Interface Control Center
FORM
TABLE 6-2 - SIMPLICITY ELITE DATA MAP
Writing to any register not in this list may cause erratic operation
This product is not designed to accept continuous writes to data stored in long term memory. It is recommended that no stored value be changed more often than an average of once per hour. Changing data more often risks damaging the ability of the control to store new data for the full life of the product.
|
|
| INITIAL/ |
|
|
|
|
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX |
| DESCRIPTION |
(HEX) | (DEC) | VALUE | VALUE | VALUE |
| ||
|
|
| |||||
|
|
| (HEX) |
|
|
|
|
00 H | 0 H | NA | 20 | NA | NA | DEVICE ID = 20 FOR ELITE | |
00 L | 0 L | NA | - | 0 | 255 | DEVICE SOFTWARE REVISION | |
01 H | 1 H | NA | 54 | - | - | OPTION BYTE #1 | |
|
| 0 |
|
|
| BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 0 STAGES OF | |
|
|
|
|
| HEAT; 0,1 = 1 STAGE; 1,0 = 2 STAGES; 1,1 = 3 STAGES | ||
|
|
|
|
|
| ||
|
| 1 |
|
|
|
|
|
|
| 2 |
|
|
| 1 | = HEATING MODE ENABLED FOR OPERATION |
|
| 3 |
|
|
| 1 | = TURN OFF CONTINUOUS FAN WHEN STARTING HEAT |
|
| 4 |
|
|
| 1 | = COOLING MODE ENABLED FOR OPERATION |
|
| 5 |
|
|
| 1 | = ECONOMIZER LOADING ACTIVE |
|
| 6 |
|
|
| 1 | = SPACE SENSOR FAULT OVERRIDE ENABLED |
|
|
|
|
|
|
| |
|
| 7 |
|
|
| NA | |
01 L | 1 L | NA | NA | NA | NA | ACTIVE ALARM | |
02 H | 2 H | NA | 30 | 0 | 30 | FAN ON DELAY FOR HEAT (SECONDS) | |
02 L | 2 L | NA | 60 | 0 | 255 | FAN OFF DELAY FOR HEAT (SECONDS) | |
03 H | 3 H | NA | 0 | 0 | 30 | FAN ON DELAY FOR COOL (SECONDS) | |
03 L | 3 L | NA | 30 | 0 | 255 | FAN OFF DELAY FOR COOL (SECONDS) | |
04 L | 4 L | NA | 3 | 1 | 10 | MINIMUM RUN TIME FOR COMPRESSORS (MINUTES) | |
05 H | 5 H | NA | 0 | 0 | 255 | HEATING #1 ACCUMULATED RUN TIME (HOURS, HIGH BYTE) | |
05 L | 5 L | NA | 0 | 0 | 255 | HEATING #1 ACCUMULATED RUN TIME (HOURS, LOW BYTE) | |
06 H | 6 H | NA | 0 | 0 | 255 | HEATING #2 ACCUMULATED RUN TIME (HOURS, HIGH BYTE) | |
06 L | 6 L | NA | 0 | 0 | 255 | HEATING #2 ACCUMULATED RUN TIME (HOURS, LOW BYTE) | |
|
|
|
|
|
|
| |
07 H | 7 H | NA | 0 | 0 | 255 | HEATING #3 ACCUMULATED RUN TIME (HOURS, HIGH BYTE) | |
07 L | 7 L | NA | 0 | 0 | 255 | HEATING #3 ACCUMULATED RUN TIME (HOURS, LOW BYTE) | |
|
|
|
|
|
| REGISTERS 8 - 20 STORE THE UNIT NAME. WHEN WRITTEN, | |
08 H - 14 L | 8 H - 20 L | NA |
|
|
| ALL 13 REGISTERS (AT 2 BYTES PER REGISTER) SHOULD BE | |
|
|
| WRITTEN. THE FORMAT IS ASCII. CHARACTER #1 IS IN 8 H. | ||||
|
|
|
|
|
| ||
|
|
|
|
|
| CHARACTER #2 IS IN 8 L. CHARACTER #3 IS IN 9 H, AND SO ON. | |
|
|
|
|
|
|
| |
15 H | 21 H | NA | - | - | - | INPUT STATUS BYTE #1 | |
|
| 0 |
|
|
| 1 | = Y1 ON (COOLING 1ST STAGE) |
|
|
|
|
|
|
|
|
|
| 1 |
|
|
| 1 | = Y2 ON (COOLING 2ND STAGE) |
|
| 2 |
|
|
| 1 | = Y3 ON (COOLING 3RD STAGE) |
|
|
|
|
|
|
|
|
|
| 3 |
|
|
| 1 | = Y4 ON (COOLING 4TH STAGE) |
|
| 4 |
|
|
| 1 | = W1 ON (HEATING 1ST STAGE) |
|
|
|
|
|
|
| Continued on next page |
130 |
|
|
|
|
|
| JOHNSON CONTROLS |