York YPAL 051, YPAL 061 manual Writing to any register not in this list may cause erratic operation

Models: YPAL 060 YPAL 051 YPAL 050 YPAL 061

1 168
Download 168 pages 27.04 Kb
Page 130
Image 130

User Interface Control Center

FORM 100.50-NOM6 (1207)

TABLE 6-2 - SIMPLICITY ELITE DATA MAP

Writing to any register not in this list may cause erratic operation

This product is not designed to accept continuous writes to data stored in long term memory. It is recommended that no stored value be changed more often than an average of once per hour. Changing data more often risks damaging the ability of the control to store new data for the full life of the product.

 

 

 

INITIAL/

 

 

 

 

ADDRESS

ADDRESS

BIT

DEFAULT

MIN

MAX

 

DESCRIPTION

(HEX)

(DEC)

VALUE

VALUE

VALUE

 

 

 

 

 

 

 

(HEX)

 

 

 

 

00 H

0 H

NA

20

NA

NA

DEVICE ID = 20 FOR ELITE

00 L

0 L

NA

-

0

255

DEVICE SOFTWARE REVISION

01 H

1 H

NA

54

-

-

OPTION BYTE #1

 

 

0

 

 

 

BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 0 STAGES OF

 

 

 

 

 

HEAT; 0,1 = 1 STAGE; 1,0 = 2 STAGES; 1,1 = 3 STAGES

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

2

 

 

 

1

= HEATING MODE ENABLED FOR OPERATION

 

 

3

 

 

 

1

= TURN OFF CONTINUOUS FAN WHEN STARTING HEAT

 

 

4

 

 

 

1

= COOLING MODE ENABLED FOR OPERATION

 

 

5

 

 

 

1

= ECONOMIZER LOADING ACTIVE

 

 

6

 

 

 

1

= SPACE SENSOR FAULT OVERRIDE ENABLED

 

 

 

 

 

 

 

 

 

7

 

 

 

NA

01 L

1 L

NA

NA

NA

NA

ACTIVE ALARM

02 H

2 H

NA

30

0

30

FAN ON DELAY FOR HEAT (SECONDS)

02 L

2 L

NA

60

0

255

FAN OFF DELAY FOR HEAT (SECONDS)

03 H

3 H

NA

0

0

30

FAN ON DELAY FOR COOL (SECONDS)

03 L

3 L

NA

30

0

255

FAN OFF DELAY FOR COOL (SECONDS)

04 L

4 L

NA

3

1

10

MINIMUM RUN TIME FOR COMPRESSORS (MINUTES)

05 H

5 H

NA

0

0

255

HEATING #1 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)

05 L

5 L

NA

0

0

255

HEATING #1 ACCUMULATED RUN TIME (HOURS, LOW BYTE)

06 H

6 H

NA

0

0

255

HEATING #2 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)

06 L

6 L

NA

0

0

255

HEATING #2 ACCUMULATED RUN TIME (HOURS, LOW BYTE)

 

 

 

 

 

 

 

07 H

7 H

NA

0

0

255

HEATING #3 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)

07 L

7 L

NA

0

0

255

HEATING #3 ACCUMULATED RUN TIME (HOURS, LOW BYTE)

 

 

 

 

 

 

REGISTERS 8 - 20 STORE THE UNIT NAME. WHEN WRITTEN,

08 H - 14 L

8 H - 20 L

NA

 

 

 

ALL 13 REGISTERS (AT 2 BYTES PER REGISTER) SHOULD BE

 

 

 

WRITTEN. THE FORMAT IS ASCII. CHARACTER #1 IS IN 8 H.

 

 

 

 

 

 

 

 

 

 

 

 

CHARACTER #2 IS IN 8 L. CHARACTER #3 IS IN 9 H, AND SO ON.

 

 

 

 

 

 

 

15 H

21 H

NA

-

-

-

INPUT STATUS BYTE #1

 

 

0

 

 

 

1

= Y1 ON (COOLING 1ST STAGE)

 

 

 

 

 

 

 

 

 

 

1

 

 

 

1

= Y2 ON (COOLING 2ND STAGE)

 

 

2

 

 

 

1

= Y3 ON (COOLING 3RD STAGE)

 

 

 

 

 

 

 

 

 

 

3

 

 

 

1

= Y4 ON (COOLING 4TH STAGE)

 

 

4

 

 

 

1

= W1 ON (HEATING 1ST STAGE)

 

 

 

 

 

 

 

Continued on next page

130

 

 

 

 

 

 

JOHNSON CONTROLS

Page 130
Image 130
York YPAL 051 manual Writing to any register not in this list may cause erratic operation, User Interface Control Center