Parameter Description and Options

FORM 100.50-NOM6 (1207)

TABLE 7-1 – DEFINITIONS (CONTINUED)

MENU ITEM

DEFINITION

HEAT 1 MIN RUN TIMER

THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME

TIMER FOR HEAT SECTION 1 IN SECONDS

 

HEAT 2 (W2)

THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL W2

- SECOND STAGE HEATING

 

HEAT 2 ASCD TIMER

THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR

HEAT SECTION 2 IN SECONDS.

 

HEAT 2 MIN RUN TIMER

THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME

TIMER FOR HEAT SECTION 2 IN SECONDS

 

HEAT 3 (W3)

THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL W3

- THIRD STAGE HEATING

 

HEAT 3 ASCD TIMER

THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR

HEAT SECTION 3 IN SECONDS.

 

HEAT 3 MIN RUN TIMER

THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME

TIMER FOR HEAT SECTION 3 IN SECONDS

 

 

IN THE INTERMITTENT FAN MODE THIS IS THE TIME DELAY

HEAT FAN OFF DELAY

BETWEEN THE TIME THE HEAT CALL IS TERMINATED AND THE

 

SHUT DOWN OF THE SUPPLY FAN

 

IN THE INTERMITTENT FAN MODE THIS IS THE TIME DELAY

HEAT FAN ON DELAY

BETWEEN THE TIME THE HEATING OPERATION IS VERIFIED

 

AND THE START OF SUPPLY FAN OPERATION

HEATING MODE ENABLED FOR OPERATION

THIS PARAMETER MUST BE TURNED ON TO ALLOW HEATING

OPERATION

 

HEATING NUMBER #1 ACCUMULATED RUNTIME

THIS IS THE NUMBER OF HOURS THAT HEATING SYSTEM 1 HAS

BEEN OPERATIVE

 

HEATING NUMBER #2 ACCUMULATED RUNTIME

THIS IS THE NUMBER OF HOURS THAT HEATING SYSTEM 2 HAS

BEEN OPERATIVE

 

HEATING NUMBER #3 ACCUMULATED RUNTIME

THIS IS THE NUMBER OF HOURS THAT HEATING SYSTEM 3 HAS

BEEN OPERATIVE

 

HEATING OUTPUT #1 (H1)

THIS IS THE STATUS OF THE BINARY OUTPUT FROM THE UNIT

CONTROLLER TO HEAT SECTION # 1, OFF/ON

 

HEATING OUTPUT #2 (H2)

THIS IS THE STATUS OF THE BINARY OUTPUT FROM THE UNIT

CONTROLLER TO HEAT SECTION # 2, OFF/ON

 

HEATING OUTPUT #3 (H3)

THIS IS THE STATUS OF THE BINARY OUTPUT FROM THE UNIT

CONTROLLER TO HEAT SECTION # 3, OFF/ON

 

HOT GAS PRESENT ON COMPRESSOR # 1

THIS PARAMETER MUST BE TURNED ON WHEN HOT GAS

BYPASS IS INSTALLED

 

HOT GAS REHEAT

THIS PARAMETER WOULD BE TURNED ON TO ENABLE HOT GAS

REHEAT. THIS FEATURE IS NOT AVAILABLE ON THESE UNITS

 

HOT WATER VALVE OUTPUT STATUS

THIS GIVES THE STATUS OF THE ANALOG UNIT CONTROLLER

OUTPUT TO THE HYDRONIC VALVE IN %

 

HOT WATER VALVE OUTPUT STATUS

THIS GIVES THE STATUS OF THE ANALOG UNIT CONTROLLER

OUTPUT TO THE HYDRONIC VALVE IN % WHEN THE UNIT IS

(REVERSE ACTING)

PROGRAMMED FOR A REVERSE ACTING VALVE

 

 

THIS PARAMETER IS USED TO ENTER THE HOUR OF THE

HOUR

CURRENT TIME BASED ON A 24 HOUR SCHEDULE, 13 WOULD

 

BE 1 PM

 