York YPAL 051, YPAL 061, YPAL 050 Parameter Description and Options, 1 - DEFINITIONS CONTINUED

Models: YPAL 060 YPAL 051 YPAL 050 YPAL 061

1 168
Download 168 pages 27.04 Kb
Page 150
Image 150

Parameter Description and Options

FORM 100.50-NOM6 (1207)

TABLE 7-1 – DEFINITIONS (CONTINUED)

MENU ITEM

DEFINITION

OUTSIDE AIR HUMIDITY

THIS PARAMETER GIVES THE CURRENT VALUE OF THE

OUTSIDE AIR HUMIDITY INPUT

 

OUTSIDE AIR HUMIDITY SENSOR INSTALLED

THIS PARAMETERS IDENTIFIES TO THE UNIT CONTROLLER

THAT AN OUTDOOR AIR HUMIDITY SENSOR IS INSTALLED

 

OUTSIDE AIR TEMP

THIS PARAMETER GIVES THE CURRENT VALUE FOR THE

OUTDOOR AIR TEMPERATURE INPUT

 

POWER EXHAUST INSTALLED

THIS PARAMETER MUST BE TURNED ON TO ENABLE POWER

EXHAUST OPERATION

 

PRE-OCCUPANCY PURGE ENABLE

THIS PARAMETER IS USED TO TURN ON THE PRE-OCCUPANCY

 

PURGE OPTION. THIS FEATURE TURNS ON THE SUPPLY FAN

 

AND OPENS THE OUTDOOR AIR DAMPER PRIOR TO GOING

 

INTO THE OCCUPIED MODE.

PRE-OCCUPANCY PURGE TIME (HOURS OF

THIS PARAMETER ESTABLISHES THE NUMBER OF HOURS

DAY)

PRIOR TO THE OCCUPIED START TIME THAT THE PRE-

 

OCCUPANCY PURGE WOULD START

PRE-OCCUPANCY PURGE TIME (MINUTES OF

THIS PARAMETER ESTABLISHES THE NUMBER OF MINUTES

DAY)

PRIOR TO THE OCCUPIED START TIME THAT THE PRE-

 

OCCUPANCY PURGE WOULD START

PURGE SWITCH

THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL

 

PURGE - PURGE MODE

REDLINE

THIS FEATURE CAN BE USED TO TEMPORALLY REDUCE THE

 

ELECTRICAL CONSUMPTION OF THE UNIT BY TURNING OFF

 

SOME OF THE ACTIVE COMPRESSORS. THIS FEATURE IS ONLY

 

AVAILABLE THROUGH A COMMUNICATED INPUT.

REMOTE CONTROL INPUT ENABLE FOR THIRD

THIS ALLOWS THE USE OF AN EXTERNAL 0 TO 10 VDC SIGNAL

PARTY BAS

TO RESET THE SUPPLY AIR TEMPERATURE SETPOINT ON VAV

 

UNITS.

REMOTE CONTROL INPUT VALUE

GIVES THE VALUE OF THE 0 TO 10 VDC REMOTE CONTROL

 

INPUT FOR THE REMOTE CONTROL OF THE DAMPERS

RETURN AIR ENTHALPY

THIS PARAMETER IS THE CALCULATED VALUE FOR THE

 

RETURN AIR ENTHALPY

RETURN AIR HUMIDITY

THIS PARAMETER GIVES THE CURRENT VALUE OF THE

 

RETURN AIR HUMIDITY INPUT

RETURN AIR HUMIDITY SENSOR INSTALLED

THIS IS THE RETURN ENTHALPY SETTING WHICH THE UNIT

 

CONTROLLER USES TO DETERMINE WHEN TO SWITCH INTO

 

ECONOMIZER OPERATION IN DUAL ENTHALPY ECONOMIZER

 

MODE

RETURN AIR TEMP

THIS PARAMETER GIVE THE CURRENT VALUE FOR THE

 

RETURN AIR TEMPERATURE INPUT

RUN TEST

BY TURNING THIS FEATURE ON THE UNIT CONTROLLER

 

SEQUENCING ON ALL THE BINARY OUTPUTS TO VERIFY

 

OPERATION OF THE UNIT ELECTRICAL DEVICES

SENSOR SPACE TEMPERATURE SENSOR

THIS IS THE ACTUAL SPACE SENSOR OFFSET AMOUNT BEING

OUTSET

USED BY THE UNIT CONTROLLER IN DEGREES.

Continued on next page

150

JOHNSON CONTROLS

Page 150
Image 150
York YPAL 051, YPAL 061, YPAL 050, YPAL 060 manual Parameter Description and Options, 1 - DEFINITIONS CONTINUED