TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
|
|
| INITIAL/ |
|
|
|
|
|
| |
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX |
| DESCRIPTION |
|
| |
(HEX) | (DEC) | VALUE | VALUE | VALUE |
|
|
| |||
|
|
|
|
| ||||||
|
|
| (HEX) |
|
|
|
|
|
| |
|
|
|
|
|
| BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 2 STAGES OF |
|
| ||
|
| 0 |
|
|
| COMPRESSION; 0,1 = 3 STAGES; 1,0 = 4 STAGES; 1,1 = 4 |
|
| ||
|
|
|
|
|
| STAGES |
|
| ||
|
| 1 |
|
|
|
|
|
|
| |
|
| 2 |
|
|
| 1 | = SAT LIMIT FOR COOLING ENABLED |
|
| |
|
| 3 |
|
|
| 1 | = SAT LIMIT FOR HEATING ENABLED |
|
| |
|
| 4 |
|
|
| 1 | = HYDRONIC HEATING ENABLED |
|
| |
|
| 5 |
|
|
| 1 | = HYDRONIC HEAT ACTUATOR VALVE REVERSE ACTING |
|
| |
|
| 6 |
|
|
| 1 | = REMOTE CONTROL INPUT ENABLED FOR THIRD PARTY BAS |
|
| |
|
| 7 |
|
|
| 1 | = HOT GAS REHEAT ENABLED |
|
| |
|
|
|
|
|
|
|
|
| ||
1A L | 26 L | NA | 4 | - | - | OPTION BYTE #3 |
|
| ||
|
| 0 |
|
|
| 1 | = VAV OCCUPIED HEATING ENABLED |
|
| |
|
| 1 |
|
|
| NA |
|
| ||
|
| 2 |
|
|
| 1 | = ECONOMIZER PRESENT |
|
| |
|
| 3 |
|
|
| 1 | = OUTSIDE AIR HUMIDITY SENSOR PRESENT |
|
| |
|
| 4 |
|
|
| 1 | = RETURN AIR HUMIDITY SENSOR PRESENT |
|
| |
|
| 5 |
|
|
| 1 | = |
|
| |
|
| 6 |
|
|
| 1 | = DEMAND VENTILATION ENABLED |
|
| |
|
| 7 |
|
|
| 1 | = BUILDING PRESSURE SENSOR INSTALLED |
|
| |
1B H | 27 H | NA | 193 | - | - | OPTION BYTE #4 |
|
| ||
|
| 0 |
|
|
| 1 | = POWER EXHAUST PRESENT |
|
| |
|
| 1 |
|
|
| 1 | = MODULATING POWER EXHAUST PRESENT |
|
| |
|
|
|
|
|
|
|
|
|
| |
|
| 2 |
|
|
| 1 | = EXHAUST VFD PRESENT |
|
| |
|
| 3 |
|
|
| 1 | = LOW AMBIENT KIT INSTALLED |
|
| |
|
| 4 |
|
|
| 1 | = DIRTY FILTER SWITCH PRESENT |
|
| |
|
| 5 |
|
|
| 1 | = |
|
| |
|
| 6 |
|
|
| 1 | = INDOOR FAN OPERATES WITH SPACE SENSOR PRESENT [CV] |
|
| |
|
| 7 |
|
|
| 1 | = DAYLIGHT SAVINGS TIME ENABLED |
|
| |
1B L | 27 L | NA | 8 | - | - | OPTION BYTE #5 |
|
| ||
6 | ||||||||||
|
|
|
|
|
|
|
|
| ||
|
| 0 |
|
|
| 1 | = RUN TEST ENABLED |
| ||
|
| 1 |
|
|
| 1 | = METER OF UNOCCUPIED OVERRIDE ENABLED |
|
| |
|
| 2 |
|
|
| 1 | = METRIC DISPLAY ENABLED |
|
| |
|
| 3 |
|
|
| 1 | = USE THERMOSTAT OR COMMUNICATIONS FLAG FOR |
|
| |
|
|
|
|
| OCCUPIED SIGNAL |
|
| |||
|
|
|
|
|
|
|
| |||
|
| 4 |
|
|
| 1 | = LEAD/LAG: EQUALIZE COMPRESSOR RUN TIME ENABLED |
|
| |
|
| 5 |
|
|
| 1 | = HOT GAS BYPASS PRESENT ON COMPRESSOR #1 |
|
| |
|
|
|
|
|
|
|
|
|
| |
|
| 6 |
|
|
| 1 | = THIRD PARTY BAS ECONOMIZER ENABLED |
|
| |
|
| 7 |
|
|
| 1 | = MORNING |
|
| |
1C H | 28 H | NA | 0 | 0 | 255 | ALARM 1 - MOST RECENT ALARM. |
|
| ||
1C L | 28 L | NA | 0 | 0 | 255 | ALARM 2 |
|
| ||
1D H | 29 H | NA | 0 | 0 | 255 | ALARM 3 |
|
| ||
1D L | 29 L | NA | 0 | 0 | 255 | ALARM 4 |
|
| ||
1E H | 30 H | NA | 0 | 0 | 255 | ALARM 5 – OLDEST STORED ALARM. |
|
| ||
|
|
|
|
|
|
|
|
|
|
Continued on next page