FORM 100.50-NOM6 (1207)

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

 

 

 

INITIAL/

 

 

 

 

 

 

ADDRESS

ADDRESS

BIT

DEFAULT

MIN

MAX

 

DESCRIPTION

 

 

(HEX)

(DEC)

VALUE

VALUE

VALUE

 

 

 

 

 

 

 

 

 

 

 

(HEX)

 

 

 

 

 

 

 

 

 

 

 

 

BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 2 STAGES OF

 

 

 

 

0

 

 

 

COMPRESSION; 0,1 = 3 STAGES; 1,0 = 4 STAGES; 1,1 = 4

 

 

 

 

 

 

 

 

STAGES

 

 

 

 

1

 

 

 

 

 

 

 

 

 

2

 

 

 

1

= SAT LIMIT FOR COOLING ENABLED

 

 

 

 

3

 

 

 

1

= SAT LIMIT FOR HEATING ENABLED

 

 

 

 

4

 

 

 

1

= HYDRONIC HEATING ENABLED

 

 

 

 

5

 

 

 

1

= HYDRONIC HEAT ACTUATOR VALVE REVERSE ACTING

 

 

 

 

6

 

 

 

1

= REMOTE CONTROL INPUT ENABLED FOR THIRD PARTY BAS

 

 

 

 

7

 

 

 

1

= HOT GAS REHEAT ENABLED

 

 

 

 

 

 

 

 

 

 

 

1A L

26 L

NA

4

-

-

OPTION BYTE #3

 

 

 

 

0

 

 

 

1

= VAV OCCUPIED HEATING ENABLED

 

 

 

 

1

 

 

 

NA

 

 

 

 

2

 

 

 

1

= ECONOMIZER PRESENT

 

 

 

 

3

 

 

 

1

= OUTSIDE AIR HUMIDITY SENSOR PRESENT

 

 

 

 

4

 

 

 

1

= RETURN AIR HUMIDITY SENSOR PRESENT

 

 

 

 

5

 

 

 

1

= PRE-OCCUPANCY PURGE ENABLED

 

 

 

 

6

 

 

 

1

= DEMAND VENTILATION ENABLED

 

 

 

 

7

 

 

 

1

= BUILDING PRESSURE SENSOR INSTALLED

 

 

1B H

27 H

NA

193

-

-

OPTION BYTE #4

 

 

 

 

0

 

 

 

1

= POWER EXHAUST PRESENT

 

 

 

 

1

 

 

 

1

= MODULATING POWER EXHAUST PRESENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

1

= EXHAUST VFD PRESENT

 

 

 

 

3

 

 

 

1

= LOW AMBIENT KIT INSTALLED

 

 

 

 

4

 

 

 

1

= DIRTY FILTER SWITCH PRESENT

 

 

 

 

5

 

 

 

1

= INTELLI-START OPERATION ENABLED

 

 

 

 

6

 

 

 

1

= INDOOR FAN OPERATES WITH SPACE SENSOR PRESENT [CV]

 

 

 

 

7

 

 

 

1

= DAYLIGHT SAVINGS TIME ENABLED

 

 

1B L

27 L

NA

8

-

-

OPTION BYTE #5

 

 

6

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

1

= RUN TEST ENABLED

 

 

 

1

 

 

 

1

= METER OF UNOCCUPIED OVERRIDE ENABLED

 

 

 

 

2

 

 

 

1

= METRIC DISPLAY ENABLED

 

 

 

 

3

 

 

 

1

= USE THERMOSTAT OR COMMUNICATIONS FLAG FOR

 

 

 

 

 

 

 

OCCUPIED SIGNAL

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

1

= LEAD/LAG: EQUALIZE COMPRESSOR RUN TIME ENABLED

 

 

 

 

5

 

 

 

1

= HOT GAS BYPASS PRESENT ON COMPRESSOR #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

1

= THIRD PARTY BAS ECONOMIZER ENABLED

 

 

 

 

7

 

 

 

1

= MORNING WARM-UP ENABLED

 

 

1C H

28 H

NA

0

0

255

ALARM 1 - MOST RECENT ALARM.

 

 

1C L

28 L

NA

0

0

255

ALARM 2

 

 

1D H

29 H

NA

0

0

255

ALARM 3

 

 

1D L

29 L

NA

0

0

255

ALARM 4

 

 

1E H

30 H

NA

0

0

255

ALARM 5 – OLDEST STORED ALARM.

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page

JOHNSON CONTROLS

133

Page 133
Image 133
York YPAL 050, YPAL 061, YPAL 051, YPAL 060 manual 133