Manuals
/
York
/
Household Appliance
/
Air Conditioner
York
YPAL 051, YPAL 061, YPAL 050, YPAL 060 manual User Interface Control Center, Fans, LD13019
Models:
YPAL 060
YPAL 051
YPAL 050
YPAL 061
1
114
168
168
Download
168 pages
27.04 Kb
111
112
113
114
115
116
117
118
<
>
Install
1 -R410-A PRESSURE / TEMPERATURE CHART
Unit Placement
Maintenance
Shielded wire must be used that is grounded at the control panel only
Supply Air Temperature Reset
Cooling Setup
Remove the combustion vent assembly from the return compartment
Fault Output
The Simplicity Control then starts a 3 minute timer
Page 114
Image 114
User Interface Control Center
FORM
100.50-NOM6
(1207)
FANS
LD13019
114
JOHNSON CONTROLS
Page 113
Page 115
Page 114
Image 114
Page 113
Page 115
Contents
INSTALLATION, OPERATION & MAINTENANCE
PACKAGED ROOFTOP AIR CONDITIONING UNITS
YPAL YPAL YPAL YPAL DESIGN LEVEL F SIMPLICITY ELITE CONTROL
New Release
GENERAL SAFETY GUIDELINES
SAFETY SYMBOLS
READ BEFORE PROCEEDING
CHANGEABILITY OF THIS DOCUMENT
NOMENCLATURE
BASE MODEL NUMBER
TABLE OF CONTENTS
TABLE OF CONTENTS
Thermostat
TABLE OF CONTENTS
INITIAL START-UP
CONDENSER FAN OPERATION
TABLE OF CONTENTS
VARIABLE AIR VOLUME VAV
COOLING COMPRESSOR LOCKOUT
TABLE OF CONTENTS
“Economizer Minimum Position” Alarm
TABLE OF CONTENTS
“Supply Air Temp Alarm Setpoint for Heating” Alarm
“Supply Air Temp Alarm Setpoint for Cooling” Alarm
TABLE OF CONTENTS
LIST OF TABLES
LIST OF FIGURES
SECTION 1 - INTRODUCTION
Condensing Section
Introduction
Heating Section
Steam and Hot water - This option will be available in the future
AIR MANAGEMENT
CONTROLS
INDOOR AIR QUALITY
Introduction
Gas Heat Sections - Are factory and leaked checked
installing contractor to take appropri
SECTION 2 - INSTALLATION
installed, it is the responsibility of the
If the VAV boxes in the conditioned
Installation
Proper rigging and handling of the equipment is
TABLE 2-2 - UNIT WEIGHTS - 050-061 MODELS
UNIT WEIGHTS
Installation
Center of Gravity
UNIT WEIGHTS CONTINUED
Unit Placement
TABLE 2-4 - UNIT CORNER WEIGHTS - 050-061 MODELS
Installation
ROOF CURB INSTALLATION
PHYSICAL DATA
TABLE 2-5 - PHYSICAL DATA - 050-061 MODELS
TABLE 2-5 - PHYSICAL DATA - 050-061 MODELS CONTINUED
PHYSICAL DATA CONTINUED
Installation
TABLE 2-6 - PHYSICAL DATA - COMPRESSORS
050-061 MODELS
GENERAL
ARRANGEMENT DRAWING
GENERAL
Installation
ARRANGEMENT
GENERAL
2-4 - GENERAL ARRANGEMENT DRAWING CONT
GENERAL
CONTINUED
GENERAL ARRANGEMENTDRAWINGS
ARRANGEMENT DRAWING CONT
FIG. 2-5 - GENERAL ARRANGEMENT DRAWING
Installation
CURB LAYOUT DRAWING / 050-061 MODELS
SUPPLY
ELECTRICAL DATA
Load Definitions
TABLE 2-9 - SUPPLY AND EXHAUST FAN MOTOR DATA - ODP
ELECTRIC DATA CONTINUED
Installation
TABLE 2-10 - SUPPLY AND EXHAUST FAN MOTOR DATA - TEFC
ELECTRIC DATA CONTINUED
TABLE 2-14 - ELECTRIC HEAT
TABLE 2-15 - AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
Installation
Condensate Drain Piping
Condensate Drain Trap
H must be at least 1 inch plus fan total static pressure X = 1/2 H
Fan input
Shielded wire must be used that is grounded at the control panel only
Thermostat
Space Sensor
Occupied / Unoccupied Input
Fault Output
CO2 Sensor
Shutdown Input
Supply Air Temperature Reset
VAV Heat Relay Output
Wiring Notes
FIELD CONTROL WIRING CONNECTIONS
Installation
2. All wiring is Class 2, low voltage
POWER WIRING
Overcurrent Protection Device Data is supplied on
Minimum CircuitAmpacity MCA is based on 125%
Installation
SINGLE-POINT POWER SUPPLY WIRING
Field Power Supply
FIG. 2-9 - SINGLE-POINT POWER SUPPLY WIRING
SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT SWITCH
Field Power Supply
Field Power Supply #2
DUAL-POINT POWER SUPPLY WIRING
Installation
Field Power Supply #1
CONTROLS
Duct Static Transducer
Static Pressure Probe Installation
Static Pressure Control Plastic Tubing Pneumatic Tubing
Building Pressure Transducer
Filter Compartment Economizer Compartment
FIG. 2-12 - ATMOSPHERIC SENSOR PROBE
LD13127
Duct Connection Guidelines
Installation
GAS HEATING
Gas Piping Recommendations
Installation
1. Remove the combustion vent assembly from the return compartment
SECTION 3 - START-UP
Unit Checks
Startup
FIG. 3-1 - FAN HOLD DOWN BRACKETS
Verifying Compressor Rotation
Compressor Oil Level Check
UNIT CHECKS - POWER APPLIED
Subcooling R-410A
Refrigerant Charge
Checking Superheat and Subcooling
Superheat R-410A
Leak Checking
TABLE 3-1 -R410-A PRESSURE / TEMPERATURE CHART
Startup
Pre-Start Checks
Post Start Checks
Manifold Gas Pressure Adjustment
Startup
Linkages
SECTION 4 - MAINTENANCE
Filters
Compressors
Motor Bearing Lubrication
Maintenance
Condenser Coils
Belt Tension
Belt Replacement
Belt Tensioning
Filter Drier Replacement
Forward Curved Fans
Maintenance
Fan Motor
Fan Shaft Bearings
Mounting Details
Maintenance
Eccentric Type
Bearing Lock Devices
FIG. 4-6 - BEARING WITH ECCENTRIC CAM
2. Torque screw “B” to full min. recommended value
Torquing of Set-screws
1. Torque screw “A” to 1/2 recommended torque
3. Torque screw “A” to full recommended value
THIS PAGE INTENTIONALLY LEFT BLANK
FORM 100.50-NOM6
JOHNSON CONTROLS
SECTION 5 - SEQUENCE OF OPERATION
Occupied Cooling
Sequence of Operation
Thermostat Input
Unoccupied Cooling
Unoccupied Heating
Space Sensor - Hard Wired or Communicated
Occupied Heating
Cooling Operation - Occupied or Unoccupied
Heating Operation - Occupied or Unoccupied
Stand Alone
Sequence of Operation
If after 5 minutes the return air temperature is between 1.5 F and 1.9 F above the “CV OCCUPIED COOLING SETPOINT” or “CV
Cooling Operation - Occupied or Unoccupied
Heating Operation - Occupied or Unoccupied
Cooling - Occupied with Thermostat
Sequence of Operation
Occupied Cooling with Hard Wired or Communi- cated Space Sensor
Cooling - Unoccupied with Thermostat
Occupied or Unoccupied Heating with a Thermo- stat
Heating - Unoccupied with a Hard Wired or Com- municated Space Sensor
Cooling - Unoccupied with a Hard Wired or Com- municated Space Sensor
Heating - Occupied with a Hard Wired or Com- municated Space Sensor
Sequence of Operation
Occupied Cooling - Stand Alone
Heating - Unoccupied Stand Alone
Cooling - Unoccupied Stand Alone
Heating - Occupied Stand Alone
Sequence of Operation
Operation and Pressure Control Range
Configuration Jumpers and Potentiometers
Constant Volume CV
Sequence of Operation
Variable Air Volume VAV
Sequence of Operation
VAV Supply Fan Speed Control
Dry Bulb
“DUCT PRESSURE SHUTDOWN SETPOINT”
“OUTSIDE AIR HUMIDITY SENSOR INSTALLED”
Single Enthalpy
Dual Enthalpy
“RETURN AIR HUMIDITY SENSOR INSTALLED”
Sequence of Operation
Constant Volume Economizer Set Point
Variable Air Volume Economizer Set Point
Sequence of Operation
Economizer / Compressor Operation
Economizer PI Loop Proportional and Integral
ECONOMIZER LOADING
Constant Volume
Variable Air Volume
Sequence of Operation
TABLE 5-5 COMPRESSOR ON WHEN SPACE INPUT SATISFIED
The unit must have an economizer installed
The unit type must be Constant Volume
The unit can not be in an active heating or cooling mode
Sequence of Operation
Conditions of Operation
Cooling
Sequence of Operation
Heating
The Simplicity Control then starts a 3 minute timer
Sequence of Operation
Sequence of Operation
Sequence of Operation
The following parameter must be enabled in order to use to feature
Sequence of Operation
Sequence of Operation
Sequence of Operation
The following must be enabled for Metric Operation
Sequence of Operation
Sequence of Operation
Subsequent Operation
When the “CV OCCUPIED HEATING” set point is reached the Simplicity Elite control will divide the elapsed time into 5-minute increments
Sequence of Operation
Sequence of Operation
Sequence of Operation
MORNING WARM-UP
The following parameters must be programmed to use Hydronic Heat
Sequence of Operation
Demand Ventilation
Manual
Fixed Minimum
Sequence of Operation
Sequence of Operation
Definitions
VENTILATION LOW AMBIENT MINIMUM POSITION RESET
Sequence of Operation
Sequence of Operation
On/Off Control Based on Outdoor Damper Posi- tion
On/Off Control Based on Building Pressure
Sequence of Operation
When the building static pressure is 0.025” WC or more above the “BUILDING PRESSURE SETPOINT” the Simplicity Elite control sends a 2 to 10 volt DC signal to open the exhaust damper. The output is at the “EXD+” and “EXD-“ terminals at the P14 connector
Modulating Damper with Fixed Speed Exhaust
Modulating Exhaust with a VFD
Sequence of Operation
Sequence of Operation
Criteria for Operation
Sequence of Operation
Sequence of Operation
The following parameters must be programmed to use this feature
Sequence of Operation
SAT ALARM FOR HEATING
Sequence of Operation “Supply Air Temp Alarm Setpoint for Heating”
Alarm
Sequence of Operation
“SUPPLY AIR TEMP ALARM SETPOINT FOR HEATING”
“Economizer Minimum Position” Alarm
“Supply Air Temp Alarm Setpoint for Cooling” Alarm
Sequence of Operation
“Economizer Minimum Position” Alarm
“ECONOMIZER MINIMUM POSITION” alarm and flash an Alarm Code
Sequence of Operation
SECTION 6 - USER INTERFACE
User Interface Control Center
TABLE 6-1 - PARAMETER POINTS LIST
100º - 180º
0.000
User Interface Control Center
TABLE - 6-1 - PARAMETER POINTS LIST CONT
SETTING
UNITS OF ADJUSTMENT
ADJUSTMENT
TABLE - 6-1 - PARAMETER POINTS LIST CONT
1. On the internet connect to YorkUPG.Com
Simplicity PC Download
User Interface Control Center
2. Left click on Dealers / Distributors
3. Left click on software
LD13037
USB Adapter Drive - Simplicity Pocket PC
User Interface Control Center
Establishing Communication
FREEnet USB
FREEnet Serial
User Interface Control Center
LD13040
LD13041
7. Left-click on the particular Simplicity device de- sired
User Interface Control Center
JOHNSON CONTROLS
LD13043
DEVICE NAMES
EQUIPMENT INSTALLATION
SIMPLICITY PC DATA SCREENS
LD13015
User Interface Control Center
SENSOR READINGS
LD13017
ECONOMIZER/EXHAUST
LD13018
User Interface Control Center
FANS
LD13019
COOLING SETUP
LD13020
User Interface Control Center
COOLING STATUS
LD13021
HEATING SETUP
LD13022
User Interface Control Center
HEATING STATUS
LD13023
SYSTEM OPTIONS
LD13024
User Interface Control Center
OUTPUTS/STATUS
LD13025
LD13014
INPUTS
COMFORT/DEMAND VENTILATION
LD13026
CLOCK
User Interface Control Center
GRAPHIC
JOHNSON CONTROLS
WEEKLY SCHEDULE SETTINGS
Weekly Schedule
LD13029
User Interface Control Center
Holiday Schedule
HOLIDAY SCHEDULE
ALARMS
LD13031
REVISING SETTINGS
User Interface Control Center
LD13032
To open the change screen double left click
LD13033
User Interface Control Center
LD13034
LD13035
Writing to any register not in this list may cause erratic operation
User Interface Control Center
TABLE 6-2 - SIMPLICITY ELITE DATA MAP
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
1A H
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
1A L
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
50 L
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
4A H
60 L
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
115 L
A5 L
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
A4 L
A6 L
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
BA H
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
CA L
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP CONT
SECTION 7 - PARAMETER DESCRIPTIONS AND OPTIONS
TABLE 7-1 - DEFINITIONS
Parameter Description and Options
TABLE 7-1 - DEFINITIONS CONTINUED
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
DEFINITION
Parameter Description and Options
TABLE 7-1 - DEFINITIONS CONTINUED
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
DEFINITION
Parameter Description and Options
TABLE 7-1 - DEFINITIONS CONTINUED
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
DEFINITION
Parameter Description and Options
TABLE 7-1 - DEFINITIONS CONTINUED
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
DEFINITION
Parameter Description and Options
TABLE 7-1 - DEFINITIONS CONTINUED
TABLE 7-1 - DEFINITIONS CONTINUED
MENU ITEM
DEFINITION
Parameter Description and Options
TABLE 7-1 - DEFINITIONS CONTINUED
SECTION 8 - SERVICE
Temperature Sensors
Duct Pressure Transducer
Discharge Pressure Transducer
Service
Return Fan Pressure Transducer
Building Pressure Transducer
TABLE 8-5 - PRESSURE TRANSDUCERS
Suction Pressure Transducer
Humidity Sensors
TABLE 8-6 - HUMIDITY SENSOR OUTPUTS
CO2 Sensor
Furnace Status Input
Service
TABLE 8-7 - CO2 SENSOR OUTPUT
RAT+
FIG. 8-1 - CONNECTOR LOCATIONS
TABLE 8-8 - WIRING DATA
SAT+
Service
TABLE 8-8 - WIRING DATA CONTINUED
TABLE 8-8 - WIRING DATA CONTINUED
VAV OPEN
VAV OPEN +
FAULTS AND LOCKOUTS
Service
TABLE 8-9 - ALARM CODE DESCRIPTIONS
ALARM CODE
DESCRIPTION
Service
TABLE 8-9 - ALARM CODE DESCRIPTIONS CONTINUED
YPAL 060 Compressors 1B and 2B YPAL 061 Compressors 1B, 2A and 2B
Gas Heating Alarms 16
Low Pressure Cutout Alarm 09, 10
Limit Switch Alarms 13, 14
Space Temperature Sensor Alarm
Outdoor Air Temperature Sensor Alarm
Supply Air Temperature Sensor Alarm
Return Air Temperature Sensor Alarm
Dirty Filter Switch Alarm
IAQ CO2 Sensor Alarm
Outdoor Humidity Sensor Alarm
Return Humidity Sensor Alarm
Time Clock Error Alarm
Economizer Minimum Position Alarm
Supply Air Temperature Cooling Alarm
Supply Air Temperature Heating Alarm
Space Temperature Trending Alarm
Subject to change without notice. Printed in USA
Form 100.50-NOM6 New Release
Tele
ALL RIGHTS RESERVED