
Startup
•Check the supply pressure. It must be within the limitations shown in Table
•The flame is stable, with flame present only at the end of the burner, no burning is occurring inside the burner. There should be little yellow tipping of the flame.
•There may be some smoke thru the flue, due to tooling oil burning off of the heat exchanger tub- ing.
TABLE 3-2 – LOW FIRE / HIGH FIRE PRESSURES
TYPE OF | LINE PRESSURE | MANIFOLD PRESSURE | |||||
|
|
| LOW FIRE | HIGH FIRE | |||
GAS | MINIMUM | MAXIMUM | |||||
+/- 0.3 “WC | +/- 0.3 “WC | ||||||
|
|
|
|
| |||
NATURAL | 4.5 “WC | 13.5 “WC | 1.2 “WC | 3.5 “WC | |||
PROPANE | 11.0 “WC | 13.5 “WC | 4.2 “WC | 10.0”WC | |||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
HIGH FIRE PRESSURE
REGULATOR
REGULATOR VENT COVER
|
|
| LOW FIRE |
|
|
| PRESSURE |
|
|
| REGULATOR |
|
| TWO STAGE | |
|
| PRESSURE | |
|
| REGULATOR | |
|
|
| |
INLET |
|
| LD11760a |
|
|
| |
|
|
|
|
FIG. 3-2 – MANIFOLD GAS PRESSURE
ADJUSTMENT
FORM
Manifold Gas Pressure Adjustment
•Small adjustments to the manifold gas pressure can be made by following the procedure outlined below. Refer to Figure
•Turn the gas off to the unit.
•Use a 3/16 inch Allen wrench to remove the 1/8 inch NPT plug from the outlet pressure tap of the valve.
•Install a brass adapter to allow the connection of a hose to the outlet pressure tap of the valve.
•Connect the hose to a manometer capable of read- ing the required manifold pressure value.
•Turn the gas back on.
•Place the heat section into high fire operation.
•Compare the high fire manifold pressure to Table
•To adjust the high fire manifold pressure remove the cap from the high fire pressure regulator. Use a 3/32Allen wrench to make the manifold pressure adjustment. To increase the manifold pressure, turn the screw clockwise; to decrease the manifold pressure, turn the screw counterclockwise. Place your finger over the adjustment opening while verifying the manifold pressure.
•Place the heat section into low fire operation.
•Compare the low fire manifold pressure to Table
•To adjust the low fire manifold pressure remove the cap from the low fire pressure regulator. Use a 3/32 inch Allen wrench to make the manifold pressure adjustment. To increase the manifold pressure, turn the screw clockwise; to decrease the manifold pressure, turn the screw counter- clockwise. Place your finger over the adjustment opening while verifying the manifold pressure.
•Turn the heat off.
•Turn the gas off.
•Remove the brass tubing adapter and replace the plug in the outlet pressure tap.
TABLE 3-3 – GAS HEAT PERFORMANCE DATA
| GAS INPUT CAPACITY | MAXIMUM OUTPUT CAPACITY | AIRFLOW | TEMP. RISE | ||
UNIT | (BTU/HR X 1000) | (BTU/HR X 1000) | MIN. | MAX. | (°F) | |
|
|
|
| |||
375 | 300 | 7,500 | 24,000 | 40 | ||
750 | 600 | 14,000 | 24,000 | 40 | ||
| ||||||
| 1125 | 900 | 21,000 | 24,000 | 40 |
54 | JOHNSON CONTROLS |