York YPAL 051, YPAL 061, YPAL 050, YPAL 060 manual Startup, Manifold Gas Pressure Adjustment

Models: YPAL 060 YPAL 051 YPAL 050 YPAL 061

1 168
Download 168 pages 27.04 Kb
Page 54
Image 54

Startup

Check the supply pressure. It must be within the limitations shown in Table 3-2. Supply pressure should be checked with all gas appliances in the building at full fire. At no time should the standby gas pressure exceed 13.5" WC, nor the operating pressure drop below 4.5" WC for natural gas or 11.0" WC for propane. If the gas pressure is out- side these limits, contact the installing mechanical contractor for corrective action.

The flame is stable, with flame present only at the end of the burner, no burning is occurring inside the burner. There should be little yellow tipping of the flame.

There may be some smoke thru the flue, due to tooling oil burning off of the heat exchanger tub- ing.

TABLE 3-2 – LOW FIRE / HIGH FIRE PRESSURES

TYPE OF

LINE PRESSURE

MANIFOLD PRESSURE

 

 

 

LOW FIRE

HIGH FIRE

GAS

MINIMUM

MAXIMUM

+/- 0.3 “WC

+/- 0.3 “WC

 

 

 

 

 

NATURAL

4.5 “WC

13.5 “WC

1.2 “WC

3.5 “WC

PROPANE

11.0 “WC

13.5 “WC

4.2 “WC

10.0”WC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH FIRE PRESSURE

REGULATOR

REGULATOR VENT COVER

 

 

 

LOW FIRE

 

 

 

PRESSURE

 

 

 

REGULATOR

 

 

TWO STAGE

 

 

PRESSURE

 

 

REGULATOR

 

 

 

INLET

 

 

LD11760a

 

 

 

 

 

 

 

FIG. 3-2 – MANIFOLD GAS PRESSURE

ADJUSTMENT

FORM 100.50-NOM6 (1207)

Manifold Gas Pressure Adjustment

Small adjustments to the manifold gas pressure can be made by following the procedure outlined below. Refer to Figure 3-2 for the high and low fi re pressure regulator adjustment locations.

Turn the gas off to the unit.

Use a 3/16 inch Allen wrench to remove the 1/8 inch NPT plug from the outlet pressure tap of the valve.

Install a brass adapter to allow the connection of a hose to the outlet pressure tap of the valve.

Connect the hose to a manometer capable of read- ing the required manifold pressure value.

Turn the gas back on.

Place the heat section into high fire operation.

Compare the high fire manifold pressure to Table 3-2.

To adjust the high fire manifold pressure remove the cap from the high fire pressure regulator. Use a 3/32Allen wrench to make the manifold pressure adjustment. To increase the manifold pressure, turn the screw clockwise; to decrease the manifold pressure, turn the screw counterclockwise. Place your finger over the adjustment opening while verifying the manifold pressure.

Place the heat section into low fire operation.

Compare the low fire manifold pressure to Table 3-2.

To adjust the low fire manifold pressure remove the cap from the low fire pressure regulator. Use a 3/32 inch Allen wrench to make the manifold pressure adjustment. To increase the manifold pressure, turn the screw clockwise; to decrease the manifold pressure, turn the screw counter- clockwise. Place your finger over the adjustment opening while verifying the manifold pressure.

Turn the heat off.

Turn the gas off.

Remove the brass tubing adapter and replace the plug in the outlet pressure tap.

TABLE 3-3 – GAS HEAT PERFORMANCE DATA

 

GAS INPUT CAPACITY

MAXIMUM OUTPUT CAPACITY

AIRFLOW

TEMP. RISE

UNIT

(BTU/HR X 1000)

(BTU/HR X 1000)

MIN.

MAX.

(°F)

 

 

 

 

50-61

375

300

7,500

24,000

40

750

600

14,000

24,000

40

 

 

1125

900

21,000

24,000

40

54

JOHNSON CONTROLS

Page 54
Image 54
York YPAL 051, YPAL 061, YPAL 050, YPAL 060 manual Startup, Manifold Gas Pressure Adjustment