Parameter Description and Options

 

FORM 100.50-NOM6 (1207)

TABLE 7-1 – DEFINITIONS (CONTINUED)

 

 

 

MENU ITEM

DEFINITION

 

THIS FEATURE IS ONLY AVAILABLE ON CONSTANT VOLUME

 

UNITS WITH A SPACE SENSOR USING THE INTERNAL

INTELLI-START OPERATION ENABLE

SCHEDULE. THIS OPTION BRINGS THE UNIT UP TO THE CV

 

OCCUPIED COOLING OR CV OCCUPIED HEATING SETPOINTS

 

PRIOR TO THE BEGINNING OF OCCUPIED OPERATION.

LAST ALARM 1

THIS PARAMETER IDENTIFIES THE MOST RECENT ALARM

LAST ALARM 2

THIS PARAMETER IDENTIFIES THE ALARM PRECEDING ALARM 1

LAST ALARM 3

THIS PARAMETER IDENTIFIES THE ALARM PRECEDING ALARM 2

LAST ALARM 4

THIS PARAMETER IDENTIFIES THE ALARM PRECEDING ALARM 3

LAST ALARM 5

THIS PARAMETER IDENTIFIES THE ALARM OLDEST IN HISTORY

LEAD-LAG EQUALIZE COMPRESSOR RUN TIME

THIS PARAMETER ENABLES LEAD LAG OPERATION FOR THE

ENABLED

COMPRESSOR, OFF OR ON

 

THIS GIVES THE STATUS OF THE BINARY INPUT FROM THE

LIMIT SWITCH #1

LIMIT SWITCH TO THE UNIT CONTROLLER FOR HEAT SECTION 1

 

IN SECONDS. OFF - FAULTED, ON - NORMAL

 

THIS GIVES THE STATUS OF THE BINARY INPUT FROM THE

LIMIT SWITCH #2

LIMIT SWITCH TO THE UNIT CONTROLLER FOR HEAT SECTION 2

 

IN SECONDS. OFF - FAULTED, ON - NORMAL

 

THIS GIVES THE STATUS OF THE BINARY INPUT FROM THE

LIMIT SWITCH #3

LIMIT SWITCH TO THE UNIT CONTROLLER FOR HEAT SECTION 3

 

IN SECONDS. OFF - FAULTED, ON - NORMAL

 

THIS FEATURE CAN BE USED TO TEMPORALLY REDUCE THE

LOADSHED

ELECTRICAL CONSUMPTION OF THE UNIT BY TURNING OFF

ALL OF THE ACTIVE COMPRESSORS. THIS FEATURE IS ONLY

 

 

AVAILABLE THROUGH A COMMUNICATED INPUT.

 

THIS PARAMETER IDENTIFIES IF THE SUPPLY VOLTAGE TO THE

LOW AC SUPPLY VOLTAGE DETECTED

CONTROL IS OUTSIDE THE ACCEPTABLE LIMITS. OFF = WITHIN

 

LIMITS, ON = FAULTED, OUTSIDE LIMITS

LOW AMBIENT ECONOMIZER MINIMUM

THIS PARAMETER ESTABLISHES THE MINIMUM POSITION

FOR THE OUTDOOR AIR DAMPER DURING LOW AMBIENT

POSITION

OPERATION

 

 

THIS PARAMETER IS USED TO TURN ON AND SET THE

 

OUTDOOR TEMPERATURE AT WHICH THIS FEATURE BECOMES

LOW AMBIENT ECONOMIZER SETPOINT

ACTIVE. A 0 VALUE TURNS THE FEATURE OFF. THIS FEATURE

REDUCES THE MINIMUM VENTILATION POSITION OF THE

 

 

OUTDOOR DAMPER DURING TIMES OF COLD OUTDOOR

 

TEMPERATURES

 

THIS PARAMETER MUST BE TURNED ON IF A LOW AMBIENT

LOW AMBIENT KIT INSTALLED

VFD IS INSTALLED ON THE CONDENSER FAN. THIS ALLOWS

 

COMPRESSOR OPERATION BELOW 45.0° F

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE LOW

LPS1

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 1 TO THE

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE LOW

LPS2

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 2 TO THE

 

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

Continued on next page