User Interface Control Center

FORM 100.50-NOM6 (1207)

TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)

ADDRESS

DESCRIPTION

UNITS OF ADJUSTMENT

RANGE OF

CURRENT

NUMBER

ADJUSTMENT

SETTING

 

 

36

OUTSIDE AIR HUMIDITY SENSOR INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

37

ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT

BTUS PER POUND

10 - 50

27

38

RETURN AIR HUMIDITY SENSOR INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

39

ECONOMIZER OUTSIDE AIR TEMP ENABLE

DEGREES F

40º - 80º

55º

SETPOINT

 

 

 

 

40

DEMAND VENTILATION (IAQ) ENABLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

41

IAQ SENSOR RANGE

PARTS PER MILLION

0 - 5000 PPM

2000

42

IAQ SETPOINT

PARTS PER MILLION

0 - 5000 PPM

1000

43

POWER EXHAUST INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

ON

44

MODULATING POWER EXHAUST INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

45

EXHAUST VFD INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

46

EXHAUST DAMPER POSITION FOR EXHAUST FAN

PERCENT OF ECONOMIZER

0 - 100%

80%

TO TURN ON (MODULATING ONLY)

POSITION

 

 

 

47

EXHAUST DAMPER POSITION FOR EXHAUST FAN

PERCENT OF ECONOMIZER

0 - 100%

20%

TO TURN OFF

POSITION

 

 

 

48

ECONOMIZER DAMPER POSITION FOR EXHAUST

PERCENT OF ECONOMIZER

0 - 100%

60%

FAN TO TURN ON (NON-MODULATING ONLY)

POSITION

 

 

 

49

ECONOMIZER DAMPER POSITION FOR EXHAUST

PERCENT OF ECONOMIZER

0 - 100%

20%

FAN TO TURN OFF (MODULATING ONLY)

POSITION

 

 

 

50

APS DATA

0 = CLOSED,

0 = CLOSED,

OPEN

1 = OPEN

1 = OPEN

 

 

 

51

DIRTY FILTER SWITCH INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

 

 

 

 

 

52

DIRTY FILTER SWITCH DATA

0 = CLOSED,

0 = OPEN,

OPEN

1 = OPEN

1 = CLOSED

 

 

 

53

COOLING MODE OPERATION ENABLE

PARAMETER BIT

0 = OFF, 1 = ON

ON

54

HEATING MODE ENABLED FOR OPERATION

PARAMETER BIT

0 = OFF, 1 = ON

ON

55

CONTINUOUS INDOOR FAN OPERATION WITH

PARAMETER BIT

0 = OFF, 1 = ON

ON

SENSOR

 

 

 

 

56

SPACE TEMPERATURE OFFSET RANGE

DEGREES F

-5º F - 5º F

0º F

57

METRIC OPERATION

PARAMETER BIT

0 = OFF, 1 = ON

OFF

58

THIRD PARTY BAS ECONOMIZER ENABLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

59

YEAR

YEAR (BCD)

00 - 99

4

 

 

 

 

 

60

MONTH

MONTH

1 - 12

1

61

DAY OF MONTH

DAY OF MONTH

1 - 31

1

 

 

 

 

 

62

DAY OF WEEK

DAY OF WEEK

1 - 7

1

63

HOUR

HOURS

0 - 23

0

64

MINUTE

MINUTES

0 - 59

0

65

SUPPLY AIR TEMP

DEGREES F

-40º - 180º

0

66

RETURN AIR TEMP

DEGREES F

-40º - 180º

0

67

OUTSIDE AIR TEMP

DEGREES F

-40º - 180º

0

68

SPACE TEMP

DEGREES F

-40º - 180º

0

69

OUTSIDE AIR HUMIDITY

HUMIDITY

0% - 100%

0

70

RETURN AIR HUMIDITY

HUMIDITY

0% - 100%

0

 

 

 

 

 

71

OCCUPIED INPUT ENABLE

PARAMETER BIT

0 = OFF, 1 = ON

OFF

 

 

 

Continued on next page