Sequence of Operation
“BUILDING STATIC PRESSURE SENSOR INSTALLED” – must be turned on using Parameter 85 under the PROGRAM key on the Simplicity Elite control board or under the EQUIPMENT INSTALLATION tab in the Simplicity PC software package.
“BUILDING PRESSURE SETPOINT” must be programmed using Parameter 31 under the PROGRAM key on the Simplicity Elite control board or under the ECONOMIZER/EXHAUST tab in the Simplicity PC software package.
“EXHAUST VFD INSTALLED” must be turned on using Parameter 45 under the PROGRAM key on the Simplicity Elite control board or under the ECONOMIZER/EXHAUST tab in the Simplicity PC software package.
Sequence of Operation
When the building static pressure is 0.025” WC or more above the “BUILDING PRESSURE SETPOINT” the Simplicity Elite control sends a 2 to 10 volt DC signal to Exhaust Fan VFD, the output is at the “EXD+” and
When the building static pressure is 0.025” WC or more below the “BUILDING PRESSURE SETPOINT” the Simplicity Elite control lowers the 2 – 10 volt DC output to the Exhaust Fan VFD. When the output is equal to or below 2 volts, the Exhaust Fan VFD enable input is removed.
PRE-OCCUPANCY PURGE
This feature allows the blower to come on and the economizer damper to open during the unoccupied period to purge the air within the conditioned space.
In order to use this feature the following parameters must be programmed:
FORM
–must be programmed using the SYSTEM OPTIONS tab in the Simplicity PC software package.
–must be programmed using the SYSTEM OPTIONS tab in the Simplicity PC software package.
Criteria for Operation
•The feature will only work when the internal scheduling feature is being used to determine occupied and unoccupied periods.
•The feature will only work on a day that has a occupied period scheduled.
Sequence of Operation
•The programmed
•While in the
•If the supply air temperature drops below 45.0° F the control will modulate the outdoor air damper closed until the supply air temperature rises above 50.0° F.
•If the supply air temperature rises above 90.0° F the control will modulate the outdoor air damper closed unit the supply air temperature falls below 85.0° F.