Parameter Description and Options
FORM
TABLE 7-1 – DEFINITIONS (CONTINUED)
MENU ITEM | DEFINITION | |
COMP 2 OUTPUT | THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE | |
UNIT CONTROLLER TO COMPRESSOR CIRCUIT 2 | ||
| ||
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE | |
COMP 2 OVERLOAD SWITCH | COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 2 TO | |
| THE UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. | |
COMP 3 ASCD ACTIVE | THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE | |
TIMER. ON MEANS THE COMPRESSOR 3 IS IN THIS MODE | ||
| ||
COMP 3 ASCD TIMER | THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR | |
COMPRESSOR 3 IN SECONDS. | ||
| ||
COMP 3 MIN RUN TIME | THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR | |
COMPRESSOR 3 IN SECONDS. | ||
| ||
COMP 3 OUTPUT | THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE | |
UNIT CONTROLLER TO COMPRESSOR CIRCUIT 3 | ||
| ||
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE | |
COMP 3 OVERLOAD SWITCH | COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 3 TO | |
| THE UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. | |
COMP 4 ASCD ACTIVE | THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE | |
TIMER. ON MEANS THE COMPRESSOR 4 IS IN THIS MODE | ||
| ||
COMP 4 ASCD TIMER | THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR | |
COMPRESSOR 4 IN SECONDS. | ||
| ||
COMP 4 MIN RUN TIME | THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR | |
COMPRESSOR 4 IN SECONDS. | ||
| ||
COMP 4 OUTPUT | THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE | |
UNIT CONTROLLER TO COMPRESSOR CIRCUIT 4 | ||
| ||
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE | |
COMP 4 OVERLOAD SWITCH | COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 4 TO | |
| THE UNIT CONTROLLER. ON - OKAY, OFF - FAULTED. | |
COMPRESSOR #1 ACCUMULATED RUNTIME | THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM | |
1 HAS BEEN OPERATIVE | ||
| ||
COMPRESSOR #2 ACCUMULATED RUNTIME | THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM | |
2 HAS BEEN OPERATIVE | ||
| ||
COMPRESSOR #3 ACCUMULATED RUNTIME | THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM | |
3 HAS BEEN OPERATIVE | ||
| ||
COMPRESSOR #4 ACCUMULATED RUNTIME | THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM | |
4 HAS BEEN OPERATIVE | ||
| ||
COMPRESSORS AVAILABLE FOR COOLING | THIS PARAMETER IDENTIFIES THE NUMBERS OF COMPRESSOR | |
THE UNIT CONTROLLER IS SET UP TO CONTROL | ||
| ||
CONDENSER FAN #1 OUTPUT | THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE | |
UNIT CONTROLLER TO THE #1 CONDENSER FAN, OFF OR ON | ||
| ||
CONDENSER FAN #2 OUTPUT | THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE | |
UNIT CONTROLLER TO THE #2 CONDENSER FAN, OFF OR ON | ||
| ||
CONTINUOUS INDOOR FAN OPERATION WITH | WHEN THIS PARAMETER IS TURNED ON, ON A CONSTANT | |
VOLUME UNIT THE SUPPLY FAN WILL OPERATE WHENEVER | ||
SENSOR | ||
THE UNIT IS IN THE OCCUPIED MODE | ||
| ||
| THIS IDENTIFIES IF THE UNIT CONTROLLER IS IN THE COMFORT | |
CONTROL IN COMFORT VENTILATION | VENTILATION MODE. OFF NOT IN MODE, ON IN COMFORT | |
| VENTILATION MODE. | |
| Continued on next page | |
142 | JOHNSON CONTROLS |