| FORM |
| ||
TABLE |
|
|
| |
|
|
|
| |
MENU ITEM | DEFINITION |
|
| |
SPACE SENSOR DETECTED | IDENTIFIES IF THE UNIT CONTROLLER HAS DETECTED THE |
|
| |
| PRESENCE OF A SPACE SENSOR. IF THE UNIT CONTROLLER |
|
| |
| DETECTS A SPACE SENSOR IT WILL SELF CONFIGURE TO USE |
|
| |
| IT FOR CONTROL OF THE UNIT. |
|
| |
SPACE SENSOR FAULT OVERRIDE ENABLE | WHEN THIS OPTION IS TURNED ON THE CONTROLLER USES |
|
| |
| THE RETURN AIR TEMPERATURE INPUT IN PLACE OF THE |
|
| |
| SPACE TEMPERATURE INPUT TO CONTROL THE UNIT. TURING |
|
| |
| THIS OPTION ON ALLOWS THE UNIT TO OPERATE IN A VAV |
|
| |
| STAND ALONE MODE |
|
| |
SPACE TEMP | THIS PARAMETER GIVES THE CURRENT VALUE OF THE SPACE |
|
| |
| TEMPERATURE INPUT |
|
| |
SPACE TEMP TRENDING ALARM TEMP | TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET |
|
| |
| TO OTHER THEN 0. A VALUE OTHER THEN 0 IS THE NUMBER |
|
| |
| OF DEGREES ABOVE OR BELOW THE SETPOINT THE |
|
| |
| TEMPERATURE MUST BE TO START THE TIMING |
|
| |
SPACE TEMP TRENDING ALARM TIME | THIS PARAMETER ESTABLISHED THE AMOUNT OF TIME THE |
|
| |
| SPACE TEMPERATURE MUST BE TRENDING ABOVE OR BELOW |
|
| |
| THE SPACE TEMP TRENDING ALARM TEMP BEFORE THE ALARM |
|
| |
| WILL BE INITIATED. |
|
| |
SPACE TEMPERATURE OFFSET RANGE | THIS SETPOINT ESTABLISHES THE MAXIMUM AMOUNT OF |
|
| |
| HEATING OR COOLING RESET AVAILABLE THROUGH THE |
|
| |
| RESET FEATURE ON A SPACE SENSOR. |
|
| |
STAGES OF HEAT AVAILABLE | THIS PARAMETER IDENTIFIES THE NUMBER OF STAGES OF |
|
| |
| HEAT THE UNIT CONTROLLER IS SET UP TO CONTROL |
|
| |
STATE COMPRESSOR OFF - LOW SUPPLY | THIS IDENTIFIES THE COMPRESSORS ARE OFF BECAUSE OF |
|
| |
VOLTAGE | LOW SUPPLY VOLTAGE. ON WHEN THIS STATE IS ACTIVE |
|
| |
STATE COMPRESSORS OFF - LOW AMBIENT | THIS IDENTIFIES THE COMPRESSOR ARE OFF BECAUSE |
|
| |
TEMPERATURE | THE OUTDOOR TEMPERATURE IS BELOW THE LOW AMBIENT |
|
| |
| LOCKOUT TEMPERATURE. ON WHEN THIS STATE IS ACTIVE |
|
| |
STATUS COMPRESSOR OFF - ECON IS USING | THIS IDENTIFIES THE COMPRESSORS ARE OFF BECAUSE THE |
|
| |
FREE COOLING | UNIT CONTROLLER IS USING OUTDOOR AIR FOR COOLING. ON |
|
| |
| WHEN THIS IS ACTIVE |
|
| |
SUPPLY AIR TEMP | THIS PARAMETER GIVES THE CURRENT VALUE FOR THE |
|
| |
| SUPPLY AIR TEMPERATURE INPUT |
|
| |
SUPPLY AIR TEMP ALARM SETPOINT FOR | TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET TO |
|
| |
COOLING | OTHER THEN 0. A VALUE OTHER THEN 0 ESTABLISHES THE |
|
| |
| SETPOINT TO USE IN DETERMINE WHEN TO INITIATE A SUPPLY |
|
| |
| AIR TEMP ALARM FOR COOLING |
|
| |
SUPPLY AIR TEMP ALARM SETPOINT FOR | TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET TO |
|
| |
7 | ||||
HEATING | OTHER THEN 0. A VALUE OTHER THEN 0 ESTABLISHES THE |
| ||
| SETPOINT TO USE IN DETERMINE WHEN TO INITIATE A SUPPLY |
|
| |
|
| |||
| AIR TEMP ALARM FOR HEATING |
|
| |
SUPPLY AIR TEMP LIMIT COOLING SETPOINT | THIS SET POINT IS USED BY THE UNIT CONTROLLER DURING |
|
| |
| ECONOMIZER LOADING OR SUPPLY AIR TEMP LIMIT MODE OF |
|
| |
| OPERATION |
|
|
Continued on next page
JOHNSON CONTROLS | 151 |