FORM 100.50-NOM6 (1207)

 

TABLE 7-1 – DEFINITIONS (CONTINUED)

 

 

 

 

 

 

 

MENU ITEM

DEFINITION

 

 

SPACE SENSOR DETECTED

IDENTIFIES IF THE UNIT CONTROLLER HAS DETECTED THE

 

 

 

PRESENCE OF A SPACE SENSOR. IF THE UNIT CONTROLLER

 

 

 

DETECTS A SPACE SENSOR IT WILL SELF CONFIGURE TO USE

 

 

 

IT FOR CONTROL OF THE UNIT.

 

 

SPACE SENSOR FAULT OVERRIDE ENABLE

WHEN THIS OPTION IS TURNED ON THE CONTROLLER USES

 

 

 

THE RETURN AIR TEMPERATURE INPUT IN PLACE OF THE

 

 

 

SPACE TEMPERATURE INPUT TO CONTROL THE UNIT. TURING

 

 

 

THIS OPTION ON ALLOWS THE UNIT TO OPERATE IN A VAV

 

 

 

STAND ALONE MODE

 

 

SPACE TEMP

THIS PARAMETER GIVES THE CURRENT VALUE OF THE SPACE

 

 

 

TEMPERATURE INPUT

 

 

SPACE TEMP TRENDING ALARM TEMP

TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET

 

 

 

TO OTHER THEN 0. A VALUE OTHER THEN 0 IS THE NUMBER

 

 

 

OF DEGREES ABOVE OR BELOW THE SETPOINT THE

 

 

 

TEMPERATURE MUST BE TO START THE TIMING

 

 

SPACE TEMP TRENDING ALARM TIME

THIS PARAMETER ESTABLISHED THE AMOUNT OF TIME THE

 

 

 

SPACE TEMPERATURE MUST BE TRENDING ABOVE OR BELOW

 

 

 

THE SPACE TEMP TRENDING ALARM TEMP BEFORE THE ALARM

 

 

 

WILL BE INITIATED.

 

 

SPACE TEMPERATURE OFFSET RANGE

THIS SETPOINT ESTABLISHES THE MAXIMUM AMOUNT OF

 

 

 

HEATING OR COOLING RESET AVAILABLE THROUGH THE

 

 

 

RESET FEATURE ON A SPACE SENSOR.

 

 

STAGES OF HEAT AVAILABLE

THIS PARAMETER IDENTIFIES THE NUMBER OF STAGES OF

 

 

 

HEAT THE UNIT CONTROLLER IS SET UP TO CONTROL

 

 

STATE COMPRESSOR OFF - LOW SUPPLY

THIS IDENTIFIES THE COMPRESSORS ARE OFF BECAUSE OF

 

 

VOLTAGE

LOW SUPPLY VOLTAGE. ON WHEN THIS STATE IS ACTIVE

 

 

STATE COMPRESSORS OFF - LOW AMBIENT

THIS IDENTIFIES THE COMPRESSOR ARE OFF BECAUSE

 

 

TEMPERATURE

THE OUTDOOR TEMPERATURE IS BELOW THE LOW AMBIENT

 

 

 

LOCKOUT TEMPERATURE. ON WHEN THIS STATE IS ACTIVE

 

 

STATUS COMPRESSOR OFF - ECON IS USING

THIS IDENTIFIES THE COMPRESSORS ARE OFF BECAUSE THE

 

 

FREE COOLING

UNIT CONTROLLER IS USING OUTDOOR AIR FOR COOLING. ON

 

 

 

WHEN THIS IS ACTIVE

 

 

SUPPLY AIR TEMP

THIS PARAMETER GIVES THE CURRENT VALUE FOR THE

 

 

 

SUPPLY AIR TEMPERATURE INPUT

 

 

SUPPLY AIR TEMP ALARM SETPOINT FOR

TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET TO

 

 

COOLING

OTHER THEN 0. A VALUE OTHER THEN 0 ESTABLISHES THE

 

 

 

SETPOINT TO USE IN DETERMINE WHEN TO INITIATE A SUPPLY

 

 

 

AIR TEMP ALARM FOR COOLING

 

 

SUPPLY AIR TEMP ALARM SETPOINT FOR

TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET TO

 

 

7

HEATING

OTHER THEN 0. A VALUE OTHER THEN 0 ESTABLISHES THE

 

 

SETPOINT TO USE IN DETERMINE WHEN TO INITIATE A SUPPLY

 

 

 

 

 

AIR TEMP ALARM FOR HEATING

 

 

SUPPLY AIR TEMP LIMIT COOLING SETPOINT

THIS SET POINT IS USED BY THE UNIT CONTROLLER DURING

 

 

 

ECONOMIZER LOADING OR SUPPLY AIR TEMP LIMIT MODE OF

 

 

 

OPERATION

 

 

Continued on next page

JOHNSON CONTROLS

151

Page 151
Image 151
York YPAL 060, YPAL 061, YPAL 050, YPAL 051 manual 151