Parameter Description and Options
| FORM | |
TABLE |
| |
|
| |
MENU ITEM | DEFINITION | |
| THIS PARAMETER MUST BE SET TO ON TO ENABLE THE DIRTY | |
DIRTY FILTER SWITCH INSTALLED | FILTER FEATURE ON THE UNIT. A DIRTY FILTER SWITCH MUST | |
| ALSO BE INSTALLED FOR THIS FEATURE TO FUNCTION | |
| THE UNIT CONTROLLER VARIES THE SPEED OF THE SUPPLY | |
DUCT PRESSURE SETPOINT | FAN ON A VAV UNIT TO MAINTAIN THIS PROGRAMMED | |
| SETPOINT | |
| IF THE DUCT STATIC PRESSURE ON A VAV UNIT EXCEED THIS | |
DUCT PRESSURE SHUTDOWN SETPOINT | VALUE THE UNIT WILL SHUT DOWN THE FAN AND LOCK OUT | |
| THE UNIT | |
DUCT STATIC READING | THIS PARAMETER GIVES THE CURRENT VALUE OF THE DUCT | |
STATIC PRESSURE INPUT | ||
| ||
ECONOMIZER DAMPER OUTPUT STATUS | THIS GIVES THE STATUS OF THE UNIT CONTROLLER OUTPUT | |
TO THE ECONOMIZER DAMPER IN % | ||
| ||
ECONOMIZER DAMPER POSITION FOR | WHEN ON/OFF EXHAUST IS BEING USED THIS IS THE POSITION | |
OF THE ECONOMIZER DAMPER TO TURN OFF THE EXHAUST | ||
EXHAUST TURN OFF | ||
FAN | ||
| ||
ECONOMIZER DAMPER POSITION FOR | WHEN ON/OFF EXHAUST IS BEING USED THIS IS THE POSITION | |
EXHAUST TURN ON | OF THE ECONOMIZER DAMPER TO TURN ON THE EXHAUST FAN | |
| ON A CONSTANT VOLUME UNIT THE UNIT CONTROLLER WILL | |
ECONOMIZER FIRST STAGE SETPOINT | TRY AND MAINTAIN THE SUPPLY AIR TEMPERATURE AT THIS | |
SETPOINT IN THE ECONOMIZER MODE WITH A FIRST STAGE | ||
| ||
| COOLING CALL | |
ECONOMIZER INSTALLED | THIS PARAMETER MUST BE TURN ON TO ENABLE ECONOMIZER | |
OPERATION | ||
| ||
ECONOMIZER IS CURRENTLY USING FREE | THIS IDENTIFIES IF THE UNIT CONTROLLER IS USING OUTDOOR | |
COOLING | AIR TO SATISFY THE COOLING DEMAND, OFF OR ON | |
ECONOMIZER LOADING ENABLE | THIS PARAMETER MUST BE TURNED ON TO ENABLE | |
ECONOMIZER LOADING | ||
| ||
| THIS PARAMETER ESTABLISHES THE POSITION OF THE | |
ECONOMIZER MINIMUM POSITION | OUTDOOR DAMPER WHEN THE ECONOMIZER IS INACTIVE AND | |
| THE UNIT IS IN THE OCCUPIED MODE | |
| THIS IS THE OUTDOOR ENTHALPY SETTING WHICH | |
ECONOMIZER OUTSIDE AIR ENTHALPY | DETERMINES WHEN TO SWITCH INTO AND OUT OF | |
SETPOINT | ECONOMIZER OPERATION IN SINGLE ENTHALPY ECONOMIZER | |
| MODE | |
ECONOMIZER OUTSIDE AIR TEMP ENABLE | THIS IS THE OUTDOOR TEMPERATURE WHICH DETERMINES | |
SETPOINT | WHEN TO SWITCH INTO AND OUT OF ECONOMIZER OPERATION | |
| ON A CONSTANT VOLUME UNIT THE UNIT CONTROLLER WILL | |
ECONOMIZER SECOND STAGE SETPOINT | TRY AND MAINTAIN THE SUPPLY AIR TEMPERATURE AT THIS | |
SETPOINT IN THE ECONOMIZER MODE WITH A SECOND STAGE | ||
| ||
| COOLING CALL | |
| THIS PARAMETER MUST BE TURNED ON IF AN ENERGY | |
ERV INSTALLED | RECOVERY VENTILATOR IS INSTALLED. THIS FEATURE IS | |
| CURRENTLY NOT AVAILABLE ON THESE UNITS |