TABLE 8-9 – ALARM CODE DESCRIPTIONS (CONTINUED)
ALARM CODE | DESCRIPTION | |
24 | THE SUPPLY FAN BINARY OUTPUT HAS BEEN TURNED ON FOR 90 SECONDS AND THE AIR PROVING SWITCH | |
CIRCUIT HAS NOT CLOSED. | ||
| ||
25 | THE SUPPLY FAN BINARY OUTPUT HAS BEEN TURNED OFF FOR 90 SECONDS AND THE AIR PROVING SWITCH | |
CIRCUIT HAS NOT OPENED. | ||
| ||
26 | A MICROELECTRONICS FAILURE HAS OCCURRED AND THE CONTROL IS OPERATING ON DEFAULTS. | |
27 | A MICROELECTRONICS FAILURE HAS OCCURRED AND THE CONTROL IS DOWN DUE TO A FATAL FAULT. | |
28 | THIS INDICATES THE SUPPLY FAN BINARY OUTPUT IS TURNED ON AND THE SUPPLY FAN OVERLOAD CIRCUIT | |
IS OPEN. THIS HAS TO OCCUR 3 TIMES WITHIN A TWO HOUR WINDOW. | ||
| ||
29 | THIS INDICATES THE OUTDOOR AIR HUMIDITY SENSOR IS OUT OF RANGE. WHEN THIS OCCURS, THE UNIT | |
CONTROLLER SWITCHES THE ECONOMIZER TYPE TO DRY BULB. | ||
| ||
30 | THIS INDICATES THE RETURN AIR HUMIDITY SENSOR IS OUT OF RANGE. WHEN THIS OCCURS, THE UNIT | |
CONTROLLER SWITCHES THE ECONOMIZER TYPE TO SINGLE ENTHALPY. | ||
| ||
31 | THIS INDICATES THE IAQ (CO2) SENSOR IS OUT OF RANGE. THE UNIT CONTROLLER CHANGES THE | |
VENTILATION MODE TO FIXED MINIMUM. | ||
| ||
32 | THIS INDICATES THE REAL TIME CLOCK CANNOT BE READ AS A RESULT OF A HARDWARE FAILURE. | |
33 | THIS INDICATES THE SPACE TEMPERATURE OFFSET IS GREATER THAN 20 K OHMS. | |
34 | THIS INDICATES THE CV/VAV INPUT IS OUT OF RANGE. THE UNIT WILL LOCK OUT. | |
35 | THIS INDICATES THE | |
WILL SHUT DOWN UNTIL THE VOLTAGE RISES ABOVE 19.2 VAC. | ||
| ||
36 | THIS INDICATES THE UNIT COOLING AND HEATING OPERATION IS SHUT DOWN BECAUSE THE UNIT IS | |
OPERATING IN A SMOKE PURGE MODE. | ||
| ||
37 | THIS INDICATES THE DUCT STATIC PRESSURE HAS EXCEEDED THE PROGRAMMED DUCT STATIC SHUTDOWN | |
SETPOINT. | ||
| ||
38 | THIS INDICATES THE SUPPLY AIR TEMPERATURE HAS EXCEEDED THE PROGRAMMED SUPPLY AIR TEMP | |
ALARM SETPOINT FOR COOLING. | ||
| ||
39 | THIS INDICATES THE SUPPLY AIR TEMPERATURE HAS EXCEEDED THE PROGRAMMED SUPPLY AIR TEMP | |
ALARM SETPOINT FOR HEATING. | ||
| ||
40 | THIS INDICATES AN ECONOMIZER MINIMUM POSITION ALARM. | |
41 | THIS INDICATES THE SPACE TEMPERATURE IS ABOVE THE SPACE TEMP TRENDING ALARM TEMP AND MOVING | |
AWAY FROM THE SPACE TEMPERATURE SETPOINT. | ||
| ||
42 | THIS INDICATES THE DUCT STATIC HAS NOT RISEN QUICKLY ENOUGH IN A VAV UNIT WHEN THE SUPPLY FAN IS | |
ENERGIZED. | ||
| ||
43 | THIS INDICATES THE HYDRONIC HEAT FREEZE STAT HAS OPENED AND THE OUTDOOR TEMPERATURE IS | |
BELOW 45.0° F. | ||
|