Parameter Description and Options
| FORM |
TABLE |
|
|
|
MENU ITEM | DEFINITION |
SUPPLY AIR TEMP LIMIT FOR COOLING | THIS PARAMETER MUST BE TURNED ON TO ENABLE SUPPLY |
ENABLE | AIR TEMP LIMIT OPERATION IN THE COOLING MODE ON A |
| CONSTANT VOLUME UNIT |
SUPPLY AIR TEMP LIMIT FOR HEATING | THIS PARAMETER MUST BE TURNED ON TO ENABLE SUPPLY |
ENABLED | AIR TEMP LIMIT OPERATION IN THE HEATING MODE ON A |
| CONSTANT VOLUME UNIT |
SUPPLY AIR TEMP LIMIT HEATING SETPOINT | THIS PARAMETER IS USED BY THE UNIT CONTROLLER DURING |
| SUPPLY AIR TEMP LIMIT FOR HEATING OPERATION ON A |
| CONSTANT VOLUME UNIT. |
TEMPERATURE/HUMIDITY (RETURN) CONTROL | THIS PARAMETER WOULD BE USED IF HOT GAS REHEAT WAS |
ENABLED | BEING USED. THIS FEATURE IS NOT AVAILABLE ON THESE |
| UNITS. THIS SHOULD ALWAYS BE SET TO OFF |
THIRD PARTY BAS ECONOMIZER ENABLED | WHEN THIS PARAMETER IS TURNED ON THE POSITION OF THE |
| ECONOMIZER DAMPER IS CONTROLLED BY AN EXTERNAL |
| VDC INPUT |
TURN OFF CONTINUOUS FAN WHEN STARTING | IF THIS PARAMETER IS TURNED ON AND THE UNIT IS RUNNING |
HEAT | CONTINUOUS FAN, THE CONTROL WILL STOP THE SUPPLY FAN |
| AT THE START OF A HEATING CYCLE AND TURN IT BACK ON |
| BASED ON THE FAN ON FOR HEAT SETTING |
UNIT MODEL NUMBER | THIS ALLOWS THE UNIT MODEL NUMBER TO BE ENTERED FOR |
| THE UNIT THROUGH THE SIMPLICITY PC SOFTWARE |
UNIT NAME | THIS ALLOWS A NAME TO BE ASSIGNED TO THE UNIT TO |
| IDENTIFY IT ON THE NETWORK THROUGH THE SIMPLICITY PC |
| SOFTWARE |
UNIT SERIAL NUMBER | THIS ALLOWS THE UNIT SERIAL NUMBER TO BE ENTERED FOR |
| THE UNIT THROUGH THE SIMPLICITY PC SOFTWARE |
UNOCCUPIED OVERRIDE TIME PERIOD | THIS PARAMETER ESTABLISHES THE MAXIMUM TIME THE UNIT |
| WILL REMAIN IN THE UNOCCUPIED OVERRIDE MODE WHEN |
| THE OVERRIDE BUTTON IS PUSHED ON THE SPACE SENSOR. |
VAV / CV SELECTION | THIS PARAMETER GIVES THE STATUS OF THE SET UP OF THE |
| UNIT , VAV OR CV |
VAV COOLING SUPPLY AIR TEMP LOWER | THIS PARAMETER ESTABLISHES THE LOWER COOLING |
SETPOINT | SETPOINT FOR VAV COOLING OPERATION |
VAV COOLING SUPPLY AIR TEMP UPPER | THIS PARAMETER ESTABLISHES THE UPPER COOLING |
SETPOINT | SETPOINT FOR VAV COOLING OPERATION |
VAV OCCUPIED HEATING ENABLED | THIS PARAMETER MUST BE TURNED ON TO ALLOW OCCUPIED |
| HEATING OPERATION. |
VAV OCCUPIED HEATING SETPOINT | THE UNIT CONTROLLER COMPARES THE SPACE TEMPERATURE |
| TO THIS VALUE AS ONE OF THE CRITERIA TO USE TO |
| DETERMINE WHEN TO INITIATE VAV OCCUPIED HEATING |
| OPERATION |
VAV SUPPLY AIR TEMP RESET SETPOINT | THE UNIT CONTROLLER COMPARES THE SPACE OR RETURN |
| AIR TEMPERATURE TO THIS VALVE TO DETERMINE IF IT |
| SHOULD CONTROL TO THE VAV COOLING SUPPLY AIR UPPER |
| OR LOWER SETPOINT |
YEAR | THIS PARAMETER IS USED TO ENTER THE CURRENT YEAR 0 TO |
| 99. FOR EXAMPLE 7 WOULD BE 2007 |
152 | JOHNSON CONTROLS |