FORM 100.50-NOM6 (1207)

SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS

TABLE 7-1 – DEFINITIONS

MENU ITEM

DEFINITION

 

 

ACCUMULATED UNOCCUPIED OVERRIDE TIME

THIS PARAMETER GIVES THE ACCUMULATED TIME THE UNIT

 

 

HAS PLACED IN UNOCCUPIED OVERRIDE MODE.

 

 

 

 

 

ACTIVE ALARM

THIS IDENTIFIES THE NUMBER OF ACTIVE ALARMS PRESENT

 

 

ADDRESS

THIS PARAMETER IS USED TO SET THE COMMUNICATION

 

 

ADDRESS FOR THE UNIT WHEN CONNECTED TO A NETWORK

 

 

 

 

 

APS DATA

THIS PARAMETER GIVES THE STATUS OF THE SUPPLY FAN AIR

 

 

PROVING SWITCH. 0 = SWITCH OPEN, 1 = SWITCH CLOSED

 

 

 

 

 

 

THIS PARAMETER ESTABLISHES THE BUILDING PRESSURE

 

 

BUILDING PRESSURE SETPOINT

SETPOINT FOR THE CONTROL OF BUILDING EXHAUST

 

 

 

OPERATION

 

 

BUILDING STATIC PRESSURE

THIS PARAMETER GIVES THE CURRENT VALUE OF THE

 

 

BUILDING STATIC PRESSURE INPUT

 

 

 

 

 

BUILDING STATIC PRESSURE SENSOR

THIS PARAMETER MUST BE TURNED ON TO ENABLE THE USE

 

 

OF BUILDING PRESSURE IN THE OPERATION OF THE EXHAUST

 

 

INSTALLED

 

 

FUNCTION

 

 

 

 

 

COMFORT VENTILATION FOR COOLING

THIS PARAMETER MUST BE TURNED ON TO ENABLED

 

 

COMFORT VENTILATION DURING COOLING MODE OPERATION

 

 

ENABLED

 

 

ON A CONSTANT VOLUME UNIT

 

 

 

 

 

COMFORT VENTILATION FOR HEATING

THIS PARAMETER MUST BE TURNED ON TO ENABLE COMFORT

 

 

VENTILATION DURING HEATING MODE OPERATION ON A

 

 

ENABLED

 

 

CONSTANT VOLUME UNIT

 

 

 

 

 

 

THIS PARAMETER IS THE LOWER SETPOINT USED BY THE UNIT

 

 

COMFORT VENTILATION LOWER SETPOINT

CONTROLLER TO DETERMINE WHEN TO SWITCH THE UNIT IN

 

 

 

COMFORT VENTILATION MODE

 

 

 

THIS PARAMETER IS THE UPPER SETPOINT USED BY THE UNIT

 

 

COMFORT VENTILATION UPPER SETPOINT

CONTROLLER TO DETERMINE WHEN TO SWITCH THE UNIT IN

 

 

 

COMFORT VENTILATION MODE

 

 

COMP 1 ASCD ACTIVE

THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE

 

 

TIMER. ON MEANS THE COMPRESSOR 1 IS IN THIS MODE

 

 

 

 

 

COMP 1 ASCD TIMER

THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR

 

 

COMPRESSOR 1 IN SECONDS.

 

 

 

 

 

COMP 1 MIN RUN TIME

THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR

 

 

COMPRESSOR 1 IN SECONDS.

 

 

 

 

 

COMP 1 OUTPUT

THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE

 

 

UNIT CONTROLLER TO COMPRESSOR CIRCUIT 1

 

 

 

 

 

 

 

 

7

 

THIS IS THE STATUS OF THE BINARY INPUT FROM THE

 

 

 

 

COMP 1 OVERLOAD SWITCH

COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 1 TO

 

 

 

 

THE UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

 

 

COMP 2 ASCD ACTIVE

THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE

 

 

TIMER. ON MEANS THE COMPRESSOR 2 IS IN THIS MODE

 

 

 

 

 

COMP 2 ASCD TIMER

THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR

 

 

COMPRESSOR 2 IN SECONDS.

 

 

 

 

 

COMP 2 MIN RUN TIME

THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR

 

 

COMPRESSOR 2 IN SECONDS.

 

 

 

 

 

 