York YPAL 050 manual The unit can not be in an active heating or cooling mode, Comfort Ventilation

Models: YPAL 060 YPAL 051 YPAL 050 YPAL 061

1 168
Download 168 pages 27.04 Kb
Page 81
Image 81

FORM 100.50-NOM6 (1207)

COMFORT VENTILATION

Comfort Ventilation is a Constant Volume control mode that uses the economizer to control the supply air temperature. When outdoor air conditions allow, the economizer will modulate the outside / return air mix to keep supply air temperatures within the upper and lower Comfort Ventilation set points. The control will modulate the economizer, and energize cooling or heating if necessary, to keep the supply air temperature within the Comfort Ventilation set points, even though the space temperature requirements are satisfied.

The following criteria must be present in order for Comfort Ventilation to function”:

The unit can not be in an active heating or cooling mode.

The unit must have an economizer installed.

The unit must be in the occupied mode.

The unit should be placed in the continuous in- door fan operation mode.

The unit type must be Constant Volume.

The following parameters must be programmed:

“COMFORT VENTILATION FOR COOLING ENABLED” - must be enabled under the COOLING SETUP tab in the Simplicity PC software package.

“COMFORT VENTILATION FOR HEATING ENABLED” - must be enabled under the HEATING SETUP tab in the Simplicity PC software package.

“COMFORT VENTILATION UPPER SETPOINT” - must be programmed under the COOLING SETUP or HEATING SETUP tab in the Simplicity PC software package.

“COMFORT VENTILATION LOWER SETPOINT” - must be programmed under the COOLING SETUP or HEATING SETUP tab in the Simplicity PC software package.

 

TABLE 5-4 OPERATION DURING OFF CYCLE

 

 

 

 

 

 

 

 

OAT VS OAT COMFORT ZONE

SAT VS SAT COMFORT ZONE

ECON OPERATION

 

HEAT STAGE

 

COMP STAGE

 

 

 

BELOW

ABOVE

OPEN

-

-

 

 

 

BELOW

BELOW

-

 

TURN ON

 

 

 

 

 

 

 

 

5

 

BELOW

WITHIN

-

-

-

 

 

ABOVE

ABOVE

-

-

 

TURN ON

 

 

 

 

 

 

 

 

 

 

 

 

 

ABOVE

BELOW

OPEN

-

-

 

 

 

ABOVE

WITHIN

-

-

-

 

 

 

WITHIN

ABOVE

OPEN

-

-

 

 

 

WITHIN

BELOW

OPEN

-

-

 

 

 

WITHIN

WITHIN

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 5-5 COMPRESSOR ON WHEN SPACE INPUT SATISFIED

 

 

 

 

 

 

 

OAT VS OAT COMFORT ZONE

SAT VS SAT COMFORT ZONE

ECON OPERATION

 

HEAT STAGE

 

COMP STAGE

 

 

 

BELOW

ABOVE

OPEN

 

-

 

TURN OFF

 

 

 

BELOW

BELOW

-

 

TURN ON

 

TURN OFF

 

 

 

BELOW

WITHIN

-

 

-

 

TURN OFF

 

 

 

ABOVE

ABOVE

-

 

-

 

LEAVE ON

 

 

 

ABOVE

BELOW

OPEN

 

-

 

LEAVE ON*

 

 

 

ABOVE

WITHIN

-

 

-

 

LEAVE ON

 

 

 

WITHIN

ABOVE

OPEN

 

-

 

TURN OFF

 

 

 

WITHIN

BELOW

OPEN

 

-

 

TURN OFF

 

 

 

WITHIN

WITHIN

-

 

-

 

TURN OFF

 

 

 

 

 

 

 

 

 

 

 

 

*If the economizer damper opens to 100%, the compressor will turn off and the economizer damper will remain at 100%.

JOHNSON CONTROLS

81

Page 81
Image 81
York YPAL 050 manual The unit can not be in an active heating or cooling mode, The unit must have an economizer installed