User Interface Control Center

FORM 100.50-NOM6 (1207)

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

 

 

 

INITIAL/

 

 

 

ADDRESS

ADDRESS

BIT

DEFAULT

MIN

MAX

DESCRIPTION

(HEX)

(DEC)

VALUE

VALUE

VALUE

 

 

 

 

 

(HEX)

 

 

 

D7L

215 L

NA

0

-

-

OPTION BYTE #7

 

 

0

 

 

 

1 = ERV ENABLED

 

 

1

 

 

 

1 = ERV UNOCCUPIED FAN ENABLED

 

 

 

 

 

 

 

 

 

2-7

 

 

 

NA

D8 H

216 H

 

S

0

100

HOT GAS REHEAT HUMIDITY SETPOINT (PERCENT HUMIDITY)

 

 

 

 

 

 

 

D8 L

216 L

 

50

20

80

TEMPERATURE / HUMIDITY SETPOINT (PERCENT HUMIDITY)

D9 H

217 H

 

3

0

5

MAXIMUM TEMPERATURE / HUMIDITY OFFSET (DEGREES F)

D9 L

217 L

 

5

1

10

TEMPERATURE / HUMIDITY VALUE THAT = 1° F OF OFFSET

 

(PERCENT HUMIDITY)

 

 

 

 

 

 

DB H

219 H

 

72

45

99

OPERATING COOLING SETPOINT (DEGREES F) [CV]

DB L

219 L

 

68

45

99

OPERATING HEATING SETPOINT (DEGREES F) [CV]

DC H

220 H

 

-

10

50

OUTSIDE AIR ENTHALPY (BTUS PER POUND)

 

 

 

 

 

 

 

DC L

220 L

 

-

10

50

RETURN AIR ENTHALPY (BTUS PER POUND)

DE L

222 L

 

50

0

100

MAXIMUM DEMAND VENTILATION ECONOMIZER POSITION

 

(PERCENT OPEN)

 

 

 

 

 

 

DF H

223 H

 

-

0

10

SPACE SENSOR OFFSET (0 = -5° F, 10 = +5° F)

E0 H

224 H

 

-

-

-

ASCD TIMER FOR HEATING STAGE #1 (SECONDS, COUNTS

 

DOWN)

 

 

 

 

 

 

E0 L

224 L

 

-

-

-

HEATING STAGE #1 MINIMUM RUN TIMER (SECONDS, COUNTS

 

DOWN)

 

 

 

 

 

 

E1 H

225 H

 

-

-

-

ASCD TIMER FOR HEATING STAGE #2 (SECONDS, COUNTS

 

DOWN)

 

 

 

 

 

 

E1 L

225 L

 

-

-

-

HEATING STAGE #2 MINIMUM RUN TIMER (SECONDS, COUNTS

 

DOWN)

 

 

 

 

 

 

E2 H

226 H

 

-

-

-

ASCD TIMER FOR HEATING STAGE #3 (SECONDS, COUNTS

 

DOWN)

 

 

 

 

 

 

E2 L

226 L

 

-

-

-

HEATING STAGE #3 MINIMUM RUN TIMER (SECONDS, COUNTS

 

DOWN)

 

 

 

 

 

 

 

 

 

 

 

 

 

E3 H

227 H

 

0

0

99

LOW AMBIENT ECONOMIZER MINIMUM POSITION (PERCENT)

E3 L

227 L

 

0

0

60

LOW AMBIENT ECONOMIZER SETPOINT (DEGREES F)

140