User Interface Control Center
FORM
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
|
|
| INITIAL/ |
|
|
| |
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX | DESCRIPTION | |
(HEX) | (DEC) | VALUE | VALUE | VALUE | |||
|
| ||||||
|
|
| (HEX) |
|
|
| |
D7L | 215 L | NA | 0 | - | - | OPTION BYTE #7 | |
|
| 0 |
|
|
| 1 = ERV ENABLED | |
|
| 1 |
|
|
| 1 = ERV UNOCCUPIED FAN ENABLED | |
|
|
|
|
|
|
| |
|
|
|
|
| NA | ||
D8 H | 216 H |
| S | 0 | 100 | HOT GAS REHEAT HUMIDITY SETPOINT (PERCENT HUMIDITY) | |
|
|
|
|
|
|
| |
D8 L | 216 L |
| 50 | 20 | 80 | TEMPERATURE / HUMIDITY SETPOINT (PERCENT HUMIDITY) | |
D9 H | 217 H |
| 3 | 0 | 5 | MAXIMUM TEMPERATURE / HUMIDITY OFFSET (DEGREES F) | |
D9 L | 217 L |
| 5 | 1 | 10 | TEMPERATURE / HUMIDITY VALUE THAT = 1° F OF OFFSET | |
| (PERCENT HUMIDITY) | ||||||
|
|
|
|
|
| ||
DB H | 219 H |
| 72 | 45 | 99 | OPERATING COOLING SETPOINT (DEGREES F) [CV] | |
DB L | 219 L |
| 68 | 45 | 99 | OPERATING HEATING SETPOINT (DEGREES F) [CV] | |
DC H | 220 H |
| - | 10 | 50 | OUTSIDE AIR ENTHALPY (BTUS PER POUND) | |
|
|
|
|
|
|
| |
DC L | 220 L |
| - | 10 | 50 | RETURN AIR ENTHALPY (BTUS PER POUND) | |
DE L | 222 L |
| 50 | 0 | 100 | MAXIMUM DEMAND VENTILATION ECONOMIZER POSITION | |
| (PERCENT OPEN) | ||||||
|
|
|
|
|
| ||
DF H | 223 H |
| - | 0 | 10 | SPACE SENSOR OFFSET (0 = | |
E0 H | 224 H |
| - | - | - | ASCD TIMER FOR HEATING STAGE #1 (SECONDS, COUNTS | |
| DOWN) | ||||||
|
|
|
|
|
| ||
E0 L | 224 L |
| - | - | - | HEATING STAGE #1 MINIMUM RUN TIMER (SECONDS, COUNTS | |
| DOWN) | ||||||
|
|
|
|
|
| ||
E1 H | 225 H |
| - | - | - | ASCD TIMER FOR HEATING STAGE #2 (SECONDS, COUNTS | |
| DOWN) | ||||||
|
|
|
|
|
| ||
E1 L | 225 L |
| - | - | - | HEATING STAGE #2 MINIMUM RUN TIMER (SECONDS, COUNTS | |
| DOWN) | ||||||
|
|
|
|
|
| ||
E2 H | 226 H |
| - | - | - | ASCD TIMER FOR HEATING STAGE #3 (SECONDS, COUNTS | |
| DOWN) | ||||||
|
|
|
|
|
| ||
E2 L | 226 L |
| - | - | - | HEATING STAGE #3 MINIMUM RUN TIMER (SECONDS, COUNTS | |
| DOWN) | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
E3 H | 227 H |
| 0 | 0 | 99 | LOW AMBIENT ECONOMIZER MINIMUM POSITION (PERCENT) | |
E3 L | 227 L |
| 0 | 0 | 60 | LOW AMBIENT ECONOMIZER SETPOINT (DEGREES F) |
140 | JOHNSON CONTROLS |