Sequence of Operation

FORM 100.50-NOM6 (1207)

TABLE 5-6 HEAT STAGE ON WHEN SPACE INPUT SATISFIED

OAT VS OAT COMFORT ZONE

SAT VS SAT COMFORT ZONE

ECON OPERATION

HEAT STAGE

COMP STAGE

BELOW

ABOVE

OPEN

LEAVE ON*

-

BELOW

BELOW

-

LEAVE ON

-

BELOW

WITHIN

-

LEAVE ON

-

ABOVE

ABOVE

-

TURN OFF

TURN ON

ABOVE

BELOW

OPEN

TURN OFF

-

ABOVE

WITHIN

-

TURN OFF

-

WITHIN

ABOVE

OPEN

TURN OFF

-

 

 

 

 

 

WITHIN

BELOW

OPEN

TURN OFF

-

WITHIN

WITHIN

-

TURN OFF

-

 

 

 

 

 

Sequence of Operation

Tables 5-4 thru 5-6 use the following definitions:

SAT COMFORT ZONE – the temperature be- tween the “COMFORT VENTILATION LOWER SETPOINT” minus 1.0° F and the “COMFORT VENTILATION UPPER SETPOINT” plus 1.0° F.

OAT COMFORT ZONE - the temperature be- tween the “COMFORT VENTILATION LOWER SETPOINT” and the “COMFORT VENTILA-

TION UPPER SETPOINT”.

OAT – Outdoor Air Temperature.

SAT – Supply Air Temperature.

ECON OPERATION – Economizer damper will open to BRING SAT into the SAT COMFORT ZONE.

Conditions of Operation

In order for compressor operation “COMFORT VENTILATION FOR COOLING ENABLED” must be enabled.

In order for heat stages to operate “COMFORT VENTILATION FOR HEATING ENABLED” must be enabled.

Economizer operation will occur with either, or both, “COMFORT VENTILATION FOR COOL- ING ENABLED” or “COMFORT VENTILA- TION FOR HEATING ENABLED” enabled.

EXCESSIVE SAT (SUPPLY AIR TEMPERATURE) CONTROL

This feature is only available on Constant Volume units. On a Constant Volume unit, the compressors and heat stages are control by the space temperature only, either by thermostat or zone sensor. As long as the room device is calling for cooling or heating the compressors or heating section does not control the actual temperature of the supply air leaving the unit. The enabling of this feature adds a means to prevent low or high supply air temperatures from being delivered to the conditioned space.

Cooling

The following System Parameters must be programmed:

“SUPPLY AIR TEMP LIMIT FOR COOLING ENABLED”- must be enabled using Parameter 14 under the PROGRAM key on the Simplicity control board or under the COOLING SETUP tab in the Simplicity PC software package.

“SUPPLY AIR TEMP LIMIT COOLING SETPOINT”

Using Parameter 15 under the PROGRAM key on the Simplicity control board or under the COOLING SETUP tab in the Simplicity PC software package.

If a single compressor is energized the control will monitor the supply air temperature and respond as follows:

82

JOHNSON CONTROLS

Page 82
Image 82
York YPAL 051, YPAL 061, YPAL 050 Tion Upper Setpoint, Conditions of Operation, Supply AIR Temp Limit Cooling Setpoint