CONNECTOR # | TYPE | IDENTIFICATION | WIRE # | DESCRIPTION | |
|
|
|
|
| |
P14 | AO | EXD+ | 407 | EXHAUST FAN VFD / DAMPER OUTPUT+ | |
P14 | AO | HGR- | - | NOT USED | |
|
|
|
|
| |
P14 | AO | HGR+ | - | NOT USED | |
P14 | AO | HWV- | 410 | HOT WATER VALVE OUTPUT - | |
P14 | AO | HWV+ | 409 | HOT WATER VALVE OUTPUT + | |
P14 | AO | VFD- | 402 | SUPPLY FAN VFD OUTPUT - | |
P14 | AO | VFD+ | 401 | SUPPLY FAN VFD OUTPUT + | |
P4 | COMM | - | (+) COMMUNICATION CONNECTION | ||
P4 | COMM | - | |||
P5 | COMM | - | CONNECTION FOR SIMPLICITY PC SOFTWARE | ||
P12 | DI | C10 | JUMPER | COMPRESSOR 1A MOTOR PROTECTION CIRCUIT | |
|
|
|
|
| |
P12 | DI | C20 | JUMP / 440 | COMPRESSOR 1B MOTOR PROTECTION CIRCUIT | |
P12 | DI | C20 | JUMP / 441 | 24 VAC TO COMMON | |
P12 | DI | C30 | JUMP / 442 | COMPRESSOR 2A MOTOR PROTECTION CIRCUIT | |
P12 | DI | C30 | JUMP / 443 | 24 VAC TO COMMON | |
P12 | DI | C40 | JUMP / 444 | COMPRESSOR 2B MOTOR PROTECTION CIRCUIT | |
P12 | DI | C40 | JUMP / 445 | 24 VAC TO COMMON | |
P10 | DI | GV1 | 510 | HEAT SECTION 1 GAS VALVE INPUT | |
P10 | DI | GV2 | 525 | HEAT SECTION 2 GAS VALVE INPUT | |
P10 | DI | GV3 | 536 | HEAT SECTION 3 GAS VALVE INPUT | |
TERMINAL | DI | 24 VAC | 301 | 24 VAC INPUT TO UNIT CONTROLLER FOR BINARY | |
OUTPUTS | |||||
|
|
|
| ||
P11 | DI | APS | 411 | AIR PROVING SIWTCH INPUT | |
|
|
|
|
| |
P11 | DI | APS | 412 | 24 VAC TO COMMON | |
P12 | DI | C10 | JUMPER | COMPRESSOR 1A MOTOR PROTECTION CIRCUIT | |
TERMINAL | DI | COM | 304 | 24 VAC COMMON | |
P22 | DI | FILT | 390 | DIRTY FILTER SWITCH INPUT | |
P22 | DI | FILT | 391 | 24 VAC TO COMMON | |
P16 | DI | FOVR | JUMP / 404 | 24 VAC TO COMMON | |
P16 | DI | FOVR | JUMP / 403 | SUPPLY FAN OVERLOAD INPUT CV UNITS ONLY | |
TERMINAL | DI | FSI | 388 | FREEZE STAT INPUT | |
TERMINAL | DI | FSP | 389 | 24 VAC TO COMMON | |
|
|
|
|
| |
P15 | DI | HSP1 | 399 | 24 VAC TO COMMON | |
P15 | DI | HSP1 | 400 | COMPRESSOR SYSTEM 1 HIGH PRESSURE INPUT | |
|
|
|
|
| |
P15 | DI | HSP2 | - | NOT USED | |
P15 | DI | HSP2 | 400 | JUMPERED TO HSP1 | |
P16 | DI | HSP3 | 431 | 24 VAC TO COMMON | |
P16 | DI | HSP3 | 432 | COMPRESSOR SYSTEM 2 1 HIGH PRESSURE INPUT | |
P16 | DI | HSP4 | - | NOT USED | |
|
|
|
|
| |
P16 | DI | HSP4 | 432 | JUMPERED TO HSP3 | |
P10 | DI | LIM1 | 507 | HEAT SECTION 1 LIMIT INPUT | |
P10 | DI | LIM2 | 522 | HEAT SECTION 2 LIMIT INPUT | |
P10 | DI | LIM3 | 533 | HEAT SECTION 3 LIMIT INPUT | |
P15 | DI | LPS1 | 395 | 24 VAC TO COMMON | |
P15 | DI | LPS1 | 396 | COMPRESSOR SYSTEM 1 LOW PRESSURE INPUT | |
P15 | DI | LPS2 | - | NOT USED | |
|
|
|
|
|