FORM 100.50-NOM6 (1207)

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

 

 

 

INITIAL/

 

 

 

 

 

 

ADDRESS

ADDRESS

BIT

DEFAULT

MIN

MAX

 

DESCRIPTION

 

 

(HEX)

(DEC)

VALUE

VALUE

VALUE

 

 

 

 

 

 

 

 

 

 

 

(HEX)

 

 

 

 

 

 

 

 

5

 

 

 

1

= W2 ON (HEATING 2ND STAGE)

 

 

 

 

6

 

 

 

1

= W3 ON (HEATING 3RD STAGE)

 

 

 

 

7

 

 

 

1

= G ON (INDOOR FAN)

 

 

 

 

 

 

 

 

 

 

 

15 L

21 L

NA

-

-

-

INPUT STATUS BYTE #2

 

 

 

 

0

 

 

 

1

= HPS1 CLOSED (NOT TRIPPED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

1

= HPS2 CLOSED

 

 

 

 

2

 

 

 

1

= HPS3 CLOSED

 

 

 

 

3

 

 

 

1

= HPS4 CLOSED

 

 

 

 

4

 

 

 

1

= LPS1 CLOSED (NOT TRIPPED)

 

 

 

 

5

 

 

 

1

= LPS2 CLOSED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

1

= LPS3 CLOSED

 

 

 

 

7

 

 

 

1

= LPS4 CLOSED

 

 

16 H

22 H

NA

-

-

-

INPUT STATUS BYTE #3

 

 

 

 

0

 

 

 

1

= C1 OVERLOAD CLOSED (NOT TRIPPED)

 

 

 

 

1

 

 

 

1

= C2 OVERLOAD CLOSED

 

 

 

 

2

 

 

 

1

= C3 OVERLOAD CLOSED

 

 

 

 

3

 

 

 

1

= C4 OVERLOAD CLOSED

 

 

 

 

4

 

 

 

1

= PURGE SWITCH CLOSED (ACTIVE)

 

 

 

 

5

 

 

 

1

= OCC INPUT ON

 

 

 

 

6

 

 

 

NA

 

 

 

 

7

 

 

 

1

= DIRTY FILTER CLOSED (DIRTY CONDITION)

 

 

16 L

22 L

NA

-

-

-

INPUT STATUS BYTE #4

 

 

 

 

0

 

 

 

1

= GAS VALVE #1 ON

 

 

 

 

1

 

 

 

1

= GAS VALVE #2 ON

 

 

 

 

2

 

 

 

1

= GAS VALVE #3 ON

 

 

 

 

3

 

 

 

1

= LIMIT #1 CLOSED (NOT TRIPPED)

 

 

 

 

4

 

 

 

1

= LIMIT #2 CLOSED

 

 

 

 

5

 

 

 

1

= LIMIT #3 CLOSED

 

 

 

 

6

 

 

 

NA

 

 

 

 

 

 

 

6

 

 

7

 

 

 

NA

 

17 L

23 H

NA

-

-

-

INPUT STATUS BYTE #5

 

 

 

 

0

 

 

 

1

= FAN OVERLOAD CLOSED (NOT TRIPPED)

 

 

 

 

1

 

 

 

1

= FREEZE STAT CLOSED (NOT LOW TEMPERATURE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

1

= AIR PROVING CLOSED (AIR FLOW IS SENSED)

 

 

 

 

3

 

 

 

NA

 

 

 

 

4

 

 

 

NA

 

 

 

 

5

 

 

 

1

= VAV; 0 = CV

 

 

 

 

6

 

 

 

1

= CV / VAV OUT OF RANGE (FAULT CONDITION)

 

 

 

 

7

 

 

 

1

= LOW 24 VAC SUPPLY VOLTAGE

 

 

17 H

23 L

NA

-

-

-

INPUT STATUS BYTE #6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

1

= PROGRAM BUTTON PRESSED

 

 

 

 

1

 

 

 

1

= TEST / UP BUTTON PRESSED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

1

= ALARMS / CHANGE BUTTON PRESSED

 

 

Continued on next page

JOHNSON CONTROLS

131

Page 131
Image 131
York YPAL 060, YPAL 061, YPAL 050, YPAL 051 manual Description HEX DEC Value