Installation
FORM
UNIT WEIGHTS
TABLE 2-2 – UNIT WEIGHTS - 050-061 MODELS
MODEL SIZE | 050 | 051 | 060 | 061 |
BASIC UNIT* | 7433 | 7433 | 7800 | 7819 |
ECONOMIZERS |
|
|
|
|
NO OUTSIDE AIR | 240 | 240 | 240 | 240 |
25% OUTSIDE AIR FIXED POSITION MAUAL | 446 | 446 | 446 | 446 |
DAMPER |
|
|
|
|
25% OUTSIDE AIR 2 POSITION ACTUATED | 476 | 476 | 476 | 476 |
DAMPER |
|
|
|
|
|
|
|
|
|
FULL MODULATION WITH MINIMUM POSITION | 476 | 476 | 476 | 476 |
POWER EXHAUSTS |
|
|
|
|
FAN, MOTOR, MODULATING DAMPER AND HOOD | 501 | 501 | 501 | 501 |
FAN, MOTOR, VFD, BAROMETRIC DAMPER AND | 506 | 506 | 506 | 506 |
HOOD |
|
|
|
|
GAS HEAT |
|
|
|
|
375 MBH | 162 | 162 | 162 | 162 |
|
|
|
|
|
750 MBH | 324 | 324 | 324 | 324 |
1125 MBH | 486 | 486 | 486 | 486 |
OPTIONS |
|
|
|
|
OPEN PERIMETER CURB | 544 | 544 | 544 | 544 |
|
|
|
|
|
CONDENSER COIL WIRE GUARD | 64 | 64 | 64 | 64 |
COPPER CONDENSER COILS (ADDITIONAL) | 516 | 516 | 773 | 773 |
12” RIGID FILTERS (ADDITIONAL) | 319 | 319 | 319 | 319 |
*UNIT INCLUDES FC FAN W/ 20 HP MOTOR, VFD AND 2” THROWAWAY FILTERS
Center of Gravity
92
Y
BC
AD
X 339
Condenser Coil End
LD08298
TABLE 2-3 – UNIT CENTER OF GRAVITY
MODEL |
| 050 |
| 051 | ||
X |
| Y | X |
| Y | |
|
|
| ||||
BASIC UNIT | 184.1 |
| 50.2 | 184.1 |
| 50.2 |
|
|
|
|
|
|
|
BASIC UNIT W/ ECON. | 191.0 |
| 49.9 | 191.0 |
| 49.9 |
BASIC UNIT W/ ECON. & HEATING | 187.4 |
| 50.0 | 187.4 |
| 50.0 |
|
|
|
|
|
|
|
BASIC UNIT W/ ECON. & HEATING & POWER | 194.9 |
| 49.5 | 194.9 |
| 49.5 |
EXHAUST |
|
| ||||
|
|
|
|
|
| |
|
|
|
|
|
|
|
MODEL |
| 060 |
| 061 | ||
X |
| Y | X |
| Y | |
|
|
| ||||
BASIC UNIT | 179.8 |
| 49.9 | 179.6 |
| 50.0 |
|
|
|
|
|
|
|
BASIC UNIT W/ ECON. | 186.7 |
| 49.7 | 186.5 |
| 49.7 |
BASIC UNIT W/ ECON. & HEATING | 183.5 |
| 49.8 | 183.2 |
| 49.8 |
|
|
|
|
|
|
|
BASIC UNIT W/ ECON. & HEATING & POWER | 190.9 |
| 49.3 | 190.7 |
| 49.3 |
EXHAUST |
|
| ||||
|
|
|
|
|
| |
|
|
|
|
|
|
|
20 | JOHNSON CONTROLS |