| FORM | |
TABLE |
|
| |||
|
|
|
|
| |
CONNECTOR # | TYPE | IDENTIFICATION | WIRE # | DESCRIPTION | |
|
|
|
|
| |
P15 | DI | LPS2 | 396 | JUMPERED TO LSP1 | |
P16 | DI | LPS3 | 433 | 24 VAC TO COMMON | |
P16 | DI | LSP3 | 434 | COMPRESSOR SYSTEM 2 LOW PRESSURE INPUT | |
P16 | DI | LPS4 | - | NOT USED | |
P16 | DI | LPS4 | 434 | JUMPERED TO LSP3 | |
TERMINAL | DI | R | SD | 24 VAC INPUT TO UNIT CONTROLLER | |
JUMPER | |||||
|
|
|
| ||
TERMINAL | DI | SDI | SD | INPUT FOR SMOKE SHUTDOWN | |
JUMPER | |||||
|
|
|
| ||
TERMINAL | DI | SD2 | 303 | 24 VAC TO COMMON | |
P12 | DO | C1 | 427 | COMPRESSOR 1A OUTPUT | |
P12 | DO | C2 | 428 | COMPRESSOR 1BOUTPUT | |
P12 | DO | C3 | 429 | COMPRESSOR 2A OUTPUT | |
P12 | DO | C4 | 430 | COMPRESSOR 2B OUTPUT | |
P13 | DO | CF1 | 423 | CONDENSER FAN BANK 1 OUTPUT | |
P13 | DO | CF2 | 425 | CONDENSER FAN BANK 2 OUTPUT | |
P13 | DO | EXH | 422 | EXHAUST FAN OUTPUT | |
P13 | DO | FAN | 421 | SUPPLY FAN OUTPUT | |
|
|
|
|
| |
P10 | DO | H1 | 570 | HEAT SECTION ONE OUTPUT | |
P10 | DO | H2 | 572 | HEAT SECTION TWO OUTPUT | |
P10 | DO | H3 | 574 | HEAT SECTION 3 OUTPUT | |
P3 | FIELD INPUT | BAS ECON - | - | ECONOMIZER DAMPER INPUT - VDC | |
P3 | FIELD INPUT | BAS ECON + | - | ECONOMIZER DAMPER INPUT + VDC | |
P1 | FIELD INPUT | C | - | COMMON SIDE OF 24 VAC SUPPLY | |
P1 | FIELD INPUT | G | - | SUPPLY FAN INPUT | |
P1 | FIELD INPUT | OCC | - | OCCUPIED INPUT | |
P3 | FIELD INPUT | PURGE | - | SMOKE PURGE INPUT | |
|
|
|
|
| |
P1 | FIELD INPUT | R | - | HOT SIDE OF 24 VAC SUPPLY | |
P19 | FIELD INPUT | REM- | - | REMOTE RESET - | |
P19 | FIELD INPUT | REM+ | - | REMOTE RESET + | |
P1 | FIELD INPUT | SD | - | NOT USED | |
P8 | FIELD INPUT | GND | - | SPACE TEMPERATURE INPUT COMMON | |
P8 | FIELD INPUT | SSO | - | SPACE TEMP SENSOR OFFSET + | |
P8 | FIELD INPUT | ST | - | SPACE TEMPERATURE INPUT + | |
P2 | FIELD INPUT | W1 | - | IST STAGE HEAT INPUT | |
P2 | FIELD INPUT | W2 | - | 2ND STAGE HEAT INPUT | |
P2 | FIELD INPUT | W3 | - | 3RD STAGE HEAT INPUT | |
P1 | FIELD INPUT | X | - | FAULT OUTPUT | |
P2 | FIELD INPUT | Y1 | - | 1ST STAGECOOLING INPUT | |
P2 | FIELD INPUT | Y2 | - | 2ND STATE COOLING INPUT | |
P2 | FIELD INPUT | Y3 | - | 3RD STAGE COOLING INPUT | |
|
|
|
|
| |
P3 | FIELD INPUT | Y4 | - | 4TH STAGE COOLING INPUT | |
TERMINAL | FIELD OUTPUT / AO | VAV OPEN - | - | IDENTIFIES UNIT IS IN THE HEATING MODE (24 VDC | |
|
|
|
|
| |
TERMINAL | FIELD OUTPUT / AO | VAV OPEN + | - | IDENTIFIES UNIT IS IN THE HEATING MODE (24VDC +) |
8