FORM 100.50-NOM6 (1207)

TABLE 8-8 – WIRING DATA (CONTINUED)

 

 

 

 

 

 

 

CONNECTOR #

TYPE

IDENTIFICATION

WIRE #

DESCRIPTION

 

 

 

 

 

P15

DI

LPS2

396

JUMPERED TO LSP1

P16

DI

LPS3

433

24 VAC TO COMMON

P16

DI

LSP3

434

COMPRESSOR SYSTEM 2 LOW PRESSURE INPUT

P16

DI

LPS4

-

NOT USED

P16

DI

LPS4

434

JUMPERED TO LSP3

TERMINAL

DI

R

SD

24 VAC INPUT TO UNIT CONTROLLER

JUMPER

 

 

 

 

TERMINAL

DI

SDI

SD

INPUT FOR SMOKE SHUTDOWN

JUMPER

 

 

 

 

TERMINAL

DI

SD2

303

24 VAC TO COMMON

P12

DO

C1

427

COMPRESSOR 1A OUTPUT

P12

DO

C2

428

COMPRESSOR 1BOUTPUT

P12

DO

C3

429

COMPRESSOR 2A OUTPUT

P12

DO

C4

430

COMPRESSOR 2B OUTPUT

P13

DO

CF1

423

CONDENSER FAN BANK 1 OUTPUT

P13

DO

CF2

425

CONDENSER FAN BANK 2 OUTPUT

P13

DO

EXH

422

EXHAUST FAN OUTPUT

P13

DO

FAN

421

SUPPLY FAN OUTPUT

 

 

 

 

 

P10

DO

H1

570

HEAT SECTION ONE OUTPUT

P10

DO

H2

572

HEAT SECTION TWO OUTPUT

P10

DO

H3

574

HEAT SECTION 3 OUTPUT

P3

FIELD INPUT

BAS ECON -

-

ECONOMIZER DAMPER INPUT - VDC

P3

FIELD INPUT

BAS ECON +

-

ECONOMIZER DAMPER INPUT + VDC

P1

FIELD INPUT

C

-

COMMON SIDE OF 24 VAC SUPPLY

P1

FIELD INPUT

G

-

SUPPLY FAN INPUT

P1

FIELD INPUT

OCC

-

OCCUPIED INPUT

P3

FIELD INPUT

PURGE

-

SMOKE PURGE INPUT

 

 

 

 

 

P1

FIELD INPUT

R

-

HOT SIDE OF 24 VAC SUPPLY

P19

FIELD INPUT

REM-

-

REMOTE RESET -

P19

FIELD INPUT

REM+

-

REMOTE RESET +

P1

FIELD INPUT

SD

-

NOT USED

P8

FIELD INPUT

GND

-

SPACE TEMPERATURE INPUT COMMON

P8

FIELD INPUT

SSO

-

SPACE TEMP SENSOR OFFSET +

P8

FIELD INPUT

ST

-

SPACE TEMPERATURE INPUT +

P2

FIELD INPUT

W1

-

IST STAGE HEAT INPUT

P2

FIELD INPUT

W2

-

2ND STAGE HEAT INPUT

P2

FIELD INPUT

W3

-

3RD STAGE HEAT INPUT

P1

FIELD INPUT

X

-

FAULT OUTPUT

P2

FIELD INPUT

Y1

-

1ST STAGECOOLING INPUT

P2

FIELD INPUT

Y2

-

2ND STATE COOLING INPUT

P2

FIELD INPUT

Y3

-

3RD STAGE COOLING INPUT

 

 

 

 

 

P3

FIELD INPUT

Y4

-

4TH STAGE COOLING INPUT

TERMINAL

FIELD OUTPUT / AO

VAV OPEN -

-

IDENTIFIES UNIT IS IN THE HEATING MODE (24 VDC -)

 

 

 

 

 

TERMINAL

FIELD OUTPUT / AO

VAV OPEN +

-

IDENTIFIES UNIT IS IN THE HEATING MODE (24VDC +)

8

JOHNSON CONTROLS

159

Page 159
Image 159
York YPAL 060, YPAL 061, YPAL 050, YPAL 051 manual 159