TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
|
|
| INITIAL/ |
|
|
|
|
|
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX | DESCRIPTION |
|
|
(HEX) | (DEC) | VALUE | VALUE | VALUE |
|
| ||
|
|
|
| |||||
|
|
| (HEX) |
|
|
|
|
|
C6 H | 198 H |
| - | - | - | ASCD TIMER FOR COMPRESSOR #4 HIGH BYTE |
|
|
C6 L | 198 L |
| - | - | - | ASCD TIMER FOR COMPRESSOR #4 LOW BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
C7 H | 199 H |
| 0 | - | - | COMPRESSOR #1 MINIMUM RUN TIMER HIGH BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
C7 L | 199 L |
| 0 | - | - | COMPRESSOR #1 MINIMUM RUN TIMER LOW BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
C8 H | 200 H |
| 0 | - | - | COMPRESSOR #2 MINIMUM RUN TIMER HIGH BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
C8 L | 200 L |
| 0 | - | - | COMPRESSOR #2 MINIMUM RUN TIMER LOW BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
C9 H | 201 H |
| 0 | - | - | COMPRESSOR #3 MINIMUM RUN TIMER HIGH BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
C9 L | 201 L |
| 0 | - | - | COMPRESSOR #3 MINIMUM RUN TIMER LOW BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
CA H | 202 H |
| 0 | - | - | COMPRESSOR #4 MINIMUM RUN TIMER HIGH BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
CA L | 202 L |
| 0 | - | - | COMPRESSOR #4 MINIMUM RUN TIMER LOW BYTE (SECONDS, |
|
|
| COUNTS DOWN) |
|
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
CB H | 203 H |
| - | - | - | FAN ASCD TIMER HIGH BYTE (ALWAYS ZERO) |
|
|
CB L | 203 L |
| - | - | - | FAN ASCD TIMER LOW BYTE. (SECONDS, COUNTS DOWN) |
|
|
CC H | 204 H |
| 0 | - | - | FAN MINIMUM RUN TIMER (SECONDS, COUNTS DOWN) |
|
|
CD H | 205 H |
| 0 | - | - | FAN ON DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN) |
|
|
CD L | 205 L |
| 0 | - | - | FAN OFF DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN) |
|
|
CE H | 206 H |
| 0 | - | - | FAN ON DELAY TIMER FOR COOL (SECONDS, COUNT DOWN) |
|
|
CE L | 206 L |
| 0 | - | - | FAN OFF DELAY TIMER FOR COOL (SECONDS, COUNT DOWN) |
|
|
CF H | 207 H |
| 0 | 0 | 255 | ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, HIGH |
|
|
| BYTE) |
|
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
CF L | 207 L |
| 0 | 0 | 255 | ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, LOW |
|
|
| BYTE) |
| 6 | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
D4 H | 212 H |
| - | 0 | 100 | SUPPLY FAN VFD OUTPUT STATUS, |
|
|
|
| |||||||
D4 L | 212 L |
| - | 0 | 100 | EXHAUST DAMPER OUTPUT STATUS, |
|
|
D5 H | 213 H |
| - | 0 | 100 | HOT WATER VALVE OUTPUT STATUS, |
|
|
D5 L | 213 L |
| - | 0 | 100 | HOT GAS REHEAT VALVE OUTPUT STATUS, |
|
|
D6 H | 214 H |
| - | 0 | 100 | ECONOMIZER DAMPER OUTPUT STATUS, |
|
|
D7 H | 215 H | NA | 0 | - | - | OPTION BYTE #6 |
|
|
|
| 0 |
|
|
| 1 = COMFORT VENTILATION FOR COOLING ENABLED |
|
|
|
| 1 |
|
|
| 1 = COMFORT VENTILATION FOR HEATING ENABLED |
|
|
|
| 2 |
|
|
| 1 = TEMPERATURE / HUMIDITY CONTROL ENABLED |
|
|
|
| 3 |
|
|
| 1 = HOT GAS REHEAT ALTERNATE OPERATION ENABLED |
|
|
|
|
|
|
|
|
|
|
|
|
| 4 |
|
|
| 1 = NETWORK OCCUPIED FLAG: OCC IS ON |
|
|
|
| 5 |
|
|
| NA |
|
|
|
| 6 |
|
|
| 1 = DIFFERENTIAL ENTHALPY MODE ENABLED |
|
|
|
| 7 |
|
|
| NA |
|
|
Continued on next page