CO2 Sensor
Two CO2 sensors are used in conjunction with the “DEMAND VENTILATION” option. In “DEMAND VENTILATION” the Unit Control monitors the CO2 level of the outdoor air and the CO2 level in the conditioned space and varies the amount of ventilation air based on the relationship between these two values. Table
TABLE 8-7 – CO2 SENSOR OUTPUT
PPM CO2 | OUTPUT | PPM CO2 | OUTPUT |
| VOLTAGE |
| VOLTAGE |
| VDC |
| VDC |
|
|
|
|
80 | 0.20 | 1120 | 2.80 |
|
|
|
|
160 | 0.40 | 1200 | 3.00 |
|
|
|
|
240 | 0.60 | 1280 | 3.20 |
|
|
|
|
320 | 0.80 | 1360 | 3.40 |
|
|
|
|
400 | 1.00 | 1440 | 3.60 |
|
|
|
|
480 | 1.20 | 1520 | 3.80 |
|
|
|
|
560 | 1.40 | 1600 | 4.00 |
|
|
|
|
640 | 1.60 | 1680 | 4.20 |
|
|
|
|
720 | 1.80 | 1760 | 4.40 |
|
|
|
|
800 | 2.00 | 1840 | 4.60 |
|
|
|
|
880 | 2.20 | 1920 | 4.80 |
|
|
|
|
960 | 2.40 | 2000 | 5.00 |
|
|
|
|
1040 | 2.60 |
|
|
|
|
|
|
FORM
Furnace Status Input
The Unit Controller monitors the operation of the Staged and Modulating Gas Heat sections and displays the status through the STATUS screen of the User Interface. The operation of each of the gas heat sections is monitored by a multiplexer installed in the gas heat section. When a gas heat section is energized, it sends a