FORM 100.50-NOM6 (1207)

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

 

 

 

INITIAL/

 

 

 

 

 

ADDRESS

ADDRESS

BIT

DEFAULT

MIN

MAX

DESCRIPTION

 

 

(HEX)

(DEC)

VALUE

VALUE

VALUE

 

 

 

 

 

 

 

 

 

(HEX)

 

 

 

 

 

A4 H

164 H

 

-

0

255

SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,

 

 

 

HIGH BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)

 

 

 

 

 

 

 

 

 

 

A4 L

164 L

 

-

0

255

SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,

 

 

 

LOW BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)

 

 

 

 

 

 

 

 

 

 

A5 L

165 L

 

3

0

5

SPACE SENSOR OFFSET RANGE (DEGREES)

 

 

A6 L

166 L

 

-

0

100

RETURN AIR HUMIDITY (%)

 

 

A7 L

167 L

 

-

0

100

OUTSIDE AIR HUMIDITY (%)

 

 

A8 H

168 H

 

-

0

255

DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, HIGH BYTE)

 

 

A8 L

168 L

 

-

0

255

DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, LOW BYTE)

 

 

A9 H

169 H

 

-

0

255

BUILDING PRESSURE VALUE (0.001” WC, HIGH BYTE, 0 = -0.250”

 

 

 

WC, MAX = 0.250” WC)

 

 

 

 

 

 

 

 

 

 

A9 L

169 L

 

-

0

255

BUILDING PRESSURE VALUE (0.001” WC, LOW BYTE, 0 = -0.250”

 

 

 

WC, MAX = 0.250” WC)

 

 

 

 

 

 

 

 

 

 

AA H

170 H

 

-

0

255

DUCT PRESSURE VALUE (0.01” WC, HIGH BYTE, 0 = 0.00” WC,

 

 

 

MAX = 5.00” WC)

 

 

 

 

 

 

 

 

 

 

AA L

170 L

 

-

0

255

DUCT PRESSURE VALUE (0.01” WC, LOW BYTE, 0 = 0.00” WC, MAX

 

 

 

= 5.00” WC)

 

 

 

 

 

 

 

 

 

 

AB H

171 H

 

0

0

200

REMOTE CONTROL INPUT VALUE (0.05 VDC COUNTS FOR

 

 

 

COOLING SAT SETPOINT SCALING)

 

 

 

 

 

 

 

 

 

 

AB L

171 L

 

40

0

200

DEMAND VENTILATION SETPOINT (25 PPM INCREMENTS,

 

 

 

MAXIMUM 5000 PPM)

 

 

 

 

 

 

 

 

 

 

AC L

172 L

 

80

0

200

AIR QUALITY (DV) SENSOR RANGE (25 PPM INCREMENTS,

 

 

 

MAXIMUM 5000 PPM)

 

 

 

 

 

 

 

 

 

 

AD L

173 L

 

60

0

240

UNOCCUPIED OVERRIDE TIME PERIOD (MINUTES)

 

 

AE H

174 H

 

45

0

100

OUTDOOR AIR TEMPERATURE COOLING LOCKOUT

 

 

 

TEMPERATURE (DEGREES F, 0 = DISABLED)

 

 

 

 

 

 

 

 

 

 

AE L

174 L

 

75

0

100

OUTDOOR AIR TEMPERATURE HEATING LOCKOUT

 

 

 

TEMPERATURE (DEGREES F, 0 = DISABLED)

 

 

 

 

 

 

 

 

 

 

AF H

175 H

 

50

40

65

SAT COOLING LIMIT SETPOINT (DEGREES F)

 

 

 

 

 

 

 

 

 

 

6

AF L

175 L

 

135

100

180

SAT HEATING LIMIT SETPOINT (DEGREES F)

 

 

 

 

B0 H

176 H

 

120

80

180

HYDRONIC HEATING STAGE #1 SUPPLY AIR SETPOINT (DEGREES

 

 

 

 

 

F)

 

 

 

 

 

 

 

 

 

 

B0 L

176 L

 

150

80

180

HYDRONIC HEATING STAGE #2 SUPPLY AIR SETPOINT (DEGREES

 

 

 

F)

 

 

 

 

 

 

 

 

 

 

B1 H

177 H

 

80

60

85

COMFORT VENTILATION UPPER SETPOINT (DEGREES F)

 

 

B1 L

177 L

 

70

60

85

COMFORT VENTILATION LOWER SETPOINT (DEGREES F)

 

 

B2 H

178 H

 

60

40

70

VAV COOLING SUPPLY AIR TEMPERATURE: UPPER SETPOINT

 

 

 

(DEGREES F)

 

 

 

 

 

 

 

 

 

 

B2 L

178 L

 

55

40

70

VAV COOLING SUPPLY AIR TEMPERATURE: LOWER SETPOINT

 

 

 

(DEGREES F)

 

 

 

 

 

 

 

 

 

 

B3 H

179 H

 

72

40

85

VAV COOLING SUPPLY AIR TEMPERATURE: RESET SETPOINT

 

 

 

(DEGREES F)

 

 

 

 

 

 

 

 

 

 

B3 L

179 L

 

68

40

85

VAV OCCUPIED HEATING SETPOINT (DEGREES F)

 

 

Continued on next page

JOHNSON CONTROLS

137

Page 137
Image 137
York YPAL 050, YPAL 061, YPAL 051, YPAL 060 manual 137