TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
|
|
| INITIAL/ |
|
|
|
|
|
ADDRESS | ADDRESS | BIT | DEFAULT | MIN | MAX | DESCRIPTION |
|
|
(HEX) | (DEC) | VALUE | VALUE | VALUE |
|
| ||
|
|
|
| |||||
|
|
| (HEX) |
|
|
|
|
|
A4 H | 164 H |
| - | 0 | 255 | SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES, |
|
|
| HIGH BYTE, 16 BIT VALUE, 0 = |
|
| |||||
|
|
|
|
|
|
|
| |
A4 L | 164 L |
| - | 0 | 255 | SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES, |
|
|
| LOW BYTE, 16 BIT VALUE, 0 = |
|
| |||||
|
|
|
|
|
|
|
| |
A5 L | 165 L |
| 3 | 0 | 5 | SPACE SENSOR OFFSET RANGE (DEGREES) |
|
|
A6 L | 166 L |
| - | 0 | 100 | RETURN AIR HUMIDITY (%) |
|
|
A7 L | 167 L |
| - | 0 | 100 | OUTSIDE AIR HUMIDITY (%) |
|
|
A8 H | 168 H |
| - | 0 | 255 | DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, HIGH BYTE) |
|
|
A8 L | 168 L |
| - | 0 | 255 | DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, LOW BYTE) |
|
|
A9 H | 169 H |
| - | 0 | 255 | BUILDING PRESSURE VALUE (0.001” WC, HIGH BYTE, 0 = |
|
|
| WC, MAX = 0.250” WC) |
|
| |||||
|
|
|
|
|
|
|
| |
A9 L | 169 L |
| - | 0 | 255 | BUILDING PRESSURE VALUE (0.001” WC, LOW BYTE, 0 = |
|
|
| WC, MAX = 0.250” WC) |
|
| |||||
|
|
|
|
|
|
|
| |
AA H | 170 H |
| - | 0 | 255 | DUCT PRESSURE VALUE (0.01” WC, HIGH BYTE, 0 = 0.00” WC, |
|
|
| MAX = 5.00” WC) |
|
| |||||
|
|
|
|
|
|
|
| |
AA L | 170 L |
| - | 0 | 255 | DUCT PRESSURE VALUE (0.01” WC, LOW BYTE, 0 = 0.00” WC, MAX |
|
|
| = 5.00” WC) |
|
| |||||
|
|
|
|
|
|
|
| |
AB H | 171 H |
| 0 | 0 | 200 | REMOTE CONTROL INPUT VALUE (0.05 VDC COUNTS FOR |
|
|
| COOLING SAT SETPOINT SCALING) |
|
| |||||
|
|
|
|
|
|
|
| |
AB L | 171 L |
| 40 | 0 | 200 | DEMAND VENTILATION SETPOINT (25 PPM INCREMENTS, |
|
|
| MAXIMUM 5000 PPM) |
|
| |||||
|
|
|
|
|
|
|
| |
AC L | 172 L |
| 80 | 0 | 200 | AIR QUALITY (DV) SENSOR RANGE (25 PPM INCREMENTS, |
|
|
| MAXIMUM 5000 PPM) |
|
| |||||
|
|
|
|
|
|
|
| |
AD L | 173 L |
| 60 | 0 | 240 | UNOCCUPIED OVERRIDE TIME PERIOD (MINUTES) |
|
|
AE H | 174 H |
| 45 | 0 | 100 | OUTDOOR AIR TEMPERATURE COOLING LOCKOUT |
|
|
| TEMPERATURE (DEGREES F, 0 = DISABLED) |
|
| |||||
|
|
|
|
|
|
|
| |
AE L | 174 L |
| 75 | 0 | 100 | OUTDOOR AIR TEMPERATURE HEATING LOCKOUT |
|
|
| TEMPERATURE (DEGREES F, 0 = DISABLED) |
|
| |||||
|
|
|
|
|
|
|
| |
AF H | 175 H |
| 50 | 40 | 65 | SAT COOLING LIMIT SETPOINT (DEGREES F) |
|
|
|
|
|
|
|
|
|
| 6 |
AF L | 175 L |
| 135 | 100 | 180 | SAT HEATING LIMIT SETPOINT (DEGREES F) |
| |
|
|
| ||||||
B0 H | 176 H |
| 120 | 80 | 180 | HYDRONIC HEATING STAGE #1 SUPPLY AIR SETPOINT (DEGREES |
|
|
|
| |||||||
| F) |
|
| |||||
|
|
|
|
|
|
|
| |
B0 L | 176 L |
| 150 | 80 | 180 | HYDRONIC HEATING STAGE #2 SUPPLY AIR SETPOINT (DEGREES |
|
|
| F) |
|
| |||||
|
|
|
|
|
|
|
| |
B1 H | 177 H |
| 80 | 60 | 85 | COMFORT VENTILATION UPPER SETPOINT (DEGREES F) |
|
|
B1 L | 177 L |
| 70 | 60 | 85 | COMFORT VENTILATION LOWER SETPOINT (DEGREES F) |
|
|
B2 H | 178 H |
| 60 | 40 | 70 | VAV COOLING SUPPLY AIR TEMPERATURE: UPPER SETPOINT |
|
|
| (DEGREES F) |
|
| |||||
|
|
|
|
|
|
|
| |
B2 L | 178 L |
| 55 | 40 | 70 | VAV COOLING SUPPLY AIR TEMPERATURE: LOWER SETPOINT |
|
|
| (DEGREES F) |
|
| |||||
|
|
|
|
|
|
|
| |
B3 H | 179 H |
| 72 | 40 | 85 | VAV COOLING SUPPLY AIR TEMPERATURE: RESET SETPOINT |
|
|
| (DEGREES F) |
|
| |||||
|
|
|
|
|
|
|
| |
B3 L | 179 L |
| 68 | 40 | 85 | VAV OCCUPIED HEATING SETPOINT (DEGREES F) |
|
|
Continued on next page
JOHNSON CONTROLS | 137 |