FORM
TABLE 7-1 – DEFINITIONS (CONTINUED)
MENU ITEM | DEFINITION |
|
|
| THIS PARAMETER ALLOWS THE EXHAUST FAN TO OPERATE |
|
|
ERV UNOCCUPIED FAN ENABLE | ANYTIME THE SUPPLY FAN IS ON. THIS FEATURE IS REQUIRED |
|
|
WHEN AN ENERGY RECOVERY VENTILATOR IS INSTALLED. |
|
| |
|
|
| |
| THIS FEATURE IS CURRENTLY NOT USED ON THESE UNITS. |
|
|
EXHAUST DAMPER POSITION FOR EXHAUST | WHEN MODULATING DAMPER EXHAUST IS BEING USED THIS IS |
|
|
THE POSITION OF THE EXHAUST DAMPER TO TURN OFF THE |
|
| |
TO TURN OFF |
|
| |
EXHAUST FAN |
|
| |
|
|
| |
EXHAUST DAMPER POSITION FOR EXHAUST | WHEN MODULATING DAMPER EXHAUST IS BEING USED THIS |
|
|
IS THE POSITION OF THE EXHAUST DAMPER TO TURN ON THE |
|
| |
TO TURN ON |
|
| |
EXHAUST FAN |
|
| |
|
|
| |
EXHAUST FAN OUTPUT | THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE |
|
|
UNIT CONTROLLER TO THE EXHAUST FAN, OFF OR ON |
|
| |
|
|
| |
| THIS GIVES THE STATUS OF THE ANALOG UNIT CONTROLLER |
|
|
EXHAUST DAMPER / VFD OUTPUT STATUS | OUTPUT TO THE EXHAUST DAMPER OR EXHAUST FAN VFD IN |
|
|
| % |
|
|
| THIS PARAMETER IDENTIFIES TO THE UNIT CONTROLLER THAT |
|
|
EXHAUST VFD INSTALLED | AN EXHAUST FAN VFD IS INSTALLED. THE PARAMETER MUST |
|
|
| BE TURNED ON TO ENABLE THIS FEATURE |
|
|
FAN (G) THERMOSTAT INPUT | THIS GIVES THE STATUS OF THE BINARY INPUT TO THE G |
|
|
TERMINAL OF THE UNIT CONTROLLER, OFF OR ON |
|
| |
|
|
| |
FAN ASD TIMER | THIS IS THE STATUS OF THE SUPPLY FAN OFF DELAY IN |
|
|
SECONDS |
|
| |
|
|
| |
FAN OFF DELAY TIMER FOR COOL | THIS GIVES THE STATUS OF THE COOLING TIME OFF DELAY IN |
|
|
SECONDS |
|
| |
|
|
| |
FAN OFF DELAY TIMER FOR HEAT | THIS GIVES THE STATUS OF THE COOLING TIME OFF DELAY IN |
|
|
SECONDS |
|
| |
|
|
| |
FAN ON DELAY TIMER FOR COOL | THIS GIVES THE STATUS OF THE COOLING TIME ON DELAY IN |
|
|
SECONDS |
|
| |
|
|
| |
FAN ON DELAY TIMER FOR HEAT | THIS GIVES THE STATUS OF THE COOLING TIME ON DELAY IN |
|
|
SECONDS |
|
| |
|
|
| |
| THIS IS THE BINARY INPUT FROM THE HYDRONIC HEAT FREEZE |
|
|
FREEZE THERMOSTAT SWITCH | STAT TO THE UNIT CONTROLLER. OFF = FAULTED, ON = |
|
|
| NORMAL OPERATION |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE GAS |
|
|
GAS VALVE #1 | VALVE FOR HEAT SECTION 1 TO THE UNIT CONTROLLER OFF / |
|
|
| ON |
|
|
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE GAS |
|
|
GAS VALVE #2 | VALVE FOR HEAT SECTION 2 TO THE UNIT CONTROLLER OFF / |
|
|
| ON |
|
|
| 7 | ||
| THIS IS THE STATUS OF THE BINARY INPUT FROM THE GAS |
| |
GAS VALVE #3 | VALVE FOR HEAT SECTION 3 TO THE UNIT CONTROLLER OFF / |
|
|
| ON |
|
|
HEAT 1 (W1) | THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL W1 |
|
|
- FIRST STAGE HEATING |
|
| |
|
|
| |
HEAT 1 ASCD TIMER | THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR |
|
|
HEAT SECTION 1 IN SECONDS. |
|
| |
|
|
| |
| Continued on next page |
|