York YPAL 050, YPAL 061, YPAL 051, YPAL 060 9 - ALARM CODE DESCRIPTIONS, Alarm Code, Description

Models: YPAL 060 YPAL 051 YPAL 050 YPAL 061

1 168
Download 168 pages 27.04 Kb
Page 161
Image 161

FORM 100.50-NOM6 (1207)

TABLE 8-9 – ALARM CODE DESCRIPTIONS

ALARM CODE

DESCRIPTION

01

COMPRESSOR SYSTEM 1 (COMPRESSORS 1A, 1B) LOCKED OUT ON HIGH PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 2-HOUR WINDOW.

 

02

COMPRESSOR SYSTEM 1 (COMPRESSORS 1A, 1B) LOCKED OUT ON HIGH PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 2-HOUR WINDOW.

 

03

COMPRESSOR SYSTEM 2 (COMPRESSORS 2A, 2B) LOCKED OUT ON HIGH PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 2-HOUR WINDOW.

 

 

 

04

COMPRESSOR SYSTEM 2 (COMPRESSORS 2A, 2B) LOCKED OUT ON HIGH PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 2-HOUR WINDOW.

 

05

COMPRESSOR SYSTEM 1 (COMPRESSORS 1A, 1B) LOCKED OUT ON LOW PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

06

COMPRESSOR SYSTEM 1 (COMPRESSORS 1A, 1B) LOCKED OUT ON LOW PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

07

COMPRESSOR SYSTEM 2 (COMPRESSORS 2A, 2B) LOCKED OUT ON LOW PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

 

 

08

COMPRESSOR SYSTEM 2 (COMPRESSORS 2A, 2B) LOCKED OUT ON LOW PRESSURE CONTROL. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

09

COMPRESSOR SYSTEM 1A LOCKED OUT ON COMPRESSOR MOTOR PROTECTION MODULE. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

10

COMPRESSOR SYSTEM 1B LOCKED OUT ON COMPRESSOR MOTOR PROTECTION MODULE. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

11

COMPRESSOR SYSTEM 2A LOCKED OUT ON COMPRESSOR MOTOR PROTECTION MODULE. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

12

COMPRESSOR SYSTEM 2B LOCKED OUT ON COMPRESSOR MOTOR PROTECTION MODULE. THE CIRCUIT

OPENED THREE TIMES WITHIN A 1-HOUR WINDOW.

 

13

FIRST STAGE HEATING IS LOCKED OUT ON LIMIT SWITCH TRIPS. THE CIRCUIT OPENED THREE TIMES WITHIN

A 1-HOUR WINDOW.

 

14

SECOND STAGE HEATING IS LOCKED OUT ON LIMIT SWITCH TRIPS. THE CIRCUIT OPENED THREE TIMES

WITHIN A 1-HOUR WINDOW.

 

15

THIRD STAGE HEATING IS LOCKED OUT ON LIMIT SWITCH TRIPS. THE CIRCUIT OPENED THREE TIMES WITHIN

A 1-HOUR WINDOW.

 

 

FIRST STAGE OF HEATING IS LOCKED OUT BECAUSE THE IGNITION CONTROL BOARD FAILED TO TURN

16

ON THE GAS VALVE AFTER 5 MINUTES OF OPERATION OR THE GAS VALVE HAS VOLTAGE ON IT AND THE

 

CONTROL IS NOT CALLING FOR THE STAGE OF HEATING.

 

SECOND STAGE OF HEATING IS LOCKED OUT BECAUSE THE IGNITION CONTROL BOARD FAILED TO TURN

17

ON THE GAS VALVE AFTER 5 MINUTES OF OPERATION OR THE GAS VALVE HAS VOLTAGE ON IT AND THE

 

CONTROL IS NOT CALLING FOR THE STAGE OF HEATING.

 

THIRD STAGE OF HEATING IS LOCKED OUT BECAUSE THE IGNITION CONTROL BOARD FAILED TO TURN

18

ON THE GAS VALVE AFTER 5 MINUTES OF OPERATION OR THE GAS VALVE HAS VOLTAGE ON IT AND THE

 

CONTROL IS NOT CALLING FOR THE STAGE OF HEATING.

19

SPACE TEMPERATURE SENSOR HAS FAILED OPEN OR SHORTED. THE DISPLAY WILL INDICATE –40.0.

 

 

20

SUPPLY AIR TEMPERATURE SENSOR HAS FAILED OPEN OR SHORTED. THE DISPLAY WILL INDICATE –40.0.

21

RETURN AIR TEMPERATURE SENSOR HAS FAILED OPEN OR SHORTED. THE DISPLAY WILL INDICATE –40.0.

22

OUTDOOR AIR TEMPERATURE SENSOR HAS FAILED OPEN OR SHORTED. THE DISPLAY WILL INDICATE –40.0.

23

DIRTY FILTER SWITCH HAS CLOSED INDICATING THE FILTERS NEED REPLACED. THIS HAS NO EFFECT ON

THE OPERATION OF THE UNIT.

 

 

 

8

Continued on next page

JOHNSON CONTROLS

161

Page 161
Image 161