4) Common specifications

Control specifications

Item

Description

Control method

Sinusoidal PWM control

Output voltage

Main circuit voltage feedback control (Automatic regulation, "fixed" and "control off"

adjustment

selections possible)

Output frequency range

0.01 to 400Hz, set to 0.01 to 80Hz by default, max. frequency adjustable from 30 to 400Hz

Frequency setting

0.01Hz: operation panel input (60Hz base), 0.015Hz: analog input (60Hz base, 12/16

resolution

bit/0-10Vdc)

Frequency

+/-0.2% of the max. output frequency (25+/-10°C): analog input, +/-0.01% (25+/-

precision

10°C): digital input

Voltage/

Constant V/f, variable torque, automatic torque boost, vector control and automatic energy-saving

frequency

control, base frequency 1234 adjustment (25 to 400Hz) arbitrary V/f 5-point settings, torque boost

characteristic

adjustment (0 to 30%), start-up frequency adjustment (0 to 10Hz), end frequency adjustment (0 to 30Hz)

Frequency setting

3kΩ potentiometer (1 to 10kΩ-potentiometer connection also possible), 0 to 10Vdc

signal

(input impedance Zin: 33kΩ), 0 to +/-10Vdc (Zin: 67kΩ), 4 to 20mAdc (Zin: 500Ω)

Terminal board reference

2 sources can be set from a total of seven types, including analog input (RR, VI, II,

frequency input

RX, RX2), pulse and binary/BCD (*RX2 and binary/BCD: optional)

Frequency jump

Can be set in three places, jump frequency and band setting

Upper/lower limit

Upper limit frequency: 0 to maximum frequency, lower limit frequency: 0 to upper

frequencies

limit frequency

PWM carrier

Adjustable within a range of 0.5 to 15kHz

(0.5 to 8kHz for 200V 55kW model and 400V 75kW model,

frequency selections

 

0.5 to 5kHz for 200V 75-90kW models and 400V 110-280kW models)

PID control

Proportional gain, integral time, anti-hunting gain, filter delay adjustments

Torque control

Voltage control reference: DC0 to +/-10V

 

Acceleration/

0.01 to 6000 sec., acceleration/deceleration time selectable from among 1, 2, 3 and 4, automatic

 

deceleration time

acceleration/deceleration function, S-pattern acceleration/deceleration patterns 1 and 2 adjustment

 

DC injection

Braking start frequency: adjustment (0 to 120Hz), braking current adjustment: ( 0 to 100%), braking time

 

braking

adjustment: (0 to 10 sec.), emergency stop braking function, motor shaft stationary control function

 

Forward/reverse

Forward run F-CC "closed", reverse when R-CC "closed", reverse when both "closed"

 

run (*1)

coast stop when ST-CC "opened", Emergency stop from panel or terminal block

 

Jog run (*1)

Jog run from panel with JOG mode selection. Terminal block operation possible with

 

parameter settings.

 

 

 

Preset-speed

Set frequency +15-speed preset speeds possible with open/close combinations. S1,

 

S2,S3, S4 and CC Acceleration/deceleration time, torque limit and V/f selectable on

 

operation (*1)

 

a frequency.

 

 

specifications

Retry

When a protective function activities, after main circuit devices are checked, running

restarts. Settable to a max. of 10times. wait time adjustment (0 to 10sec)

 

 

 

 

Soft-stall

Automatic load reduction control during overload (Default setting: OFF)

 

Cooling fan ON/OFF

Fan is automatically stopped, When not necessary to ensure to extended life time.

 

Panel key

Prohibit functions such as reset only or monitor only etc., can be selected. All key

Operation

operation ON/OFF

operations can be also prohibited. A protection reset function which requires special

switching

operation to enable it is available.

 

 

Regenerative power

Operation is continued even during momentary power failure using regenerative

 

ride-through control

energy from the motor. (Default setting: OFF)

 

Auto-restart in

The motor can be restarted at the same speed in the same direction it run under no-

 

load conditions before stop. (Default setting: OFF)

 

 

 

Simple pattern

32 patterns in 4 groups (8 pattern in each group) can be set according to 15-speed

 

operation frequency. Up to 32 patterns of operation, control from terminal

 

run

 

board/repeated operation possible.

 

 

 

Commercial power/

Power supply to motor, switchable between commercial power and inverter

 

inverter switching

 

 

High-speed run at

With this function, the load applied to the motor can be monitored. Its rotating speed

 

low-load

is increased to improve the operation efficiency when the load applied to it is low.

 

Drooping function

This function prevent a load from being imposed to a single inverter because of

 

 

imbalance, when more than one inverter is used in combination to drive the load.

 

Override function

Preset frequency control value adjustable by signals from an external control unit

 

Protective

Stall prevention, current limit, over-current, over-voltage, load-side short-circuit, load-side ground

Protection

fault(*7), undervoltage, momentary power failure (15ms or longer), regeneration power ride-through

function

control, electronic thermal overload protection, armature over-current during start-up, load-side

 

over-current during start-up, dynamic braking resistor overload, heat sink overheat, emergency stop

Electronic thermal

Standard motor/constant-torque VF motor switching, electronic thermal stall

characteristic

prevention operational level adjustment

 

Reset

Reset triggered by closing 1a-contact (or opening 1b-contact), by control panel operation, or

 

by turning on the power after turning off temporarily. Tripped state retention and clear settings

 

 

(Continued on the following page)