Toshiba VF-A7 Resolution, Calibrating a meter when the inverter is out of operation

Models: VF-A7

1 250
Download 250 pages 39.4 Kb
Page 72
Image 72

[Terminal AM-related parameters]

Title

Function

Adjustment range

Default setting



AM Terminal meter selection

Same as (: disabled)



AM Terminal meter adjustment

Resolution

Both the terminals FM and AM have a maximum resolution of 1/1024.

With the default settings, FM terminal outputs about 16 V (external impedance is infinity) or about 3mA (external impedance is 0 ohm), when running frequency is 80Hz. AM terminal outputs about 16 V or about 3mA, when the output current reading on the control panel is 150%

■Calibrating a meter when the inverter is out of operation

If it is difficult to calibrate a meter because of large fluctuations of its reading, you may put the inverter out of operation to make its calibration easier.

It is possible to adjust the meter for hte data item selected with the parameter  or . Refer to the table on the next page for the calibration procedure.

Adjustment level:

(a): The output voltage FM/AM-CC reaches 100% at the maximum frequency ().

(b): The output voltage at FM/AM-CC reaches 100% when the reading on the control panel is 150%.

(c): The output voltage at FM/AM-CC reaches 100% when the reading on the control panel is 100%.

(d): Special output (Refer to the instruction manual for the applicable device.)

(e): The output voltage at FM/AM-CC reaches 100% when the electric power is √3×200V(400V)×(inverter rated current).

[Example of the calibration of the frequency meter connected to the terminal FM-CC]

*Before proceeding to calibration, make the zero-adjustment of the meter itself.

Key operated,

LED display

 

 

 

Operation

 



The running frequency is displayed.(If the monitor display

 

mode setting  is set at [Running frequency])

 

 

 

 

MON



Press the MON key to call up the first basic parameter

 

 (automatic acceleration/deceleration).

 

 

 

 

 

 

 

 

 

 

 



Select  by pressing the or key.

 

 

 

 

 

 

 

 

 

ENT



Press the Enter key to display the running frequency.

 

 

 

 

 

 

 

 

 

 

 

Adjust the meter by pressing the or key.

 

 

 

Note that the meter reading varies during adjustment,

 

 

 

though the reading in the digital LED (monitor) on the

 

control panel does not change.



 

 

 

[Point] Holding down the key for several

 

 

 

 

 

 

 

 

 

 

 

 

 

 

seconds facilitates this adjustment.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

By setup, before

the needle of meter begins to sway,

 

 

 

it will take time.

 

ENT

 

Press the Enter key to terminate the meter calibration.

 



Then,  and the running frequency are displayed

 

 

 

alternately.

 

MON

 

Press the Monitor key to return to the running frequency

 



display mode.(If the monitor display mode setting parameter

 

 

 

 is set at [Running frequency])

For meter connection, the VF-A7 inverter has two output terminals; FM and AM, which can be used simultaneously.

E-11

Page 72
Image 72
Toshiba VF-A7 instruction manual Resolution, Calibrating a meter when the inverter is out of operation