Trane BCHC Installation Controls, Installing Wall Mounted Controls, Zone Sensor Installation

Page 25

Installation Controls

Installing Wall Mounted Controls

Wall mounted zone sensors ship taped to the control box. Refer to Figure 3 for zone sensor dimensions.

Position the controller on an inside wall three to five feet above the floor and at least 18 inches from the nearest outside wall. Installing the controller at a lower height may give the advantage of monitoring the temperature closer to the zone, but it also exposes the controller to airflow obstructions. Ensure that air flows freely over the controller.

Before beginning installation, follow the wiring instructions below. Also, refer to the unit wiring schematic for specific wiring details and point connections.

Wiring Instructions

Avoid mounting the controller in an area subject to the following conditions:

Dead spots, such as behind doors or in corners that do not allow free air circulation.

Air drafts from stairwells, outside doors, or unsectioned hollow walls.

Radiant heat from the sun, fireplaces, appliances, etc.

Airflow from adjacent zones or other units.

Unheated or uncooled spaces behind the controller, such as outside walls or unoccupied spaces.

Concealed pipes, air ducts, or chimneys in partition spaces behind the controller.

Zone Sensor Installation

Follow the procedure below to install the zone sensor module (see Figure 3).

Figure 3. Wall-mounted zone sensor dimensions

1.Note the position of the setpoint adjustment knob and gently pry the adjustment knob from the cover using the blade of a small screwdriver.

2.Insert the screwdriver blade behind the cover at the top of the module and carefully pry the cover away from the base.

3.To install the zone sensor module without a junction box (directly to the wall):

a.Using the module base as a template, mark the rectangular cutout for the control wiring and module installation holes. Ensure the base is level.

b.Set the base aside and make the cutout. Then, drill two 3/16” diameter holes approximately one-inch deep. Insert and fully seat the plastic anchors.

c.Pull the control wires through the cutout and attach the module to the wall using the screws provided.

4.To install the zone sensor module to a standard junction box:

a.Level and install a 2” x 4” junction box (installer supplied) vertically on the wall.

BCXC-SVX01B-EN

25

Image 25
Contents April Blower Coil Air HandlerEnvironmental Concerns Refrigerant warning informationResponsible Refrigerant Practices Hazard of Explosion and Deadly Gases Trademarks About This ManualTable of Contents BCXC-SVX01B-EN Digits 1, 2, 3, 4 Unit Model Digit 16 Motor HorsepowerDigits 5, 6, 7 Unit Size Digit 8 Unit VoltageModel Number Description Blower Coil General Information General InformationGeneral Information Receiving and Handling Pre-InstallationJobsite Storage Recommendations Service Access Installation PreparationPre-Installation Unit size Dimension aRigging and Handling Unit Handling ProcedureImproper Unit Lift Unit Location RecommendationsSkid Removal Pre-Installation ChecklistHorizontal blower coil dimensions in. and weights lb Dimensions and WeightsUnit Size RH LH Weight Horizontal Blower CoilVertical blower coil dimensions in. and weights lb Dimensions and WeightsUnit Size Weight Vertical Blower CoilAngle Filter and Mixing Box Angle filter and mixing box dimensions in. and weights lbUnit size AIR Flow Filter Filter Access Panel Bottom or Top Access Filter BoxElectric Heat Electric heat dimensions in. and weights lbSteam Coil Steam coil box dimensions in. and weights lbCoil Connections, NPT Supply ReturnHydronic coil connection sizes, OD Coil ConnectionsDX coil connection sizes, OD Steam coil connection sizes, female connection, NPTBasic Piping Piping PackagesDimensions and Weights Deluxe Piping Actual size Piping NominalInstalling Wall Mounted Controls Installation ControlsZone Sensor Installation Wiring InstructionsInstallation Controls Communication WiringService Communication Wiring Zone Sensors Without Interconnecting WiringTracer Summit Communication Wiring Installation Electrical Zone sensor maximum wiring distances, ft m Installation ElectricalWire size range Max. wiring distance Electrical Grounding Restrictions Hazardous VoltageAvailable electric heat, min-max kW Useful FormulasUnit size Voltage Motor electrical data 240/50/1 220/50/1190/50/3 380/50/3Installing the Unit Installation MechanicalBchc Installation Procedure Horizontal Units, Model BchcVertical Units, Model Bcvc Installation MechanicalMixing Box Option Heating Coil OptionLinkage Installation Procedure Mixing Box Installation ProcedureCondensate Drain Connections Duct Connections Recommended drain trap installation for draw-through unitsWater Coil Connections Installation PipingPotential coil-freeze condition Refrigerant Coil PipingValve Damage Installation PipingSuction Line Field-installed evaporation piping example Field-Installing Evaporator PipingCoil Condensate Steam PipingGeneral Steam CoilsType NS steam coils, horizontal tubes for horizontal airflow Control Options Controls InterfaceTracer Controllers Controls Interface Rover Service SoftwareTracer controller input/output summary Tracer controller ZN010 ZN510 ZN520End Device Option Availability Tracer controller function summaryTracer Control Device ZN010 Tracer ZN510 Tracer ZN520 Pre-Start Pre-Start ChecklistReceiving Unit LocationDuctwork Pre-Start Component OverviewUnit Piping ElectricalSequence of Operation Start-UpTracer ZN Controller Sequence of Operation Unoccupied Mode Occupied ModeSensor type Sensor position Unit occupancy mode Start-UpCooling Operation Occupied Standby Mode Tracer ZN510 or ZN520 onlyOccupied Bypass Mode, Tracer ZN510 or ZN520 Only DX Cooling Tracer ZN520 only Start-Up Economizer Cooling Tracer ZN520 OnlyDischarge Air Tempering Tracer ZN520 Only Heating OperationTracer ZN520 fan configuration Fan Mode Operation Rotating ComponentsAuto fan operation Fan speed default Fan sequence of operationTracer ZN010 and ZN510 Fan Speed SwitchTracer ZN520 Continuous Fan OperationFan mode operation, Tracer ZN010 and ZN510 Fan Off DelayStart-Up Fan Cycling Operation Fan Start on High SpeedLocal fan switch enabled Entering Water Temperature Sampling FunctionTwo- and Four-Pipe Changeover Operation Fan operation in heating and cooling modesUnit type EWT sensor required? Coil water temperature Unit mode as related to water temperatureElectric Heat Operation Economizer Damper Tracer ZN520 OnlyTracer Dehumidification Tracer ZN520 Only BIP1 Low Temperature Detection OptionData Sharing Tracer ZN510 or ZN520 Only Binary InputsBIP2 Condensate Overflow Detection Option Binary input configurationsBIP3 Occupancy Sensor BIP4 Fan Status ZN520 OnlyBinary Outputs Analog InputsAnalog inputs Analog input Terminal Function Range ZN010 ZN510 ZN520Binary output configuration Space Temperature MeasurementZone sensor wiring connections Zone SensorExternal Setpoint Adjustment Fan Mode SwitchFan Switch Local SetpointCommunication Jack On/Cancel ButtonsMaintenance Procedures MaintenanceFan Assembly Set Screws MaintenanceFan Belt Tension Torque in.-lb Ft-lbBCBH/BCVC valve package waterflow limits Belt tensionHydronic coil data BCHC/BCVC coil general dataRow coil Steam coil data Unit Motor Motor sheave Fan sheave Belt Drive data1750 1450 Size Watts Browning Trane 60 Hz 50 Hz Potential unit damage from coil cleaners Coil MaintenanceInspecting and Cleaning Coils Steam, Hot Water, and Cooling Coil Cleaning ProcedureRotating parts Periodic Maintenance ChecklistsMaintenance Troubleshooting DiagnosticsLED Activity Manual Output Test Procedure DiagnosticsManual Output Test Translating Multiple Diagnostics DiagnosticsTracer ZN520 test sequence Fan Cool output a Heat output Damper Steps J1-1, J1-3Automatic Reset by the Controller Resetting DiagnosticsCycling Power Diagnostics Manual Output TestRover Service Tool Diagnostic Reset Tracer ZN510 or ZN520 OnlyTracer ZN520 diagnostics Tracer ZN010 and ZN510 controller diagnosticsDiagnostic Latching Fan Valves Electric heat Damper Diagnostic Fan Other outputsaFan outputs do not energize Common DiagnosticsValves stay closed Probably cause ExplanationElectric heat not operating Valves stay openFresh air damper stays closed DX or electric outputs do not energize Fresh air damper stays openTwo-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Two-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Control Interface Four-Pipe Bcxc with Control Interface Bcxc with DX Coil and Tracer ZN520 Field Installed DeviceBcxc with DX Coil, Hydronic Heating, and Tracer ZN520 BCXC-SVX01B-EN