Trane Comprehensive Guide to BCHB Blower Coil Models

Page 7

Model Number Description

Following is a complete description of the blower coil model number. Each digit in the model number has a corresponding code that identifies specific unit options.

Digits 1, 2, 3, 4 — Unit Model

BCHC= horizontal blower coil

BCVC= vertical blower coil

Digits 5, 6, 7 — Unit Size

012

024

054

 

018

036

072

090

Digit 8 — Unit Voltage

A

=

115/60/1

H

=

575/60/3

B

=

208/60/1

J

=

220/50/1

C

=

230/60/1

K

=

240/50/1

D

=

277/60/1

L

=

380/50/3

E

=

208/60/3

M

=

415/50/3

F

=

230/60/3

N

=

190/50/3

G

=

460/60/3

P

= two-speed,

 

 

 

 

 

115/60/1

0

=

no motor, ctrls, elec ht.

Digit 9 —Insulation Type

1= 1” matte-faced

2= 1” foil-faced

Digits 10, 11 — Design Sequence

A0

Digit 12 — Motor, Drive, and Control Box Location

A= same side as coil connections, horizontal or counterswirl only

B= opposite side from coil connections, horizontal or counterswirl only

C= same side as coil connections, pre-swirl only

D= opposite side from coil connections, pre-swirl only

R= right-hand access L = left-hand access

Digit 13 — Drain Pan Type, Coil & Drain Connection Side

0 = none

1= polymer drain pan & right-hand connections

2= polymer drain pan & left-hand connections

3= stainless steel drain pan & right- hand connections

4= stainless steel drain pan & left- hand connections

Digit 14 — Unit Coil #1*

Note: All coils are hydronic unless stated

 

 

otherwise.

0

=

none

A

=

1-row preheat

L

=

2-row hydronic high-capacity

 

 

preheat

F= 4-row hydronic

G= 6-row hydronic

J= 4-row hydronic, autochangeover

K= 6-row hydronic, autochangeover

M= 4-row hydronic high-capacity

N= 6-row hydronic high-capacity

R= 4-row hydronic high-capacity, autochangeover

T= 6-row hydronic high-capacity, autochangeover

1= 3-row DX, 3/16” distributor (0.032)

2= 4-row DX, 3/16” distributor (0.032)

3= 6-row DX, 3/16” distributor (0.032)

4= 3-row DX, 3/16” distributor (0.049)

5= 4-row DX, 3/16” distributor (0.049)

6= 6-row DX, 3/16” distributor (0.049)

Digit 15 — Unit Coil #2*

Note: All coils are hydronic unless stated otherwise.

0 = none

A = 1-row reheat

L= 2-row hydronic high-capacity reheat

F= 4-row hydronic

G= 6-row hydronic

H= 2-row hydronic, autochangeover

J= 4-row hydronic, autochangeover

K= 6-row hydronic, autochangeover

M= 4-row hydronic high-capacity

N= 6-row hydronic high-capacity

P = 2-row hydronic high-capacity, autochangeover

R= 4-row hydronic high-capacity, autochangeover

T= 6-row hydronic high-capacity, autochangeover

1= 3-row DX, 3/16” distributor (0.032)

2= 4-row DX, 3/16” distributor (0.032)

3= 6-row DX, 3/16” distributor (0.032)

4= 3-row DX, 3/16” distributor (0.049)

5= 4-row DX, 3/16” distributor (0.049)

6= 6-row DX, 3/16” distributor (0.049)

Digit 16 — Motor Horsepower

0

=

none

4

=

1 hp

1

=

1/3 hp

5

=

1-1/2 hp

2

=

1/2 hp

6

=

2 hp

3

=

3/4 hp

7

=

3 hp

Digit 17 — Motor Drives

0 = none

A= 390–552 rpm / 60 Hz

B= 478–678 rpm / 60 Hz

C= 540–765 rpm / 60 Hz

D= 619–878 rpm / 60 Hz

E= 727–1029 rpm / 60 Hz

F= 879–1245 rpm / 60 Hz

G= 1000–1417 rpm / 60 Hz

H= 1200–1700 rpm / 60 Hz

J= 1313–1859 rpm / 60 Hz

K= 1615–2288 rpm / 60 Hz

L= 678–877 rpm / 60 Hz

M= 765–990 rpm / 60 Hz

N= 878–1136 rpm / 60 Hz

P

=

1029–1332 rpm / 60 Hz

R

=

1245–1611 rpm / 60 Hz

T

=

1174–1519 rpm / 50 Hz

Digit 18 — Electric Heat Stages

0 = none

1= 1-stage

2= 2-stage

Digits 19, 20, 21 — Electric Heat

000 =

none

100

=

10.0 kW

010

=

1.0 kW

110

=

11.0 kW

015

=

1.5 kW

120

=

12.0 kW

020

=

2.0 kW

130

=

13.0 kW

025

=

2.5 kW

140

=

14.0 kW

030

=

3.0 kW

150

=

15.0 kW

035

=

3.5 kW

160

=

16.0 kW

040

=

4.0 kW

170

=

17.0 kW

045

=

4.5 kW

180

=

18.0 kW

050

=

5.0 kW

190 =

19.0 kW

055

=

5.5 kW

200 =

20.0 kW

060

=

6.0 kW

210 =

21.0 kW

065

=

6.5 kW

220

=

22.0 kW

070

=

7.0 kW

240

=

24.0 kW

075

=

7.5 kW

260

=

26.0 kW

080

=

8.0 kW

280

=

28.0 kW

090

=

9.0 kW

300 =

30.0 kW

Digit 22 — Electric Heat Controls

0 = none

A= 24 volt magnetic contactors

B= 24 volt mercury contactors

Digit 23 — Electric Heat Options

0 = none

A= electric heat with heater fuse

B= electric heat interlocking non- fused disconnect

C= A & B

BCXC-SVX01B-EN

7

Image 7
Contents April Blower Coil Air HandlerEnvironmental Concerns Refrigerant warning informationResponsible Refrigerant Practices Hazard of Explosion and Deadly Gases Trademarks About This ManualTable of Contents BCXC-SVX01B-EN Digit 8 Unit Voltage Digit 16 Motor HorsepowerDigits 1, 2, 3, 4 Unit Model Digits 5, 6, 7 Unit SizeModel Number Description Blower Coil General Information General InformationGeneral Information Receiving and Handling Pre-InstallationJobsite Storage Recommendations Unit size Dimension a Installation PreparationService Access Pre-InstallationUnit Location Recommendations Unit Handling ProcedureRigging and Handling Improper Unit LiftSkid Removal Pre-Installation ChecklistHorizontal Blower Coil Dimensions and WeightsHorizontal blower coil dimensions in. and weights lb Unit Size RH LH WeightVertical Blower Coil Dimensions and WeightsVertical blower coil dimensions in. and weights lb Unit Size WeightAngle Filter and Mixing Box Angle filter and mixing box dimensions in. and weights lbUnit size AIR Flow Filter Filter Access Panel Bottom or Top Access Filter BoxElectric Heat Electric heat dimensions in. and weights lbSupply Return Steam coil box dimensions in. and weights lbSteam Coil Coil Connections, NPTSteam coil connection sizes, female connection, NPT Coil ConnectionsHydronic coil connection sizes, OD DX coil connection sizes, ODBasic Piping Piping PackagesDimensions and Weights Deluxe Piping Actual size Piping NominalWiring Instructions Installation ControlsInstalling Wall Mounted Controls Zone Sensor InstallationZone Sensors Without Interconnecting Wiring Communication WiringInstallation Controls Service Communication WiringTracer Summit Communication Wiring Installation Electrical Electrical Grounding Restrictions Hazardous Voltage Installation ElectricalZone sensor maximum wiring distances, ft m Wire size range Max. wiring distanceAvailable electric heat, min-max kW Useful FormulasUnit size Voltage Motor electrical data 380/50/3 220/50/1240/50/1 190/50/3Horizontal Units, Model Bchc Installation MechanicalInstalling the Unit Bchc Installation ProcedureVertical Units, Model Bcvc Installation MechanicalMixing Box Option Heating Coil OptionLinkage Installation Procedure Mixing Box Installation ProcedureCondensate Drain Connections Duct Connections Recommended drain trap installation for draw-through unitsRefrigerant Coil Piping Installation PipingWater Coil Connections Potential coil-freeze conditionValve Damage Installation PipingSuction Line Field-installed evaporation piping example Field-Installing Evaporator PipingSteam Coils Steam PipingCoil Condensate GeneralType NS steam coils, horizontal tubes for horizontal airflow Control Options Controls InterfaceTracer Controllers Tracer controller ZN010 ZN510 ZN520 Rover Service SoftwareControls Interface Tracer controller input/output summaryEnd Device Option Availability Tracer controller function summaryTracer Control Device ZN010 Tracer ZN510 Tracer ZN520 Unit Location Pre-Start ChecklistPre-Start ReceivingElectrical Pre-Start Component OverviewDuctwork Unit PipingSequence of Operation Start-UpTracer ZN Controller Sequence of Operation Start-Up Occupied ModeUnoccupied Mode Sensor type Sensor position Unit occupancy modeCooling Operation Occupied Standby Mode Tracer ZN510 or ZN520 onlyOccupied Bypass Mode, Tracer ZN510 or ZN520 Only Heating Operation Start-Up Economizer Cooling Tracer ZN520 OnlyDX Cooling Tracer ZN520 only Discharge Air Tempering Tracer ZN520 OnlyFan sequence of operation Fan Mode Operation Rotating ComponentsTracer ZN520 fan configuration Auto fan operation Fan speed defaultContinuous Fan Operation Fan Speed SwitchTracer ZN010 and ZN510 Tracer ZN520Fan Start on High Speed Fan Off DelayFan mode operation, Tracer ZN010 and ZN510 Start-Up Fan Cycling OperationFan operation in heating and cooling modes Entering Water Temperature Sampling FunctionLocal fan switch enabled Two- and Four-Pipe Changeover OperationEconomizer Damper Tracer ZN520 Only Unit mode as related to water temperatureUnit type EWT sensor required? Coil water temperature Electric Heat OperationBinary Inputs BIP1 Low Temperature Detection OptionTracer Dehumidification Tracer ZN520 Only Data Sharing Tracer ZN510 or ZN520 OnlyBIP4 Fan Status ZN520 Only Binary input configurationsBIP2 Condensate Overflow Detection Option BIP3 Occupancy SensorAnalog input Terminal Function Range ZN010 ZN510 ZN520 Analog InputsBinary Outputs Analog inputsZone Sensor Space Temperature MeasurementBinary output configuration Zone sensor wiring connectionsLocal Setpoint Fan Mode SwitchExternal Setpoint Adjustment Fan SwitchCommunication Jack On/Cancel ButtonsMaintenance Procedures MaintenanceTorque in.-lb Ft-lb MaintenanceFan Assembly Set Screws Fan Belt TensionBCBH/BCVC valve package waterflow limits Belt tensionHydronic coil data BCHC/BCVC coil general dataRow coil Steam coil data Unit Motor Motor sheave Fan sheave Belt Drive data1750 1450 Size Watts Browning Trane 60 Hz 50 Hz Steam, Hot Water, and Cooling Coil Cleaning Procedure Coil MaintenancePotential unit damage from coil cleaners Inspecting and Cleaning CoilsRotating parts Periodic Maintenance ChecklistsMaintenance Troubleshooting DiagnosticsLED Activity Manual Output Test Procedure DiagnosticsManual Output Test Fan Cool output a Heat output Damper Steps J1-1, J1-3 DiagnosticsTranslating Multiple Diagnostics Tracer ZN520 test sequenceAutomatic Reset by the Controller Resetting DiagnosticsDiagnostic Reset Tracer ZN510 or ZN520 Only Diagnostics Manual Output TestCycling Power Rover Service ToolDiagnostic Fan Other outputsa Tracer ZN010 and ZN510 controller diagnosticsTracer ZN520 diagnostics Diagnostic Latching Fan Valves Electric heat DamperProbably cause Explanation Common DiagnosticsFan outputs do not energize Valves stay closedElectric heat not operating Valves stay openFresh air damper stays closed DX or electric outputs do not energize Fresh air damper stays openTwo-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Two-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Control Interface Four-Pipe Bcxc with Control Interface Bcxc with DX Coil and Tracer ZN520 Field Installed DeviceBcxc with DX Coil, Hydronic Heating, and Tracer ZN520 BCXC-SVX01B-EN