Trane BCHC, BCVC, BCXC-SVX01B-EN manual Periodic Maintenance Checklists, Rotating parts

Page 70

Maintenance

Winterizing the Coil

Make provisions to drain coils that are not in use, especially when subjected to freezing temperatures.

To drain the coil, first blow out the coil with compressed air. Next, fill and drain the tubes with full- strength ethylene glycol several times. Then drain the coil as completely as possible.

NOTICE

Potential coil-freeze condition!

Make provisions to drain the coil when not in use to prevent coil freeze-up. Failure to follow this procedure could result in equipment damage.

Periodic Maintenance Checklists

Monthly Checklist

The following check list provides the recommended maintenance schedule to keep the unit running efficiently.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

WARNING

Rotating parts!

Secure drive sheaves to ensure motor cannot freewheel. Failure to follow this procedure could result in death, personal injury or equipment damage.

1.Inspect unit air filters. Clean or replace if airflow is blocked or if filters are dirty.

2.Check the condition and tension of fan belts. Adjust tension if belts are floppy or squeal continually. Replace worn or fraying belts in matched sets.

Note: Check and adjust belt tension at least twice daily the first days of new belt operation. Belt tension will rapidly decrease until the belts are run in.

3.Re-lubricate motor bearings, if motor is fitted with oil tubes and operating conditions include moist or dirty air, continuous duty and/or high temperatures.

Semi-Annual Maintenance

1.Verify the fan motor is properly lubricated. Follow lubrication recommendations on the motor tag or nameplate. Contact the motor manufacturer for more information.

2.With power disconnected, manually rotate the fan wheel to check for obstructions in the housing or interference with fan blades. Remove any obstructions and debris.

3.Check the fan assembly sheave alignment. Tighten set screws to their proper torques.

4.Check fan belt tension. Adjust if belt is slipping. Replace if belt is worn or frayed.

5.Inspect the coils for dirt build-up. Clean fins if airflow is clogged.

Annual Maintenance

Check and tighten all set screws, bolts, locking collars and sheaves.

1. Inspect, clean, and tighten all electrical connections and wiring.

70

BCXC-SVX01B-EN

Image 70
Contents Blower Coil Air Handler AprilEnvironmental Concerns Refrigerant warning informationResponsible Refrigerant Practices Hazard of Explosion and Deadly Gases About This Manual TrademarksTable of Contents BCXC-SVX01B-EN Digits 5, 6, 7 Unit Size Digit 16 Motor HorsepowerDigits 1, 2, 3, 4 Unit Model Digit 8 Unit VoltageModel Number Description General Information Blower Coil General InformationGeneral Information Receiving and Handling Pre-InstallationJobsite Storage Recommendations Pre-Installation Installation PreparationService Access Unit size Dimension aImproper Unit Lift Unit Handling ProcedureRigging and Handling Unit Location RecommendationsPre-Installation Checklist Skid RemovalUnit Size RH LH Weight Dimensions and WeightsHorizontal blower coil dimensions in. and weights lb Horizontal Blower CoilUnit Size Weight Dimensions and WeightsVertical blower coil dimensions in. and weights lb Vertical Blower CoilAngle Filter and Mixing Box Angle filter and mixing box dimensions in. and weights lbUnit size Bottom or Top Access Filter Box AIR Flow Filter Filter Access PanelElectric heat dimensions in. and weights lb Electric HeatCoil Connections, NPT Steam coil box dimensions in. and weights lbSteam Coil Supply ReturnDX coil connection sizes, OD Coil ConnectionsHydronic coil connection sizes, OD Steam coil connection sizes, female connection, NPTPiping Packages Basic PipingDimensions and Weights Deluxe Piping Piping Nominal Actual sizeZone Sensor Installation Installation ControlsInstalling Wall Mounted Controls Wiring InstructionsService Communication Wiring Communication WiringInstallation Controls Zone Sensors Without Interconnecting WiringTracer Summit Communication Wiring Installation Electrical Wire size range Max. wiring distance Installation ElectricalZone sensor maximum wiring distances, ft m Electrical Grounding Restrictions Hazardous VoltageAvailable electric heat, min-max kW Useful FormulasUnit size Voltage Motor electrical data 190/50/3 220/50/1240/50/1 380/50/3Bchc Installation Procedure Installation MechanicalInstalling the Unit Horizontal Units, Model BchcInstallation Mechanical Vertical Units, Model BcvcHeating Coil Option Mixing Box OptionLinkage Installation Procedure Mixing Box Installation ProcedureCondensate Drain Connections Recommended drain trap installation for draw-through units Duct ConnectionsPotential coil-freeze condition Installation PipingWater Coil Connections Refrigerant Coil PipingValve Damage Installation PipingSuction Line Field-Installing Evaporator Piping Field-installed evaporation piping exampleGeneral Steam PipingCoil Condensate Steam CoilsType NS steam coils, horizontal tubes for horizontal airflow Control Options Controls InterfaceTracer Controllers Tracer controller input/output summary Rover Service SoftwareControls Interface Tracer controller ZN010 ZN510 ZN520End Device Option Availability Tracer controller function summaryTracer Control Device ZN010 Tracer ZN510 Tracer ZN520 Receiving Pre-Start ChecklistPre-Start Unit LocationUnit Piping Pre-Start Component OverviewDuctwork ElectricalSequence of Operation Start-UpTracer ZN Controller Sequence of Operation Sensor type Sensor position Unit occupancy mode Occupied ModeUnoccupied Mode Start-UpCooling Operation Occupied Standby Mode Tracer ZN510 or ZN520 onlyOccupied Bypass Mode, Tracer ZN510 or ZN520 Only Discharge Air Tempering Tracer ZN520 Only Start-Up Economizer Cooling Tracer ZN520 OnlyDX Cooling Tracer ZN520 only Heating OperationAuto fan operation Fan speed default Fan Mode Operation Rotating ComponentsTracer ZN520 fan configuration Fan sequence of operationTracer ZN520 Fan Speed SwitchTracer ZN010 and ZN510 Continuous Fan OperationStart-Up Fan Cycling Operation Fan Off DelayFan mode operation, Tracer ZN010 and ZN510 Fan Start on High SpeedTwo- and Four-Pipe Changeover Operation Entering Water Temperature Sampling FunctionLocal fan switch enabled Fan operation in heating and cooling modesElectric Heat Operation Unit mode as related to water temperatureUnit type EWT sensor required? Coil water temperature Economizer Damper Tracer ZN520 OnlyData Sharing Tracer ZN510 or ZN520 Only BIP1 Low Temperature Detection OptionTracer Dehumidification Tracer ZN520 Only Binary InputsBIP3 Occupancy Sensor Binary input configurationsBIP2 Condensate Overflow Detection Option BIP4 Fan Status ZN520 OnlyAnalog inputs Analog InputsBinary Outputs Analog input Terminal Function Range ZN010 ZN510 ZN520Zone sensor wiring connections Space Temperature MeasurementBinary output configuration Zone SensorFan Switch Fan Mode SwitchExternal Setpoint Adjustment Local SetpointOn/Cancel Buttons Communication JackMaintenance Maintenance ProceduresFan Belt Tension MaintenanceFan Assembly Set Screws Torque in.-lb Ft-lbBelt tension BCBH/BCVC valve package waterflow limitsHydronic coil data BCHC/BCVC coil general dataRow coil Steam coil data Unit Motor Motor sheave Fan sheave Belt Drive data1750 1450 Size Watts Browning Trane 60 Hz 50 Hz Inspecting and Cleaning Coils Coil MaintenancePotential unit damage from coil cleaners Steam, Hot Water, and Cooling Coil Cleaning ProcedurePeriodic Maintenance Checklists Rotating partsMaintenance Troubleshooting DiagnosticsLED Activity Manual Output Test Procedure DiagnosticsManual Output Test Tracer ZN520 test sequence DiagnosticsTranslating Multiple Diagnostics Fan Cool output a Heat output Damper Steps J1-1, J1-3Resetting Diagnostics Automatic Reset by the ControllerRover Service Tool Diagnostics Manual Output TestCycling Power Diagnostic Reset Tracer ZN510 or ZN520 OnlyDiagnostic Latching Fan Valves Electric heat Damper Tracer ZN010 and ZN510 controller diagnosticsTracer ZN520 diagnostics Diagnostic Fan Other outputsaValves stay closed Common DiagnosticsFan outputs do not energize Probably cause ExplanationElectric heat not operating Valves stay openFresh air damper stays closed Fresh air damper stays open DX or electric outputs do not energizeWiring Diagrams Two-Pipe Bcxc with Tracer ZN510Wiring Diagrams Four-Pipe Bcxc with Tracer ZN510Four-Pipe Bcxc with Tracer ZN510 Two-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Control Interface Four-Pipe Bcxc with Control Interface Field Installed Device Bcxc with DX Coil and Tracer ZN520Bcxc with DX Coil, Hydronic Heating, and Tracer ZN520 BCXC-SVX01B-EN