Trane BCHC, BCVC Field-Installing Evaporator Piping, Field-installed evaporation piping example

Page 40

Installation Piping

Routing. To prevent residual or condensed refrigerant from “free-flowing” toward the compressor, install the suction line so it slopes slightly—1 inch per 10 feet of run [1 cm per 3 m]— toward the evaporator. Avoid putting refrigerant lines underground. Refrigerant condensation, installation debris inside the line, service access, and abrasion/corrosion can quickly impair system reliability.

Insulation. After operating the system and testing all fittings and joints to verify the system is leak-free, insulate the suction lines to prevent heat gain and unwanted condensation.

Components. Installing the suction line requires field installation of these components: an access port and possibly a suction filter. Position them as close to the compressor as possible.

Access port

The access port is used to determine suction pressure and adjust the TEV. It should be located near the external equalizer line connection. This port is usually a Schraeder valve with a core.

Suction filter

If required by the compressor unit, a replaceable-core suction filter is installed as close to the compressor unit as possible. Adding manual, ball-type shutoff valves upstream and downstream of the filter simplifies replacement of the filter core.

Field-Installing Evaporator Piping

See Figure 10 and refer to the instructions below to field-install evaporator piping.

1.Pitch the liquid line slightly—1 in./10 ft [1 cm/3 m]—so that the refrigerant drains toward the evaporator.

2.Provide one expansion valve per distributor.

3.Slightly pitch the outlet line from the suction header toward the suction riser — that is, 1 in./10 ft [1 cm/3 m] in the direction of flow. Use the tube diameter that matches the suction-header connection.

4.For the vertical riser, use the tube diameter recommended by the condensing unit manufacturer. Assure the top of the riser is higher than the evaporator coil.

5.Arrange the suction line so the refrigerant vapor leaving the coil flows downward, below the suction-header outlet, before turning upward.

6.Pitch the suction line slightly—1 in./10 ft [1 cm/3 m]—so the refrigerant drains toward the evaporator.

7.Insulate the suction line.

Figure 10. Field-installed evaporation piping example

 

Evaporator Coil with

 

Standard Circuiting

suction line

 

 

liquid

sight

line

glass

 

thermal

solenoid filter drier

expansion

valve

valve (TXV)

 

distributor

 

40

BCXC-SVX01B-EN

Image 40
Contents Blower Coil Air Handler AprilEnvironmental Concerns Refrigerant warning informationResponsible Refrigerant Practices Hazard of Explosion and Deadly Gases About This Manual TrademarksTable of Contents BCXC-SVX01B-EN Digit 16 Motor Horsepower Digits 1, 2, 3, 4 Unit ModelDigits 5, 6, 7 Unit Size Digit 8 Unit VoltageModel Number Description General Information Blower Coil General InformationGeneral Information Receiving and Handling Pre-InstallationJobsite Storage Recommendations Installation Preparation Service AccessPre-Installation Unit size Dimension aUnit Handling Procedure Rigging and HandlingImproper Unit Lift Unit Location RecommendationsPre-Installation Checklist Skid RemovalDimensions and Weights Horizontal blower coil dimensions in. and weights lbUnit Size RH LH Weight Horizontal Blower CoilDimensions and Weights Vertical blower coil dimensions in. and weights lbUnit Size Weight Vertical Blower CoilAngle Filter and Mixing Box Angle filter and mixing box dimensions in. and weights lbUnit size Bottom or Top Access Filter Box AIR Flow Filter Filter Access PanelElectric heat dimensions in. and weights lb Electric HeatSteam coil box dimensions in. and weights lb Steam CoilCoil Connections, NPT Supply ReturnCoil Connections Hydronic coil connection sizes, ODDX coil connection sizes, OD Steam coil connection sizes, female connection, NPTPiping Packages Basic PipingDimensions and Weights Deluxe Piping Piping Nominal Actual sizeInstallation Controls Installing Wall Mounted ControlsZone Sensor Installation Wiring InstructionsCommunication Wiring Installation ControlsService Communication Wiring Zone Sensors Without Interconnecting WiringTracer Summit Communication Wiring Installation Electrical Installation Electrical Zone sensor maximum wiring distances, ft mWire size range Max. wiring distance Electrical Grounding Restrictions Hazardous VoltageAvailable electric heat, min-max kW Useful FormulasUnit size Voltage Motor electrical data 220/50/1 240/50/1190/50/3 380/50/3Installation Mechanical Installing the UnitBchc Installation Procedure Horizontal Units, Model BchcInstallation Mechanical Vertical Units, Model BcvcHeating Coil Option Mixing Box OptionLinkage Installation Procedure Mixing Box Installation ProcedureCondensate Drain Connections Recommended drain trap installation for draw-through units Duct ConnectionsInstallation Piping Water Coil ConnectionsPotential coil-freeze condition Refrigerant Coil PipingValve Damage Installation PipingSuction Line Field-Installing Evaporator Piping Field-installed evaporation piping exampleSteam Piping Coil CondensateGeneral Steam CoilsType NS steam coils, horizontal tubes for horizontal airflow Control Options Controls InterfaceTracer Controllers Rover Service Software Controls InterfaceTracer controller input/output summary Tracer controller ZN010 ZN510 ZN520End Device Option Availability Tracer controller function summaryTracer Control Device ZN010 Tracer ZN510 Tracer ZN520 Pre-Start Checklist Pre-StartReceiving Unit LocationPre-Start Component Overview DuctworkUnit Piping ElectricalSequence of Operation Start-UpTracer ZN Controller Sequence of Operation Occupied Mode Unoccupied ModeSensor type Sensor position Unit occupancy mode Start-UpCooling Operation Occupied Standby Mode Tracer ZN510 or ZN520 onlyOccupied Bypass Mode, Tracer ZN510 or ZN520 Only Start-Up Economizer Cooling Tracer ZN520 Only DX Cooling Tracer ZN520 onlyDischarge Air Tempering Tracer ZN520 Only Heating OperationFan Mode Operation Rotating Components Tracer ZN520 fan configurationAuto fan operation Fan speed default Fan sequence of operationFan Speed Switch Tracer ZN010 and ZN510Tracer ZN520 Continuous Fan OperationFan Off Delay Fan mode operation, Tracer ZN010 and ZN510Start-Up Fan Cycling Operation Fan Start on High SpeedEntering Water Temperature Sampling Function Local fan switch enabledTwo- and Four-Pipe Changeover Operation Fan operation in heating and cooling modesUnit mode as related to water temperature Unit type EWT sensor required? Coil water temperatureElectric Heat Operation Economizer Damper Tracer ZN520 OnlyBIP1 Low Temperature Detection Option Tracer Dehumidification Tracer ZN520 OnlyData Sharing Tracer ZN510 or ZN520 Only Binary InputsBinary input configurations BIP2 Condensate Overflow Detection OptionBIP3 Occupancy Sensor BIP4 Fan Status ZN520 OnlyAnalog Inputs Binary OutputsAnalog inputs Analog input Terminal Function Range ZN010 ZN510 ZN520Space Temperature Measurement Binary output configurationZone sensor wiring connections Zone SensorFan Mode Switch External Setpoint AdjustmentFan Switch Local SetpointOn/Cancel Buttons Communication JackMaintenance Maintenance ProceduresMaintenance Fan Assembly Set ScrewsFan Belt Tension Torque in.-lb Ft-lbBelt tension BCBH/BCVC valve package waterflow limitsHydronic coil data BCHC/BCVC coil general dataRow coil Steam coil data Unit Motor Motor sheave Fan sheave Belt Drive data1750 1450 Size Watts Browning Trane 60 Hz 50 Hz Coil Maintenance Potential unit damage from coil cleanersInspecting and Cleaning Coils Steam, Hot Water, and Cooling Coil Cleaning ProcedurePeriodic Maintenance Checklists Rotating partsMaintenance Troubleshooting DiagnosticsLED Activity Manual Output Test Procedure DiagnosticsManual Output Test Diagnostics Translating Multiple DiagnosticsTracer ZN520 test sequence Fan Cool output a Heat output Damper Steps J1-1, J1-3Resetting Diagnostics Automatic Reset by the ControllerDiagnostics Manual Output Test Cycling PowerRover Service Tool Diagnostic Reset Tracer ZN510 or ZN520 OnlyTracer ZN010 and ZN510 controller diagnostics Tracer ZN520 diagnosticsDiagnostic Latching Fan Valves Electric heat Damper Diagnostic Fan Other outputsaCommon Diagnostics Fan outputs do not energizeValves stay closed Probably cause ExplanationElectric heat not operating Valves stay openFresh air damper stays closed Fresh air damper stays open DX or electric outputs do not energizeWiring Diagrams Two-Pipe Bcxc with Tracer ZN510Wiring Diagrams Four-Pipe Bcxc with Tracer ZN510Four-Pipe Bcxc with Tracer ZN510 Two-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Control Interface Four-Pipe Bcxc with Control Interface Field Installed Device Bcxc with DX Coil and Tracer ZN520Bcxc with DX Coil, Hydronic Heating, and Tracer ZN520 BCXC-SVX01B-EN