Trane BCHC, BCVC manual Fan Mode Operation Rotating Components, Tracer ZN520 fan configuration

Page 52

Start-Up

heating capacity of the unit (0–100%). The outputs are controlled based on the unit configuration and the required heating capacity.

Fan Mode Operation

WARNING

Rotating Components!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

For multiple fan speed applications, the Tracer™ ZN controller offers additional fan configuration flexibility. See Table 19 for fan operation sequences. Separate default fan speeds for heating and cooling modes can be configured using Rover™ service software.

Table 19. Tracer ZN520 fan configuration

 

Auto fan operation

Fan speed default

 

 

 

Heating

Continuous

Off

 

 

Low

 

 

High

 

 

 

Cooling

Continuous

Off

 

 

Low

 

 

High

 

 

 

The fan runs continuously at selected speeds, high or low. When the fan mode switch is in the auto position or a hardwired fan mode input does not exist, the fan operates at the default configured speed. See Table 20 for Tracer™ ZN520 default fan configuration for heating and cooling modes. During unoccupied mode, the fan cycles between high speed and off with heating and cooling fan modes. If the requested speed is off, the fan always remains off.

Table 20. Fan sequence of operation

Fan speed

Tracer™ ZN controller

Sequence of operation

 

 

 

Off

ZN010, ZN510, ZN520

• fan is off

 

 

• control valves and damper option are closed

 

 

• low air temperature detection open is still active

 

 

Low or high (continuous fan) ZN010, ZN510

• fan operates continuously at selected speed

 

 

2-position control valve option cycle as needed

 

 

2-position control valve option opens to an adjustable mechanical stop-position

 

 

Low or high (continuous fan) ZN520

• fan operates continuously at selected speed

 

 

• modulating control valve option cycles as needed

 

 

 

Auto (cycling)

ZN010, ZN510

• fan, 2-position damper cycle, and control valve cycle as needed

 

 

• in cooling mode, fan cycles from off to high

 

 

• in heating mode, fan cycles from off to low

 

 

• when heating/cooling is not required, the fan is off and the 2-position damper

 

 

option closes

 

 

 

Auto

ZN520

• fan cycles between high and medium, and never turns off unless the controller is

 

 

in unoccupied mode

• modulating or 2-position control open to maintain setpoint

During dehumidification, when the fan is in auto, the fan speed can switch depending on the error. The fan speed increases as the space temperature rises above the active cooling setpoint.

52

BCXC-SVX01B-EN

Image 52
Contents Blower Coil Air Handler AprilEnvironmental Concerns Refrigerant warning informationResponsible Refrigerant Practices Hazard of Explosion and Deadly Gases About This Manual TrademarksTable of Contents BCXC-SVX01B-EN Digit 16 Motor Horsepower Digits 1, 2, 3, 4 Unit ModelDigits 5, 6, 7 Unit Size Digit 8 Unit VoltageModel Number Description General Information Blower Coil General InformationGeneral Information Receiving and Handling Pre-InstallationJobsite Storage Recommendations Installation Preparation Service AccessPre-Installation Unit size Dimension aUnit Handling Procedure Rigging and HandlingImproper Unit Lift Unit Location RecommendationsPre-Installation Checklist Skid RemovalDimensions and Weights Horizontal blower coil dimensions in. and weights lbUnit Size RH LH Weight Horizontal Blower CoilDimensions and Weights Vertical blower coil dimensions in. and weights lbUnit Size Weight Vertical Blower CoilAngle Filter and Mixing Box Angle filter and mixing box dimensions in. and weights lbUnit size Bottom or Top Access Filter Box AIR Flow Filter Filter Access PanelElectric heat dimensions in. and weights lb Electric HeatSteam coil box dimensions in. and weights lb Steam CoilCoil Connections, NPT Supply ReturnCoil Connections Hydronic coil connection sizes, ODDX coil connection sizes, OD Steam coil connection sizes, female connection, NPTPiping Packages Basic PipingDimensions and Weights Deluxe Piping Piping Nominal Actual sizeInstallation Controls Installing Wall Mounted ControlsZone Sensor Installation Wiring InstructionsCommunication Wiring Installation ControlsService Communication Wiring Zone Sensors Without Interconnecting WiringTracer Summit Communication Wiring Installation Electrical Installation Electrical Zone sensor maximum wiring distances, ft mWire size range Max. wiring distance Electrical Grounding Restrictions Hazardous VoltageAvailable electric heat, min-max kW Useful FormulasUnit size Voltage Motor electrical data 220/50/1 240/50/1190/50/3 380/50/3Installation Mechanical Installing the UnitBchc Installation Procedure Horizontal Units, Model BchcInstallation Mechanical Vertical Units, Model BcvcHeating Coil Option Mixing Box OptionLinkage Installation Procedure Mixing Box Installation ProcedureCondensate Drain Connections Recommended drain trap installation for draw-through units Duct ConnectionsInstallation Piping Water Coil ConnectionsPotential coil-freeze condition Refrigerant Coil PipingValve Damage Installation PipingSuction Line Field-Installing Evaporator Piping Field-installed evaporation piping exampleSteam Piping Coil CondensateGeneral Steam CoilsType NS steam coils, horizontal tubes for horizontal airflow Control Options Controls InterfaceTracer Controllers Rover Service Software Controls InterfaceTracer controller input/output summary Tracer controller ZN010 ZN510 ZN520End Device Option Availability Tracer controller function summaryTracer Control Device ZN010 Tracer ZN510 Tracer ZN520 Pre-Start Checklist Pre-StartReceiving Unit LocationPre-Start Component Overview DuctworkUnit Piping ElectricalSequence of Operation Start-UpTracer ZN Controller Sequence of Operation Occupied Mode Unoccupied ModeSensor type Sensor position Unit occupancy mode Start-UpCooling Operation Occupied Standby Mode Tracer ZN510 or ZN520 onlyOccupied Bypass Mode, Tracer ZN510 or ZN520 Only Start-Up Economizer Cooling Tracer ZN520 Only DX Cooling Tracer ZN520 onlyDischarge Air Tempering Tracer ZN520 Only Heating OperationFan Mode Operation Rotating Components Tracer ZN520 fan configurationAuto fan operation Fan speed default Fan sequence of operationFan Speed Switch Tracer ZN010 and ZN510Tracer ZN520 Continuous Fan OperationFan Off Delay Fan mode operation, Tracer ZN010 and ZN510Start-Up Fan Cycling Operation Fan Start on High SpeedEntering Water Temperature Sampling Function Local fan switch enabledTwo- and Four-Pipe Changeover Operation Fan operation in heating and cooling modesUnit mode as related to water temperature Unit type EWT sensor required? Coil water temperatureElectric Heat Operation Economizer Damper Tracer ZN520 OnlyBIP1 Low Temperature Detection Option Tracer Dehumidification Tracer ZN520 OnlyData Sharing Tracer ZN510 or ZN520 Only Binary InputsBinary input configurations BIP2 Condensate Overflow Detection OptionBIP3 Occupancy Sensor BIP4 Fan Status ZN520 OnlyAnalog Inputs Binary OutputsAnalog inputs Analog input Terminal Function Range ZN010 ZN510 ZN520Space Temperature Measurement Binary output configurationZone sensor wiring connections Zone SensorFan Mode Switch External Setpoint AdjustmentFan Switch Local SetpointOn/Cancel Buttons Communication JackMaintenance Maintenance ProceduresMaintenance Fan Assembly Set ScrewsFan Belt Tension Torque in.-lb Ft-lbBelt tension BCBH/BCVC valve package waterflow limitsHydronic coil data BCHC/BCVC coil general dataRow coil Steam coil data Unit Motor Motor sheave Fan sheave Belt Drive data1750 1450 Size Watts Browning Trane 60 Hz 50 Hz Coil Maintenance Potential unit damage from coil cleanersInspecting and Cleaning Coils Steam, Hot Water, and Cooling Coil Cleaning ProcedurePeriodic Maintenance Checklists Rotating partsMaintenance Troubleshooting DiagnosticsLED Activity Manual Output Test Procedure DiagnosticsManual Output Test Diagnostics Translating Multiple DiagnosticsTracer ZN520 test sequence Fan Cool output a Heat output Damper Steps J1-1, J1-3Resetting Diagnostics Automatic Reset by the ControllerDiagnostics Manual Output Test Cycling PowerRover Service Tool Diagnostic Reset Tracer ZN510 or ZN520 OnlyTracer ZN010 and ZN510 controller diagnostics Tracer ZN520 diagnosticsDiagnostic Latching Fan Valves Electric heat Damper Diagnostic Fan Other outputsaCommon Diagnostics Fan outputs do not energizeValves stay closed Probably cause ExplanationElectric heat not operating Valves stay openFresh air damper stays closed Fresh air damper stays open DX or electric outputs do not energizeWiring Diagrams Two-Pipe Bcxc with Tracer ZN510Wiring Diagrams Four-Pipe Bcxc with Tracer ZN510Four-Pipe Bcxc with Tracer ZN510 Two-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Control Interface Four-Pipe Bcxc with Control Interface Field Installed Device Bcxc with DX Coil and Tracer ZN520Bcxc with DX Coil, Hydronic Heating, and Tracer ZN520 BCXC-SVX01B-EN